-- Console Management Controller- (CMC) MIB
-- Management Information Base for SNMP Network Management
--
--
-- Copyright 2000,2003 Hewlett-Packard Development Company, L.P.
--
-- Hewlett-Packard Company shall not be liable for technical or
-- editorial errors or omissions contained herein. The information in
-- this document is provided "as is" without warranty of any kind and
-- is subject to change without notice. The warranties for HP products
-- are set forth in the express limited warranty statements
-- accompanying such products. Nothing herein should be construed as
-- constituting an additional warranty.
--
-- Confidential computer software. Valid license from HP required for
-- possession, use or copying. Consistent with FAR 12.211 and 12.212,
-- Commercial Computer Software, Computer Software Documentation, and
-- Technical Data for Commercial Items are licensed to the U.S.
-- Government under vendor's standard commercial license.
--
-- Refer to the READMIB.RDM file for more information about the
-- organization of the information in the Compaq Enterprise.
--
-- The Compaq Enterprise number is 232.
-- The ASN.1 prefix to, and including the Compaq Enterprise is:
-- 1.3.6.1.4.1.232
--
-- MIB Version 1.2
-- *********************************************************************
-- Release History
-- Date: May 1, 2003 (version 1.2)
-- Revised by M. Spence, changed version to 1.2 to follow standard conventions
-- no functional changes between 1.11 and 1.2
-- Date: April 14, 2003 (version 1.11)
-- Revised by M. Spence, Fixed more Trap Descriptions that were incorrect.
-- Date: February 17, 2003 (Version 1.11)
-- Revised by M. Spence, Enhance Trap Descriptions
-- Fixed incorrect variable in Trap 153018
--
-- Date: December 19, 2000 (Version 1.1)
-- Revised by M. Hain, included door locking device
--
-- Date: October 17, 2000 (Version 1.0)
-- Revised by M. Hain
-- *********************************************************************
-- Note: To use this MIB in a Trap Receiver application without CPQHOST.MIB, you must
-- remove the "compaq" line from the IMPORTS section and uncomment the line that defines
-- the "compaq" enterprise as 232.
CPQCMC-MIB DEFINITIONS ::= BEGIN
IMPORTS
compaq FROM CPQHOST-MIB
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
sysName FROM RFC1213-MIB
sysContact FROM RFC1213-MIB
sysLocation FROM RFC1213-MIB
sysDescr FROM RFC1213-MIB
TRAP-TYPE FROM RFC-1215;
-- Uncomment the next line if you are not using the CPQHOST.MIB.
-- compaq OBJECT IDENTIFIER ::= { enterprises 232 }
cpqCmc OBJECT IDENTIFIER ::= { compaq 153 }
cpqCmcMibRev OBJECT IDENTIFIER ::= { cpqCmc 1 }
cpqCmcComponent OBJECT IDENTIFIER ::= { cpqCmc 2 }
cpqCmcInterface OBJECT IDENTIFIER ::= { cpqCmcComponent 1 }
cpqCmcOsCommon OBJECT IDENTIFIER ::= { cpqCmcInterface 1 }
cpqCmcDevice OBJECT IDENTIFIER ::= { cpqCmcComponent 2 }
cpqCmcSetup OBJECT IDENTIFIER ::= { cpqCmcDevice 2 }
cpqCmcSetupConfig OBJECT IDENTIFIER ::= { cpqCmcSetup 1 }
cpqCmcSetupGeneral OBJECT IDENTIFIER ::= { cpqCmcSetupConfig 1 }
cpqCmcSetupEvents OBJECT IDENTIFIER ::= { cpqCmcSetupConfig 2 }
cpqCmcSetupTemp1 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 1}
cpqCmcSetupTemp2 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 2}
cpqCmcSetupFan1 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 3}
cpqCmcSetupFan2 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 4}
cpqCmcSetupVoltage OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 5}
cpqCmcSetupHumidity OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 6}
cpqCmcSetupInput1 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 7}
cpqCmcSetupInput2 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 8}
cpqCmcSetupInput3 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 9}
cpqCmcSetupInput4 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 10}
cpqCmcSetupLock1 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 11}
cpqCmcSetupLock2 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 12}
cpqCmcSetupSmoke OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 13}
cpqCmcSetupShock OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 14}
cpqCmcSetupAux1 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 15}
cpqCmcSetupAux2 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 16}
cpqCmcSetupAlarm1 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 17}
cpqCmcSetupAlarm2 OBJECT IDENTIFIER ::= { cpqCmcSetupEvents 18}
cpqCmcSetupClock OBJECT IDENTIFIER ::= { cpqCmcSetupConfig 3 }
cpqCmcSetupThreshold OBJECT IDENTIFIER ::= { cpqCmcSetup 2 }
cpqCmcTraps OBJECT IDENTIFIER ::= { cpqCmcSetup 3 }
cpqCmcValues OBJECT IDENTIFIER ::= { cpqCmcDevice 3 }
cpqCmcStatus OBJECT IDENTIFIER ::= { cpqCmcDevice 4 }
cpqCmcControl OBJECT IDENTIFIER ::= { cpqCmcDevice 5 }
cpqCmcLog OBJECT IDENTIFIER ::= { cpqCmcDevice 6 }
--*****************************************************************************
--CMC ConsoleManagementController
--*****************************************************************************
--cpqCmcMibRev-group
cpqCmcMibRevMajor OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Major Revision level.
A change in the major revision level represents a major change
in the architecture of the MIB. A change in the major revision
level may indicate a significant change in the information,
correct interpretation of data may require a MIB document
with the same major revision level."
::= { cpqCmcMibRev 1 }
cpqCmcMibRevMinor OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Minor Revision level.
A change in the minor revision level may represent some minor
additional support, no changes to any pre-existing information
has occurred."
::= { cpqCmcMibRev 2 }
cpqCmcMibCondition OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
degraded (3),
failed (4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The overall condition (status) of the system (rack(s)) represented by
this MIB.
(2) OK
(3) a minor problem, warning condition (yellow LED on CMC)
(4) a major problem (red LED on CMC)"
::= { cpqCmcMibRev 3 }
--********************************************************************************
-- cpqCmcOsCommon-group
cpqCmcOsCommonPollFreq OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Insight Agent's polling frequency.
The frequency, in seconds, at which the Insight Agent requests
information from the device driver. A frequency of zero (0)
indicates that the Insight Agent retrieves the information upon
request of a management station, it does not poll the device
driver at a specific interval."
