snmp_mib_archive/cpqdsccs.cfg
Heston Snodgrass 89bf4b016e initial commit
2016-12-15 15:03:18 -07:00

217 lines
7.3 KiB
INI
Executable File

#-MIBFILE: cpqdsccs.mib
CPQDSCCS-MIB DEFINITIONS ::= BEGIN
compaq OBJECT IDENTIFIER ::= { enterprises 232 }
DisplayString ::=
OCTET STRING
PhysAddress ::=
OCTET STRING
mib-2 OBJECT IDENTIFIER ::= { mgmt 1 }
system OBJECT IDENTIFIER ::= { mib-2 1 }
sysName OBJECT IDENTIFIER ::= { system 5 }
mib-2 OBJECT IDENTIFIER ::= { mgmt 1 }
sysDescr OBJECT IDENTIFIER ::= { system 1 }
sysContact OBJECT IDENTIFIER ::= { system 4 }
sysLocation OBJECT IDENTIFIER ::= { system 6 }
cpqDsccs OBJECT IDENTIFIER ::= { compaq 171 }
dsccsTrapInfo OBJECT IDENTIFIER ::= { cpqDsccs 1 }
csRoomName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The location of the room."
::= { dsccsTrapInfo 1 }
csContactName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The contact person name."
::= { dsccsTrapInfo 2 }
csContactPhoneNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The contact person phone number."
::= { dsccsTrapInfo 3 }
csProductName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..25))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The product name: Dynamic Smart Cooling."
::= { dsccsTrapInfo 4 }
csProductId OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..10))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The product ID."
::= { dsccsTrapInfo 5 }
csSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..10))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The product serial number."
::= { dsccsTrapInfo 6 }
csSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The product software version."
::= { dsccsTrapInfo 7 }
trapEventId OBJECT-TYPE
SYNTAX INTEGER {
webGuiDscAutoMode(1001),
webGuiDscMonitoringMode(1002),
webGuiDscEmergencyOverrideMode(1003),
webGuiDscOff(1004),
webGuiUserLoggedIn(1005),
webGuiUserLoggedOut(1006),
webGuiUserSessionExpired(1007),
ctrlMasterSensorTempAboveAcceptBand(2001),
ctrlOrphanSensorTempAboveAcceptBand(2002),
ctrlTempSensorAboveAcceptBand(2003),
ctrlRegionInfluenceAhuNoSensors(2004),
ctrlNoTciDataForSensorAndAhu(2005),
ctrlTciDataExistsForSensorsRemovedFromDsc(2006),
ctrlSensorTimestampOld(2007),
ctrlAhuOff(2008),
ctrlStarted(2009),
ctrlStopped(2010),
commisFullStartedByUser(3001),
commisPartialStartedByUserForAhu(3002),
commisAbortedByUseer(3003),
commisFinishedSuccessfully(3004),
commisFailedSupplyAirTempForAhuDidNotChange(3005),
commisFailedCouldNotChangeAhuSetPoint(3006),
commisFailedDataCenterTempExceedThresholdLimit(3007),
commisCannotPerformOperation(3008),
commisLoadingConfigProfile(3009),
commisLoadingPropertiesForConfigProfile(3010),
commisLoadingConfigParamForProfile(3011),
commisPerformCheckForAhusInConfigProfile(3012),
commisInitSubsystemForConfigProfile(3013),
commisInitSubsystemForCOnfigProfileAndInstance(3014),
commisStartingForConfigProfile(3015),
commisBeginInitCycle(3016),
commisProcessCompletedSuccessfullyForConfiguration(3017),
commisHaltActiveCommmissioningExecution(3018),
commisExecutionFailedForConfiguration(3019),
commisPerformPerturbationForInitDistributionLevel(3020),
commisPerformPerturbationForAhu(3021),
commisAttestSystemPerturbationForAhu(3022),
commisAssertionFailedForAhuFeedbackOnTest(3023),
commisWaitingForSystemSteadinessFromSensorNetwork(3024),
commisValidatingAhuSupplyAirTempHasChanged(3025),
commisStoreSensorNetworkStateAndDataForPerturbation(3026),
commisStoreBasecaseSensorTempAndData(3027),
commisStoreSystemPerturbationSensorTempAndData(3028),
commisMergeDataForConfig(3029),
commisRollbackAndCleanFromDatabaseChanges(3030),
commisInitDefaultConfigProfiles(3031),
commisAhuPerturbationWithinConfig(3032),
commisCannotPerformMergeOpWhenRunningCommissioning(3033),
commisCannotHaltCommissioningNoActiveInstanceRunning(3034),
commisBeginExecutionCycleSettingAhuToConfiguredLevels(3035),
commisSettingAhusToUniformDistributionLevel(3036),
commuOpcCommunicationsLost(4001),
commuMbcHostIsUnreachablePingFailed(4002),
commuOpcStatus(4003),
commuTempForSensorOutOfRange(4004),
commuFailsafeDeviceHeartbeatNotPresent(4005),
commuReverseAirFlowDetectedInRack(4006),
commuAhuSupplyAirTempReachedHighLimit(4007),
commuAhuSupplyAirTempReachedLowLimit(4008),
commuAhuReturnAirTempReachedHighLimit(4009),
commuAhuReturnAirTempReachedLowLimit(4010),
commuAhuPoweredOff(4011),
commuAhuFluidLeakDetected(4012),
commuAhuSwitchedToLocalControl(4013),
commuSensorTimestampOld(4014),
internalSoftwareUnhandledException(6001),
other(7001)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "The event ID."
