LIEBERT-GP-PDU-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
MODULE-IDENTITY,
|
|
OBJECT-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Integer32,
|
|
Unsigned32
|
|
FROM SNMPv2-SMI
|
|
lgpPdu,
|
|
liebertPduModuleReg
|
|
FROM LIEBERT-GP-REGISTRATION-MIB
|
|
;
|
|
|
|
-- =============================================================================
|
|
-- Module Identification and Registration
|
|
-- =============================================================================
|
|
|
|
liebertGlobalProductsPduModule MODULE-IDENTITY
|
|
LAST-UPDATED "200807020000Z"
|
|
ORGANIZATION "Emerson Network Power/Liebert Corporation"
|
|
CONTACT-INFO
|
|
"Contact: Technical Support
|
|
|
|
Postal:
|
|
Liebert Corporation
|
|
1050 Dearborn Drive
|
|
P.O. Box 29186
|
|
Columbus OH, 43229
|
|
US
|
|
|
|
Tel: +1 (800) 222-5877
|
|
|
|
E-mail: liebert.monitoring@emerson.com
|
|
Web: www.liebert.com
|
|
|
|
Author: Keith Sarbaugh"
|
|
|
|
DESCRIPTION
|
|
"The MIB module used to register Liebert POWER related SNMP OIDs.
|
|
|
|
Copyright 2008-2008 Liebert Corporation. All rights reserved.
|
|
Reproduction of this document is authorized on the condition
|
|
that the forgoing copyright notice is included.
|
|
|
|
This Specification is supplied 'AS IS' and Liebert Corporation
|
|
makes no warranty, either express or implied, as to the use,
|
|
operation, condition, or performance of the Specification."
|
|
|
|
REVISION "200807020000Z"
|
|
DESCRIPTION
|
|
"Initial Version"
|
|
|
|
::= { liebertPduModuleReg 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPdu - Liebert Power Distribution Registrations
|
|
-- =============================================================================
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
-- PDU Group Information
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduCluster OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains information about PDU clusters. Clusters are
|
|
groups of PDU's under a single monitoring or control domain."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below."
|
|
::= { lgpPdu 10 }
|
|
|
|
lgpPduGrpSysStatus OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This value represents a bit-field of the various operational
|
|
states of the PDUs that are part of the cluster of PDUs
|
|
being monitored by this agent.
|
|
|
|
This value is the bit-wise logical OR of all of the
|
|
'lgpPduEntrySysStatus' columns in the 'lgpPduTable'
|
|
which represents the combined statuses of all PDUs for this agent.
|
|
|
|
Note the bit-position is given parenthetically next to the operational
|
|
state in the description below. The bit position is big-endian
|
|
(least significant digit is the right-most digit). The state is
|
|
present in the PDU when the bit is on (value = 1).
|
|
|
|
The value is a logical OR of all of the following potential states of
|
|
each PDU in the cluster.
|
|
|
|
normalOperation(1)
|
|
One or more PDUs in the cluster are operating normally with no
|
|
active warnings or alarms.
|
|
startUp(2)
|
|
One or more PDUs are in the startup state (initializing). Control
|
|
and monitoring operations may be inhibited or unavailable
|
|
while the PDU is in this state. This state will clear
|
|
automatically when the PDU(s) are fully initialized and ready to
|
|
accept control and monitoring commands.
|
|
unknownNoSupport(4)
|
|
The state of one or more PDUs are not known at this time or
|
|
there is no support for this piece of information from 1 or more
|
|
PDUs in the cluster/group.
|
|
normalWithWarning(8)
|
|
One or more PDUs are operating normally with one or more active
|
|
warnings. Appropriate personnel should investigate the
|
|
warning(s) as soon as possible and take appropriate action.
|
|
normalWithAlarm(16)
|
|
One or more PDUs are operating normally with one or more active
|
|
alarms. Appropriate personnel should investigate the alarm(s)
|
|
as soon as possible and take appropriate action.
|
|
abnormalOperation(32)
|
|
One ore more PDUs are operating abnormally. There is a
|
|
failure within the system that is unexpected under normal
|
|
operating conditions. Appropriate personnel should investigate
|
|
the cause as soon as possible. The normal functioning of
|
|
the system is likely inhibited.
|
|
unknownCommFailure(64)
|
|
The state of one or more PDUs are not known due to a communications
|
|
failure between the PDU hardware and the communications
|
|
module. This state is usually indicative of a hardware
|
|
problem.
|
|
"
|
|
::= { lgpPduCluster 5 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
-- Power Distribution (PDU) Table.