::= { cpqCmcOsCommon 1 }
--********************************************************************************
--cpqCmcDevice-group
cpqCmcDeviceCondition OBJECT-TYPE
SYNTAX INTEGER {
other(1),
ok (2),
overloadDC(3),
fuseDC(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Condition of CMC device,
(3) an overload of the 24V DC supply to the connected accessories occurred
(4) the overload-protection (fuse) has released "
::= { cpqCmcDevice 1 }
--********************************************************************************
--cpqCmcSetupGeneral-group
cpqCmcsetLanguage OBJECT-TYPE
SYNTAX INTEGER {
other(1),
english(2),
french(3),
italian(4),
german(5),
spanish(6),
dutch(7),
japanese(8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Language of LCD"
::= { cpqCmcSetupGeneral 1 }
cpqCmcsetTempUnit OBJECT-TYPE
SYNTAX INTEGER {
other(1),
celsius(2),
fahrenheit(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unit of all temperature values and thresholds, Celsius or Fahrenheit"
::= { cpqCmcSetupGeneral 2 }
cpqCmcsetAudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enableSilence(2),
disableSilence(3),
off(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Audible alarm in CMC unit:
(2): silencing with button on CMC is enabled
(3): silencing with button on CMC is disabled
(4): audible alarm is off (general).
On/off of audible alarm for each event is possible in cpqCmcsetupEvents-group"
::= { cpqCmcSetupGeneral 3 }
cpqCmcPassword OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..6))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Password to get access to terminal or LCD"
::= { cpqCmcSetupGeneral 4 }
cpqCmcPasswordOption OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable password entry to get access to terminal or LCD"
::= { cpqCmcSetupGeneral 5 }
cpqCmcquitRelay1 OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable acknowledging currently active alarm relay 1
(with 'ENTER' on CMC)."
::= { cpqCmcSetupGeneral 6 }
cpqCmcquitRelay2 OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable acknowledging currently active alarm relay 2
(with 'ENTER' on CMC)."
::= { cpqCmcSetupGeneral 7 }
cpqCmclogicRelay1 OBJECT-TYPE
SYNTAX INTEGER {
other(1),
closeAtAlarm(2),
openAtAlarm(3),
closeAtEPO(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Logic of Relay 1: (2) Relay will pick up in case of an alarm
(3) Relay will release in case of an alarm
(4) not used"
::= { cpqCmcSetupGeneral 8 }
cpqCmclogicRelay2 OBJECT-TYPE
SYNTAX INTEGER {
other(1),
closeAtAlarm(2),
openAtAlarm(3),
closeAtEPO(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Logic of Relay 2: (2) Relay will pick up in case of an alarm
(3) Relay will release in case of an alarm
(4) not used"
::= { cpqCmcSetupGeneral 9 }
--*****************************************************************************
-- cpqCmcSetupEvents-group
-- cpqCmcSetupTemp1-group
cpqCmcSetupTemp1Avail OBJECT-TYPE
SYNTAX INTEGER {
other (1),
available (2),
notAvailable (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Temperature sensor:
(2) sensor available
(3) sensor not available"
::= { cpqCmcSetupTemp1 1 }
cpqCmcSetupTemp1RelaysWarn OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of warning condition
of temperature sensor 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupTemp1 2 }
cpqCmcSetupTemp1RelaysMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of max. alarm condition
of temperature sensor 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupTemp1 3 }
cpqCmcSetupTemp1RelaysMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of min. alarm condition
of temperature sensor 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupTemp1 4 }
cpqCmcSetupTemp1AudibleAlarmWarn OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of warning condition
of temperature sensor 1:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupTemp1 5 }
cpqCmcSetupTemp1AudibleAlarmMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of max. alarm condition
of temperature sensor 1:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupTemp1 6 }
cpqCmcSetupTemp1AudibleAlarmMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of min. alarm condition
of temperature sensor 1:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupTemp1 7 }
-- cpqCmcSetupTemp2-group
cpqCmcSetupTemp2Avail OBJECT-TYPE
SYNTAX INTEGER {
other (1),
available (2),
notAvailable (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Temperature sensor:
(2) sensor available
(3) sensor not available"
::= { cpqCmcSetupTemp2 1 }
cpqCmcSetupTemp2RelaysWarn OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of warning condition
of temperature sensor 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupTemp2 2 }
cpqCmcSetupTemp2RelaysMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of max. alarm condition
of temperature sensor 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupTemp2 3 }
cpqCmcSetupTemp2RelaysMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of min. alarm condition
of temperature sensor 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupTemp2 4 }
cpqCmcSetupTemp2AudibleAlarmWarn OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of warning condition
of temperature sensor 2:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupTemp2 5 }
cpqCmcSetupTemp2AudibleAlarmMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of max. alarm condition
of temperature sensor 2:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupTemp2 6 }
cpqCmcSetupTemp2AudibleAlarmMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of min. alarm condition
of temperature sensor 2:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupTemp2 7 }
-- cpqCmcSetupFan1-group
cpqCmcSetupFan1Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan 1:
(2) Fan 1 available
(3) Fan 1 not available"
::= { cpqCmcSetupFan1 1 }
cpqCmcSetupFan1Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of alarm condition
of Fan 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupFan1 2 }
cpqCmcSetupFan1AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of alarm condition
of Fan 1:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupFan1 3 }
-- cpqCmcSetupFan2-group
cpqCmcSetupFan2Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan 2:
(2) Fan 2 available
(3) Fan 2 not available"
::= { cpqCmcSetupFan2 1 }
cpqCmcSetupFan2Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of alarm condition
of Fan 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupFan2 2 }
cpqCmcSetupFan2AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of alarm condition
of Fan 2:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupFan2 3 }
-- cpqCmcSetupVoltage-group
cpqCmcSetupVoltageAvail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Voltage monitoring:
(2) available
(3) not available"
::= { cpqCmcSetupVoltage 1 }
cpqCmcSetupVoltageRelaysMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of max. alarm condition
of voltage monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupVoltage 2 }
cpqCmcSetupVoltageRelaysMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of min. alarm condition
of voltage monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupVoltage 3 }
cpqCmcSetupVoltageAudibleAlarmMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of max. alarm condition
of voltage monitoring:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupVoltage 4 }