::= { dsccsTrapInfo 8 }
trapDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The description of the event that generates the trap."
::= { dsccsTrapInfo 9 }
trapDscTest TRAP-TYPE
ENTERPRISE cpqDsccs
VARIABLES { sysName, csRoomName, csContactName, csContactPhoneNumber, csProductName, csProductId, csSerialNumber, csSoftwareVersion, trapEventId, trapDescription }
--#TYPE "Test Trap"
--#SUMMARY "Test Trap for %s, id = %s, description = %s"
--#ARGUMENTS {0, 8, 9}
--#SEVERITY INFORMATIONAL
--#CATEGORY "Cpqdsccs"
--#MSG_FORMATTER "$V1V#System Name: # $V7V#Serial Number: # $V9V#Trap id: # $V10V#Trap Description: #"
DESCRIPTION "Test trap sent to a trap receiver to check proper reception of traps"
::= 1
trapDscCritical TRAP-TYPE
ENTERPRISE cpqDsccs
VARIABLES { sysName, csRoomName, csContactName, csContactPhoneNumber, csProductName, csProductId, csSerialNumber, csSoftwareVersion, trapEventId, trapDescription }
--#TYPE "Critical Alarm"
--#SUMMARY "Critical Alarm for %s, id = %s, description = %s"
--#ARGUMENTS {0, 8, 9}
--#SEVERITY CRITICAL
--#CATEGORY "Cpqdsccs"
--#MSG_FORMATTER "$V1V#System Name: # $V7V#Serial Number: # $V9V#Trap id: # $V10V#Trap Description: #"
DESCRIPTION "A critical alarm has occurred. Action: Check the Trap Description for more information."
::= 2
trapDscWarning TRAP-TYPE
ENTERPRISE cpqDsccs
VARIABLES { sysName, csRoomName, csContactName, csContactPhoneNumber, csProductName, csProductId, csSerialNumber, csSoftwareVersion, trapEventId, trapDescription }
--#TYPE "Warning Alarm"
--#SUMMARY "Warning Alarm for %s, id = %s, description = %s"
--#ARGUMENTS {0, 8, 9}
--#SEVERITY WARNING
--#CATEGORY "Cpqdsccs"
--#MSG_FORMATTER "$V1V#System Name: # $V7V#Serial Number: # $V9V#Trap id: # $V10V#Trap Description: #"
DESCRIPTION "A warning alarm has occurred. Action: Check the Trap Description for more information."
::= 3
trapDscInformation TRAP-TYPE
ENTERPRISE cpqDsccs
VARIABLES { sysName, csRoomName, csContactName, csContactPhoneNumber, csProductName, csProductId, csSerialNumber, csSoftwareVersion, trapEventId, trapDescription }
--#TYPE "Information Alarm"
--#SUMMARY "Information Alarm for %s, id = %s, description = %s"
--#ARGUMENTS {0, 8, 9}
--#SEVERITY INFORMATIONAL
--#CATEGORY "Cpqdsccs"
--#MSG_FORMATTER "$V1V#System Name: # $V7V#Serial Number: # $V9V#Trap id: # $V10V#Trap Description: #"
DESCRIPTION "An informational alarm has occurred. Action: Check the Trap Description for more information."
::= 4
END