cpqCmcSetupVoltageAudibleAlarmMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of min. alarm condition
of voltage monitoring:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupVoltage 5 }
-- cpqCmcSetupHumidity-group
cpqCmcSetupHumidityAvail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Humidity sensor:
(2) available
(3) not available"
::= { cpqCmcSetupHumidity 1 }
cpqCmcSetupHumidityRelaysMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of max. alarm condition
of humidity monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupHumidity 2 }
cpqCmcSetupHumidityRelaysMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of min. alarm condition
of humidity monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupHumidity 3 }
cpqCmcSetupHumidityAudibleAlarmMax OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of max. alarm condition
of humidity monitoring:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupHumidity 4 }
cpqCmcSetupHumidityAudibleAlarmMin OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of min. alarm condition
of humidity monitoring:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupHumidity 5 }
-- cpqCmcSetupInput1-group
cpqCmcSetupInput1Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input 1 sensor:
(2) available
(3) not available"
::= { cpqCmcSetupInput1 1 }
cpqCmcSetupInput1Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of a warning condition
of Input 1 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupInput1 2 }
cpqCmcSetupInput1AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of a warning condition
of Input 1 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupInput1 3 }
cpqCmcSetupInput1FansOff OBJECT-TYPE
SYNTAX INTEGER {
other(1),
both(2),
fan1(3),
fan2(4),
noFan(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan switching off if Door/Sidewall 1 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched off"
::= { cpqCmcSetupInput1 4 }
cpqCmcSetupInput1ShockSensor OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
on(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Shock sensor function if Door/Sidewall 1 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)"
::= { cpqCmcSetupInput1 5 }
cpqCmcSetupInput1Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of Input1"
::= { cpqCmcSetupInput1 6 }
cpqCmcSetupInput1Lock OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
lock1(3),
lock2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Door/Sidewall 1 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devices"
::= { cpqCmcSetupInput1 7 }
-- cpqCmcSetupInput2-group
cpqCmcSetupInput2Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input 2 sensor:
(2) available
(3) not available"
::= { cpqCmcSetupInput2 1 }
cpqCmcSetupInput2Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of a warning condition
of Input 2 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupInput2 2 }
cpqCmcSetupInput2AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of a warning condition
of Input 2 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupInput2 3 }
cpqCmcSetupInput2FansOff OBJECT-TYPE
SYNTAX INTEGER {
other(1),
both(2),
fan1(3),
fan2(4),
noFan(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan switching off if Door/Sidewall 2 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched off"
::= { cpqCmcSetupInput2 4 }
cpqCmcSetupInput2ShockSensor OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
on(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Shock sensor function if Door/Sidewall 2 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)"
::= { cpqCmcSetupInput2 5 }
cpqCmcSetupInput2Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of Input2"
::= { cpqCmcSetupInput2 6 }
cpqCmcSetupInput2Lock OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
lock1(3),
lock2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Door/Sidewall 2 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devices"
::= { cpqCmcSetupInput2 7 }
-- cpqCmcSetupInput3-group
cpqCmcSetupInput3Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input 3 sensor:
(2) available
(3) not available"
::= { cpqCmcSetupInput3 1 }
cpqCmcSetupInput3Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of a warning condition
of Input 3 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupInput3 2 }
cpqCmcSetupInput3AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of a warning condition
of Input 3 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupInput3 3 }
cpqCmcSetupInput3FansOff OBJECT-TYPE
SYNTAX INTEGER {
other(1),
both(2),
fan1(3),
fan2(4),
noFan(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan switching off if Door/Sidewall 3 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched off"
::= { cpqCmcSetupInput3 4 }
cpqCmcSetupInput3ShockSensor OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
on(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Shock sensor function if Door/Sidewall 3 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)"
::= { cpqCmcSetupInput3 5 }
cpqCmcSetupInput3Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of Input3"
::= { cpqCmcSetupInput3 6 }
cpqCmcSetupInput3Lock OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
lock1(3),
lock2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Door/Sidewall 3 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devices"
::= { cpqCmcSetupInput3 7 }
-- cpqCmcSetupInput4-group
cpqCmcSetupInput4Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input 4 sensor:
(2) available
(3) not available"
::= { cpqCmcSetupInput4 1 }
cpqCmcSetupInput4Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of a warning condition
of Input 4 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupInput4 2 }
cpqCmcSetupInput4AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of a warning condition
of Input 4 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupInput4 3 }
cpqCmcSetupInput4FansOff OBJECT-TYPE
SYNTAX INTEGER {
other(1),
both(2),
fan1(3),
fan2(4),
noFan(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan switching off if Door/Sidewall 4 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched off"
::= { cpqCmcSetupInput4 4 }
cpqCmcSetupInput4ShockSensor OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
on(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Shock sensor function if Door/Sidewall 4 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)"
::= { cpqCmcSetupInput4 5 }
cpqCmcSetupInput4Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of Input4"
::= { cpqCmcSetupInput4 6 }
cpqCmcSetupInput4Lock OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
lock1(3),
lock2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Door/Sidewall 4 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devices"
::= { cpqCmcSetupInput4 7 }
-- cpqCmcSetupLock1-group
cpqCmcSetupLock1Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Door locking device 1:
(2) device available
(3) device not available, no alarm, if door is not locked"
::= { cpqCmcSetupLock1 1 }
cpqCmcSetupLock1Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Lock 1 (door not locked..):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupLock1 2 }
cpqCmcSetupLock1RelaysDevice OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Locking device 1 (power fail, low battery...):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupLock1 3 }
cpqCmcSetupLock1AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Lock 1:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupLock1 4 }
cpqCmcSetupLock1AudibleAlarmDevice OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Locking device 1 (power fail, low battery..):
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupLock1 5 }
cpqCmcSetupLock1Time OBJECT-TYPE
SYNTAX INTEGER (3..600)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time in seconds while the lock 1 is unlocked
after getting an unlock-command"
::= { cpqCmcSetupLock1 6 }
cpqCmcSetupLock1PwrFailUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of power fail of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock1 7 }
cpqCmcSetupLock1BattLowUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of low battery of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock1 8 }
cpqCmcSetupLock1NetFailUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of network failure:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock1 9 }
cpqCmcSetupLock1LifeFailUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of lifecheck failure (connection CMC<->locking device):
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock1 10 }
-- cpqCmcSetupLock2-group
cpqCmcSetupLock2Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Door locking device 2:
(2) device available
(3) device not available, no alarm, if door is not locked"
::= { cpqCmcSetupLock2 1 }
cpqCmcSetupLock2Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Lock 2 (door not locked..):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupLock2 2 }
cpqCmcSetupLock2RelaysDevice OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Locking device 2 (power fail, low battery...):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupLock2 3 }
cpqCmcSetupLock2AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Lock 2:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupLock2 4 }
cpqCmcSetupLock2AudibleAlarmDevice OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Locking device 2 (power fail, low battery..):
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupLock2 5 }
cpqCmcSetupLock2Time OBJECT-TYPE
SYNTAX INTEGER (3..600)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time in seconds while the lock 2 is unlocked
after getting an unlock-command"
::= { cpqCmcSetupLock2 6 }
cpqCmcSetupLock2PwrFailUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of power fail of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock2 7 }
cpqCmcSetupLock2BattLowUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of low battery of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock2 8 }
cpqCmcSetupLock2NetFailUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of network failure:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock2 9 }
cpqCmcSetupLock2LifeFailUnlock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disabled (2),
auto (3),
manual (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unlock door in case of lifecheck failure (connection CMC<->locking device):
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signal"
::= { cpqCmcSetupLock2 10 }
-- cpqCmcSetupSmoke-group
cpqCmcSetupSmokeAvail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Smoke sensor:
(2) available
(3) not available"
::= { cpqCmcSetupSmoke 1 }
cpqCmcSetupSmokeRelays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Smoke Sensor:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupSmoke 2 }
cpqCmcSetupSmokeAudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Smoke Sensor:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupSmoke 3 }
cpqCmcSetupSmokeFansOff OBJECT-TYPE
SYNTAX INTEGER {
other(1),
both(2),
fan1(3),
fan2(4),
noFan(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan switching off if in case of smoke-alarm:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched off"
::= { cpqCmcSetupSmoke 4 }
cpqCmcSetupSmokeUnlock OBJECT-TYPE
SYNTAX INTEGER {
other(1),
both(2),
lock1(3),
lock2(4),
noLock(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lock is unlocked in case of smoke-alarm:
(2) both locks will be unlocked
(3) only lock1 will be unlocked
(4) only lock2 will be unlocked
(5) no lock will be unlocked"
::= { cpqCmcSetupSmoke 5 }
-- cpqCmcSetupShock-group
cpqCmcSetupShockAvail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Shock sensor:
(2) available
(3) not available"
::= { cpqCmcSetupShock 1 }
cpqCmcSetupShockRelays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Shock Sensor:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupShock 2 }
cpqCmcSetupShockAudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Shock Sensor:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupShock 3 }
cpqCmcSetupShockSensitivity OBJECT-TYPE
SYNTAX INTEGER (1..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Sensitivity of shock-sensor.
1 = low sensitivity, 10 = high sensitivity"
::= { cpqCmcSetupShock 4 }
-- cpqCmcSetupAux1-group
cpqCmcSetupAux1Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Aux 1 sensor:
(2) available
(3) not available"
::= { cpqCmcSetupAux1 1 }
cpqCmcSetupAux1Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Aux 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupAux1 2 }
cpqCmcSetupAux1AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Aux 1:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupAux1 3 }
cpqCmcSetupAux1InputType OBJECT-TYPE
SYNTAX INTEGER {
other(1),
normOpen(2),
normClosed(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Type of other digital input (used for any digital signal):
(2) contact is normally open, no alarm if contact is open,
alarm if contact is closed
(3) contact is normally closed, no alarm if contact is closed,
alarm if contact is open"
::= { cpqCmcSetupAux1 4 }
cpqCmcSetupAux1Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of the digital input (Aux1) "
::= { cpqCmcSetupAux1 5 }
cpqCmcSetupAux1Unlock OBJECT-TYPE
SYNTAX INTEGER {
other(1),
noLock(2),
lock1(3),
lock2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lock will be unlocked with Aux-Input 1:
(2) no lock will be unlocked
(3) only lock1 will be unlocked
(4) only lock2 will be unlocked
(5) both locks will be unlocked"
::= { cpqCmcSetupAux1 6 }
-- cpqCmcSetupAux2-group
cpqCmcSetupAux2Avail OBJECT-TYPE
SYNTAX INTEGER {
other(1),
available(2),
notAvailable(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Aux 2 sensor:
(2) available
(3) not available"
::= { cpqCmcSetupAux2 1 }
cpqCmcSetupAux2Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Aux 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupAux2 2 }
cpqCmcSetupAux2AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Aux 2:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupAux2 3 }
cpqCmcSetupAux2InputType OBJECT-TYPE
SYNTAX INTEGER {
other(1),
normOpen(2),
normClosed(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Type of other digital input (used for any digital signal):
(2) contact is normally open, no alarm if contact is open,
alarm if contact is closed
(3) contact is normally closed, no alarm if contact is closed,
alarm if contact is open"
::= { cpqCmcSetupAux2 4 }
cpqCmcSetupAux2Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of the digital input (Aux2) "
::= { cpqCmcSetupAux2 5 }
cpqCmcSetupAux2Unlock OBJECT-TYPE
SYNTAX INTEGER {
other(1),
noLock(2),
lock1(3),
lock2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lock will be unlocked with Aux-Input 2:
(2) no lock will be unlocked
(3) only lock1 will be unlocked
(4) only lock2 will be unlocked
(5) both locks will be unlocked"
::= { cpqCmcSetupAux2 6 }
-- cpqCmcSetupAlarm1-group
-- alarm can be set, see cpqCmcSetAlarm1
cpqCmcSetupAlarm1Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Alarm 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupAlarm1 1 }
cpqCmcSetupAlarm1AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Alarm 1:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupAlarm1 2 }
cpqCmcSetupAlarm1Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of alarm 1"
::= { cpqCmcSetupAlarm1 3 }
-- cpqCmcSetupAlarm2-group
-- alarm can be set, see cpqCmcSetAlarm2
cpqCmcSetupAlarm2Relays OBJECT-TYPE
SYNTAX INTEGER {
other(1),
off(2),
relay1(3),
relay2(4),
both(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Alarm Relays in case of an alarm condition
of Alarm 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switch"
::= { cpqCmcSetupAlarm2 1 }
cpqCmcSetupAlarm2AudibleAlarm OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alert handling of Audible Alarm of in case of an alarm condition
of Alarm 2:
(2) Start Audible Alarm
(3) No Audible Alarm"
::= { cpqCmcSetupAlarm2 2 }
cpqCmcSetupAlarm2Description OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..18))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text of alarm 2"
::= { cpqCmcSetupAlarm2 3 }
--*****************************************************************************
-- cpqCmcSetupClock
cpqCmcSetupDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"actual Date in format DD.MM.YYYY"
::= { cpqCmcSetupClock 1 }
cpqCmcSetupTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)"
::= { cpqCmcSetupClock 2 }
--*****************************************************************************
-- cpqCmcSetupThreshold-group
cpqCmcThresholdMaxTemp1 OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold value maximum temperature 1"
::= { cpqCmcSetupThreshold 1 }
cpqCmcThresholdWarningTemp1 OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold value warning temperature 1"
::= { cpqCmcSetupThreshold 2 }
cpqCmcThresholdMinTemp1 OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold value minimum temperature 1"
::= { cpqCmcSetupThreshold 3 }
cpqCmcThresholdMaxTemp2 OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold value maximum temperature 2"
::= { cpqCmcSetupThreshold 4 }
cpqCmcThresholdWarningTemp2 OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold value warning temperature 2"
::= { cpqCmcSetupThreshold 5 }
cpqCmcThresholdMinTemp2 OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold value minimum temperature 2"
::= { cpqCmcSetupThreshold 6 }
cpqCmcThresholdFan1 OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold Fan 1 in deg F or deg C, Fan 1 will start
if temperature 1 exceeds this value"
::= { cpqCmcSetupThreshold 7 }
cpqCmcThresholdFan1Hysteresis OBJECT-TYPE
SYNTAX INTEGER (1..20)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hystersis of Fan 1, Fan 1 will stop if temperature 1 falls below
value of cpqCmcThresholdFan1 minus cpqCmcThresholdFan1Hysteresis"
::= { cpqCmcSetupThreshold 8 }
cpqCmcThresholdFan2 OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold Fan 2 in deg F or deg C, Fan 2 will start
if temperature 2 exceeds this value"
::= { cpqCmcSetupThreshold 9 }
cpqCmcThresholdFan2Hysteresis OBJECT-TYPE
SYNTAX INTEGER (1..20)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hystersis of Fan 2, Fan 2 will stop if temperature 2 falls below
value of cpqCmcThresholdFan2 minus cpqCmcThresholdFan2Hysteresis"
::= { cpqCmcSetupThreshold 10 }
cpqCmcThresholdMaxVoltage OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold high value Voltage alarm"
::= { cpqCmcSetupThreshold 11 }
cpqCmcThresholdMinVoltage OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold low value Voltage alarm"
::= { cpqCmcSetupThreshold 12 }
cpqCmcThresholdMaxHumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold high value Humidity alarm"
::= { cpqCmcSetupThreshold 13 }
cpqCmcThresholdMinHumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Threshold low value Humidity alarm"
::= { cpqCmcSetupThreshold 14 }
--*****************************************************************************
--cpqCmcTrapTable-group
cpqCmcTrapTableNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of trapTable entries. The number of trap-receivers"
::= { cpqCmcTraps 1 }
cpqCmcTrapTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqCmcTrapEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of trap-receiver entries"
::= { cpqCmcTraps 2 }
cpqCmcTrapEntry OBJECT-TYPE
SYNTAX CpqCmcTrapEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of trapTable"
INDEX { cpqCmcTrapIndex }
::= { cpqCmcTrapTable 1 }
CpqCmcTrapEntry ::=
SEQUENCE {
cpqCmcTrapIndex
INTEGER,
cpqCmcTrapStatus
INTEGER,
cpqCmcTrapIPaddress
DisplayString
}
cpqCmcTrapIndex OBJECT-TYPE
SYNTAX INTEGER (1..4)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the trap-receiver-table. Its value ranges between
1 and the value of cpqCmcTrapTableNumber "
::= { cpqCmcTrapEntry 1 }
cpqCmcTrapStatus OBJECT-TYPE
SYNTAX INTEGER {
other(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable trap receiver"
::= { cpqCmcTrapEntry 2 }
cpqCmcTrapIPaddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-address of trap-receiver"
::= { cpqCmcTrapEntry 3 }
--*****************************************************************************
-- cpqCmcValues-group
cpqCmcValueTemp1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual temperature value of temperature sensor 1 in deg C or deg F"
::= { cpqCmcValues 1 }
cpqCmcValueTemp2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual temperature value of temperature sensor 2 in deg C or deg F"
::= { cpqCmcValues 2 }
cpqCmcValueVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual value of power supply (voltage monitoring and fans) in V"
::= { cpqCmcValues 3 }
cpqCmcValueHumidity OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual value of humidity
0..100%"
::= { cpqCmcValues 4 }
cpqCmcValueOperatingTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Operating time CMC-unit"
::= { cpqCmcValues 5 }
--******************************************************************************
--cpqCmcStatus-group
cpqCmcStatusTemp1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
normal (2),
warning (3),
overMax (4),
underMin (5),
noSensor (6),
error (7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of temperature 1,
see thresholds of temperature 1:
(2) temperature normal
(3) temperature exceeds warning threshold
(4) temperature exceeds max. threshold
(5) temperature drops under min. threshold
(6) no sensor connected, not available
(7) error, sensor disconnected"
::= { cpqCmcStatus 1 }
cpqCmcStatusTemp2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
normal (2),
warning (3),
overMax (4),
underMin (5),
noSensor (6),
error (7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of temperature 2,
see thresholds of temperature 2:
(2) temperature normal
(3) temperature exceeds warning threshold
(4) temperature exceeds max. threshold
(5) temperature drops under min. threshold
(6) no sensor connected, not available
(7) error, sensor disconnected"
::= { cpqCmcStatus 2 }
cpqCmcStatusFan1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
autoOff (2),
autoOn (3),
manualOff (4),
manualOn (5),
smokeOff (6),
doorOff (7),
noFan (8),
error (9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of fan 1:
(2) fan is switched off by temperature sensor 1
(3) fan is switched on by temperature sensor 1
(4) fan is switched off by Manual Control (cpqCmcSetFan1)
(5) fan is switched on by Manual Control (cpqCmcSetFan1)
(6) fan is switched off because of smoke alarm
(7) fan is switched off because door is open
(8) no fan
(9) fan error, current monitoring"
::= { cpqCmcStatus 3 }
cpqCmcStatusFan2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
autoOff (2),
autoOn (3),
manualOff (4),
manualOn (5),
smokeOff (6),
doorOff (7),
noFan (8),
error (9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of fan 2:
(2) fan is switched off by temperature sensor 2
(3) fan is switched on by temperature sensor 2
(4) fan is switched off by Manual Control (cpqCmcSetFan2)
(5) fan is switched on by Manual Control (cpqCmcSetFan2)
(6) fan is switched off because of smoke alarm
(7) fan is switched off because door is open
(8) no fan
(9) fan error, current monitoring"
::= { cpqCmcStatus 4 }
cpqCmcStatusVoltage OBJECT-TYPE
SYNTAX INTEGER {
other (1),
normal (2),
overMax (3),
underMin (4),
noVoltage (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage-status,
see thresholds of power supply:
(2) voltage normal
(3) voltage exceeds max. threshold
(4) voltage drops under min. threshold
(5) no power connected"
::= { cpqCmcStatus 5 }
cpqCmcStatusHumidity OBJECT-TYPE
SYNTAX INTEGER {
other (1),
normal (2),
overMax (3),
underMin (4),
noSensor (5),
error (6)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity-status,
see thresholds of humidity:
(2) humidity normal
(3) humidity exceeds max. threshold
(4) humidity drops under min. threshold
(5) no sensor connected, not available
(6) error, sensor disconnected"
::= { cpqCmcStatus 6 }
cpqCmcStatusInput1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
closed (2),
open (3),
noSensor(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door/sidepanel 1, closed (2), open (3)
or no sensor connected (4)"
::= { cpqCmcStatus 7 }
cpqCmcStatusInput2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
closed (2),
open (3),
noSensor(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door/sidepanel 2, closed (2), open (3)
or no sensor connected (4)"
::= { cpqCmcStatus 8 }
cpqCmcStatusInput3 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
closed (2),
open (3),
noSensor(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door/sidepanel 3, closed (2), open (3)
or no sensor connected (4)"
::= { cpqCmcStatus 9 }
cpqCmcStatusInput4 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
closed (2),
open (3),
noSensor(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door/sidepanel 4, closed (2), open (3)
or no sensor connected (4)"
::= { cpqCmcStatus 10 }
cpqCmcStatusLock1Lock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
locked (2),
unlockedAuto (3),
unlockedTime (4),
unlockedSmoke (5),
unlockedKey (6),
unlockedPwrFail (7),
unlockedBattLow (8),
unlockedNetFail (9),
unlockedConnFail (10),
readyToLock (11),
alarm (12),
configError (13),
notAvail (14)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door locking 1
(2) Door locking-device is activated, door is locked
(3) Door locking-device is not activated, door is unlocked by Network Management
(4) Door locking-device is not activated for x sec, time see
cpqCmcSetupLock1Time, door is unlocked by Network Management
(5) Door locking-device is not activated, door is unlocked because of Smoke alarm
(6) Door is unlocked from remote-signal
(7) Door locking-device is not activated, door is unlocked
because of Power Fail of locking device
(8) Door locking-device is not activated, door is unlocked
because of low Battery of locking device
(9) Door locking-device is not activated, door is unlocked
because of Network Fail
(10)Door locking-device is not activated, door is unlocked
because of connection fail, no connection locking device <-> CMC
(11)Door locking-device is ready to lock, lock will be activated after doors are closed
(12)Door locking-device is activated but door is not locked, alarm
(13)Configuration error, association door to locking-device missing
(14)Lock not installed"
::= { cpqCmcStatus 11 }
cpqCmcStatusLock2Lock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
locked (2),
unlockedAuto (3),
unlockedTime (4),
unlockedSmoke (5),
unlockedKey (6),
unlockedPwrFail (7),
unlockedBattLow (8),
unlockedNetFail (9),
unlockedConnFail (10),
readyToLock (11),
alarm (12),
configError (13),
notAvail (14)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door locking 2
(2) Door locking-device is activated, door is locked
(3) Door locking-device is not activated, door is unlocked by Network Management
(4) Door locking-device is not activated for x sec, time see
cpqCmcSetupLock1Time, door is unlocked by Network Management
(5) Door locking-device is not activated, door is unlocked because of Smoke alarm
(6) Door is unlocked from remote-signal
(7) Door locking-device is not activated, door is unlocked
because of Power Fail of locking device
(8) Door locking-device is not activated, door is unlocked
because of low Battery of locking device
(9) Door locking-device is not activated, door is unlocked
because of Network Fail
(10)Door locking-device is not activated, door is unlocked
because of connection fail, no connection locking device <-> CMC
(11)Door locking-device is ready to lock, lock will be activated after doors are closed
(12)Door locking-device is activated but door is not locked, alarm
(13)Configuration error, association door to locking-device missing
(14)Lock not installed"
::= { cpqCmcStatus 12 }
cpqCmcStatusSmoke OBJECT-TYPE
SYNTAX INTEGER {
other (1),
cleared (2),
present (3),
noSensor (4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status smoke-sensor, OK (2), smoke detected (3)
or no sensor connected (4)"
::= { cpqCmcStatus 13 }
cpqCmcStatusShock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
cleared (2),
present (3),
noSensor (4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status Shock sensor, OK (2), shock detected (3)
or no sensor connected (4)"
::= { cpqCmcStatus 14 }
cpqCmcStatusAux1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
alarm (3),
noSensor(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status aux. digital input"
::= { cpqCmcStatus 15 }
cpqCmcStatusAux2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
alarm (3),
noSensor(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status aux. digital input"
::= { cpqCmcStatus 16 }
cpqCmcStatusAlarm1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
alarm (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of alarm 1, see cmpCmcsetAlarm1. This alarm can be set from
the Network management system. A descriptional text for this alarm
can be set in cpqCmcSetupAlarm1Description."
::= { cpqCmcStatus 17 }
cpqCmcStatusAlarm2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
alarm (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of alarm 2, see cmpCmcsetAlarm2. This alarm can be set from
the Network management system. A descriptional text for this alarm
can be set in cpqCmcSetupAlarm2Description."
::= { cpqCmcStatus 18 }
-- cpqCmcStatusLock1Dev
-- MIB V1.1
cpqCmcStatusLock1Dev OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
powerFail (3),
lowBattery (4),
replaceBatt (5),
missingBatt (6),
noConnect (7),
notAvail (8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door-locking device 1
(2) OK
(3) Power fail of door locking-device
(4) Low Battery of door locking-device
(5) Battery of door locking device needs to be replaced
(6) Battery missing, insert all batteries
(7) Connection CMC->door locking device lost
(8) Lock not installed"
::= { cpqCmcStatus 19 }
cpqCmcStatusLock2Dev OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
powerFail (3),
lowBattery (4),
replaceBatt (5),
missingBatt (6),
noConnect (7),
notAvail (8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of door-locking device 2
(2) OK
(3) Power fail of door locking-device
(4) Low Battery of door locking-device
(5) Battery of door locking device needs to be replaced
(6) Battery missing, insert all batteries
(6) Connection CMC->door locking device lost
(7) Lock not installed"
::= { cpqCmcStatus 20 }
-- ***********************************************************************
-- cpqCmcControl-group
cpqCmcStatusAccess OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Status access, for future use"
::= { cpqCmcControl 1 }
cpqCmcSetLock1Lock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
lockDoor(2),
openDoorTime(3),
openDoor(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set door locking device 1, see table
With this command the management-station can set the conditions for
the door locking device
(2) Door will be locked
(3) Door will be unlocked for a defined time,
time can be changed, see cpqCmcSetupLock1Time
(4) Door is generally unlocked
Locking and unlocking with this command can not be
enabled or disabled with cpqCmcSetLock1Key-command"
::= { cpqCmcControl 2 }
cpqCmcSetLock1Key OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disable(2),
enableBoth(3),
enableKeypad(4),
enableRemoteInput(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable unlocking of the rack-door with external components
like keypad or remote input.
With this command the management station can set the conditions for
unlocking the door:
(2) unlocking is disabled, no unlocking with keypad or remote input
(3) unlocking with keypad or remote signal (both) is enabled
(4) unlocking with keypad (only) is enabled
(5) unlocking with remote input (only) is enabled
Unlocking door with the cpqCmcSetLock1Lock-command does not depend
on this variable"
::= { cpqCmcControl 3 }
cpqCmcSetLock2Lock OBJECT-TYPE
SYNTAX INTEGER {
other (1),
lockDoor(2),
openDoorTime(3),
openDoor(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set door locking device 2, see table
With this command the management-station can set the conditions for
the door locking device
(2) Door will be locked
(3) Door will be unlocked for a defined time,
time can be changed, see cpqCmcSetupLock2Time
(4) Door is generally unlocked
Locking and unlocking with this command can not be
enabled or disabled with cpqCmcSetLock2Key-command"
::= { cpqCmcControl 4 }
cpqCmcSetLock2Key OBJECT-TYPE
SYNTAX INTEGER {
other (1),
disable(2),
enableBoth(3),
enableKeypad(4),
enableRemoteInput(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable unlocking of the rack-door with external components
like keypad or remote input.
With this command the management-station can set the conditions for
unlocking the door:
(2) unlocking is disabled, no unlocking with keypad or remote input
(3) unlocking with keypad or remote signal (both) is enabled
(4) unlocking with keypad (only) is enabled
(5) unlocking with remote input (only) is enabled
Unlocking door with the cpqCmcSetDoor2-command does not depend
on this variable"
::= { cpqCmcControl 5 }
cpqCmcSetMessage OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set message to CMC, for future use"
::= { cpqCmcControl 6 }
cpqCmcSetAlarm1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
clearAlarm (2),
setAlarm (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Is used to set an alarm in the CMC from the management-station.
With this command the management-station can i.e. switch on an
alarm-relay or the AudibleAlarm of the CMC.
Can be used for alert-handling"
::= { cpqCmcControl 7 }
cpqCmcSetAlarm2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
clearAlarm (2),
setAlarm (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Is used to set an alarm in the CMC from the management-station.
With this command the management-station can i.e. switch on an
alarm-relay or the AudibleAlarm of the CMC.
Can be used for alert-handling"
::= { cpqCmcControl 8 }
cpqCmcSetFan1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
auto (2),
on (3),
off (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Is used for run and stop control of fan1.
(2) fan will run and stop according to temperature of sensor 1
and threshold of fan1
(3) fan will run independent of temperature and threshold
(4) fan will stop independent of temperature and threshold
(3) and (4) can be used for alert handling."
::= { cpqCmcControl 9 }
cpqCmcSetFan2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
auto (2),
on (3),
off (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Is used for run and stop control of fan2.
(2) fan will run and stop according to temperature of sensor 2
and threshold of fan2
(3) fan will run independent of temperature and threshold
(4) fan will stop independent of temperature and threshold
(3) and (4) can be used for alert handling"
::= { cpqCmcControl 10 }
cpqCmcSetQuitRelay1 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
switched (2),
notSwitched (3),
quit (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Status and quit of alarm relay 1.
(2) relay is switched because of an alarm
(3) relay is not switched, no alarm
(4) (set) will quit relay 1 in case of alarm"
::= { cpqCmcControl 11 }
cpqCmcSetQuitRelay2 OBJECT-TYPE
SYNTAX INTEGER {
other (1),
switched (2),
notSwitched (3),
quit (4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Status and quit of alarm relay 2.
(2) relay is switched because of an alarm
(3) relay is not switched, no alarm
(4) (set) will quit relay 2 in case of alarm"
::= { cpqCmcControl 12 }
-- ***********************************************************************
-- cpqCmcLog-group
cpqCmcLogsNumber OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of Log-entries"
::= { cpqCmcLog 1 }
cpqCmcLogTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqCmcLogEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Log-table"
::= { cpqCmcLog 2 }
cpqCmcLogEntry OBJECT-TYPE
SYNTAX CpqCmcLogEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Log-table entries"
INDEX { cpqCmcLogIndex }
::= { cpqCmcLogTable 1 }
CpqCmcLogEntry ::=
SEQUENCE {
cpqCmcLogIndex
INTEGER,
cpqCmcLogDate
DisplayString,
cpqCmcLogTime
DisplayString,
cpqCmcLogText
DisplayString,
cpqCmcLogClass
DisplayString
}
cpqCmcLogIndex OBJECT-TYPE
SYNTAX INTEGER (1..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the Log-table. Its value ranges between
1 and the value of cpqCmcLogsNumber "
::= { cpqCmcLogEntry 1 }
cpqCmcLogDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..11))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Date of log information. "
::= { cpqCmcLogEntry 2 }
cpqCmcLogTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..11))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Time of log information. "
::= { cpqCmcLogEntry 3 }
cpqCmcLogText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Log information. "
::= { cpqCmcLogEntry 4 }
cpqCmcLogClass OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of log information. "
::= { cpqCmcLogEntry 5 }
--******************************************************************************
-- Traps
-- CMC-Traps
cpqCmcalarmTemp1 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusTemp1 }
DESCRIPTION
"The temperature at rack sensor 1 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information."
--
--#TYPE "Temperature-alarm (153001)"
--#SUMMARY "Location: %s, Message: Rack temp sensor 1 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153001
cpqCmcalarmTemp2 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusTemp2 }
DESCRIPTION
"The temperature at rack sensor 2 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information."
--
--#TYPE "Temperature-alarm (153002)"
--#SUMMARY "Location: %s, Message: Rack temp sensor 2 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153002
cpqCmcalarmFan1 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusFan1 }
DESCRIPTION
"The status of Fan 1 has changed. Action: Refer to Trap Details for more information."
--
--#TYPE "Fan-alarm (153003)"
--#SUMMARY "Location: %s, Rack fan 1 status: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153003
cpqCmcalarmFan2 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusFan2 }
DESCRIPTION
"The status of Fan 2 has changed. Action: Refer to Trap Details for more information."
--
--#TYPE "Fan-alarm (153004)"
--#SUMMARY "Location: %s, Rack fan 2 status: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153004
cpqCmcalarmVoltage TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusVoltage }
DESCRIPTION
"The AC voltage of the rack is outside the specified threshold. Action: Check the incoming power source and ensure all cables are inserted correctly."
--
--#TYPE "Voltage-alarm (153005)"
--#SUMMARY "Location: %s, Message: Rack supply voltage %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153005
cpqCmcalarmHumidity TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusHumidity }
DESCRIPTION
"The humidity of the rack is outside the specified threshold. Action: Check the
air handling system for the rack and refer to Trap Details for more information."
--
--#TYPE "Humidity-alarm (153006)"
--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153006
cpqCmcalarmInput1 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusInput1 }
DESCRIPTION
"The door or sidepanel of the rack has been opened (access point #1). Action: Check for unauthorized intrusion and refer to Trap Details for more information."
--
--#TYPE "Door/sidepanel-alarm (153007)"
--#SUMMARY "Location: %s, Message: Rack access point 1 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MINOR
--#TIMEINDEX 99
--
::= 153007
cpqCmcalarmInput2 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusInput2 }
DESCRIPTION
"The door or sidepanel of the rack has been opened (access point #2). Action: Check for unauthorized intrusion and refer to Trap Details for more information."
--
--#TYPE "Door/sidepanel-alarm (153008)"
--#SUMMARY "Location: %s, Message: Rack access point 2 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MINOR
--#TIMEINDEX 99
--
::= 153008
cpqCmcalarmInput3 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusInput3 }
DESCRIPTION
"The door or sidepanel of the rack has been opened (access point #3). Action: Check for unauthorized intrusion and refer to Trap Details for more information."
--
--#TYPE "Door/sidepanel-alarm (153009)"
--#SUMMARY "Location: %s, Message: Rack access point 3 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MINOR
--#TIMEINDEX 99
--
::= 153009
cpqCmcalarmInput4 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusInput4 }
DESCRIPTION
"The door or sidepanel of the rack has been opened (access point #4). Action: Check for unauthorized intrusion and refer to Trap Details for more information."
--
--#TYPE "Door/sidepanel-alarm (153010)"
--#SUMMARY "Location: %s, Message: Rack access point 4 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MINOR
--#TIMEINDEX 99
--
::= 153010
cpqCmcalarmLock1 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusLock1Lock }
DESCRIPTION
"Rack door lock #1 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information."
--
--#TYPE "Door-locking-alarm (153011)"
--#SUMMARY "Location: %s, Message: Rack lock #1 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153011
cpqCmcalarmLock2 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusLock2Lock }
DESCRIPTION
"Rack door lock #2 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information."
--
--#TYPE "Door-locking-alarm (153012)"
--#SUMMARY "Location: %s, Message: Rack lock #1 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153012
cpqCmcalarmSmoke TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusSmoke }
DESCRIPTION
"The rack smoke detector has detected smoke. Action: Investigate rack for an over temperature condition and refer to Trap Details for more information."
--
--#TYPE "Smoke-alarm (153013)"
--#SUMMARY "Location: %s, Message: Rack smoke detector - smoke: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153013
cpqCmcalarmShock TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusShock }
DESCRIPTION
"The rack shock detector has detected a vibration to the rack. Action: Investigate rack."
--
--#TYPE "Shock-alarm (153014)"
--#SUMMARY "Location: %s, Message: Rack shock detector - shock: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153014
cpqCmcalarmAux1 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusAux1 }
DESCRIPTION
"The rack auxiliary alarm input #1 has been triggered."
--
--#TYPE "Aux-alarm (153015)"
--#SUMMARY "Location: %s, Message: aux input #1 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153015
cpqCmcalarmAux2 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusAux2 }
DESCRIPTION
"The rack auxiliary alarm input #2 has been triggered."
--
--#TYPE "Aux-alarm (153016)"
--#SUMMARY "Location: %s, Message: aux input #2 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153016
cpqCmcalarm1 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusAlarm1 }
DESCRIPTION
"Alarm 1, set from Network management"
--
--#TYPE "NMS-alarm (153017)"
--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153017
cpqCmcalarm2 TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusAlarm2 }
DESCRIPTION
"Alarm 2, set from Network management"
--
--#TYPE "NMS-alarm (153018)"
--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153018
--MIB V1.1
cpqCmcalarmLock1Dev TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusLock1Dev }
DESCRIPTION
"The rack door locking device #1 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information."
--
--#TYPE "Door-locking-alarm of device (153019)"
--#SUMMARY "Location: %s, Status: door lock device #1 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153019
cpqCmcalarmLock2Dev TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation, cpqCmcStatusLock2Dev }
DESCRIPTION
"The rack door locking device #2 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information."
--
--#TYPE "Door-locking-alarm of device (153020)"
--#SUMMARY "Location: %s, Status: door lock device #2 %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--
::= 153020
cpqCmcSetupChanged TRAP-TYPE
ENTERPRISE cpqCmc
VARIABLES { sysDescr, sysContact, sysName,
sysLocation }
DESCRIPTION
"Setup of CMC has changed."
--
--#TYPE "Setup has changed (153100)"
--#SUMMARY "Location: %s, Name: %s, contact %s"
--#ARGUMENTS {3,2,1}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--
::= 153100
END