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduTableCount OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of PDUs being monitored by this agent. This is the
|
|
number of entries in the lgpPduTable."
|
|
::= { lgpPdu 19 }
|
|
|
|
lgpPduTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of PDU entries.
|
|
The table contains zero, one, or many rows, depending upon the number
|
|
of PDUs being monitored. The Network Management System (NMS)
|
|
cannot create or delete rows in the table. The rows are created by
|
|
the agent based upon the number of PDUs being managed.
|
|
Each row in the table represents a PDU in the system."
|
|
::= { lgpPdu 20 }
|
|
|
|
lgpPduEntry OBJECT-TYPE
|
|
SYNTAX LgpPduEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the columns to be populated in the
|
|
'lgpPduTable'. Each column represents an attribute of a PDU.
|
|
This table is indexed by the PDU identifier that is unique
|
|
within the agent.
|
|
"
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex
|
|
}
|
|
::= { lgpPduTable 1 }
|
|
|
|
LgpPduEntry ::= SEQUENCE
|
|
{
|
|
lgpPduEntryIndex Unsigned32,
|
|
lgpPduEntryId Unsigned32,
|
|
lgpPduEntryUsrLabel DisplayString,
|
|
lgpPduEntrySysAssignLabel DisplayString,
|
|
lgpPduEntryPositionRelative Unsigned32,
|
|
lgpPduEntrySysStatus Unsigned32,
|
|
lgpPduEntryUsrTag1 DisplayString,
|
|
lgpPduEntryUsrTag2 DisplayString,
|
|
lgpPduEntrySerialNumber DisplayString,
|
|
lgpPduEntryRbCount Unsigned32
|
|
}
|
|
|
|
lgpPduEntryIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index that indicates the row of the 'lgpPduTable'."
|
|
::= { lgpPduEntry 1 }
|
|
|
|
lgpPduEntryId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is an internal index representing a unique identifier for
|
|
each PDU represented by this agent. The value is assigned
|
|
by the agent."
|
|
::= { lgpPduEntry 5 }
|
|
|
|
lgpPduEntryUsrLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a user assigned label representing the PDU."
|
|
::= { lgpPduEntry 10 }
|
|
|
|
lgpPduEntrySysAssignLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System assigned identifier representing the PDU. The value
|
|
is independent of any user assigned label or tag. The exact format
|
|
of this label is system dependent and is subject to change,
|
|
therefore, it should not be referenced for programmatic use."
|
|
::= { lgpPduEntry 15 }
|
|
|
|
lgpPduEntryPositionRelative OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a one-based value that indicates the PDU's relative
|
|
position within a rack or other enclosing entity."
|
|
::= { lgpPduEntry 20 }
|
|
|
|
lgpPduEntrySysStatus OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This value represents a bit-field of the various operational
|
|
states of the PDU. The value is a logical OR of all of the
|
|
following potential states of the PDU. Note the bit-position
|
|
is given parenthetically next to the operational state in the
|
|
description below. The bit position is assumed to be a big-endian
|
|
format (least significant digit is the right-most digit). The
|
|
state is present in the PDU when the bit is on (value = 1).
|
|
|
|
normalOperation(1)
|
|
The PDU is operating normally with no active warnings or alarms.
|
|
startUp(2)
|
|
The PDU is in the startup state (initializing). Control
|
|
and monitoring operations maybe inhibited or unavailable
|
|
while the PDU is in this state. This state will clear
|
|
automatically when the PDU(s) are fully initialized and
|
|
ready to accept control and monitoring commands.
|
|
normalWithWarning(8)
|
|
The PDU is operating normally with one or more active
|
|
warnings. Appropriate personnel should investigate the
|
|
warning(s) as soon as possible and take appropriate action.
|
|
normalWithAlarm(16)
|
|
The PDU is operating normally with one or more active
|
|
alarms. Appropriate personnel should investigate the alarm(s)
|
|
as soon as possible and take appropriate action.
|
|
abnormalOperation(32)
|
|
The PDU is operating abnormally. That is there is some
|
|
failure within the system that is unexpected under normal
|
|
operating conditions. Appropriate personnel should investigate
|
|
the cause as soon as possible. The normal functioning of
|
|
the system is likely inhibited.
|
|
"
|
|
::= { lgpPduEntry 25 }
|
|
|
|
lgpPduEntryUsrTag1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a user assigned Tag for the PDU. This value may be
|
|
useful for end-user grouping or asset tracking purposes.
|
|
The value for this tag does not need to be unique for this
|
|
unit or across other units."
|
|
::= { lgpPduEntry 35 }
|
|
|
|
lgpPduEntryUsrTag2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a user assigned Tag for the PDU. This value may be
|
|
useful for end-user grouping or asset tracking purposes.
|
|
The value for this tag does not need to be unique for this
|
|
unit or across other units."
|
|
::= { lgpPduEntry 40 }
|
|
|
|
lgpPduEntrySerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System assigned serial number for this PDU. This number is
|
|
assigned at time of manufacture, is globally unique with respect
|
|
to all PDU units."
|
|
::= { lgpPduEntry 45 }
|
|
|
|
lgpPduEntryRbCount OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of receptacle branches (Rb) within this PDU."
|
|
::= { lgpPduEntry 50 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- PDU Power Source.
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduPowerSource OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains information about PDU power sources."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below."
|
|
::= { lgpPdu 30 }
|
|
|
|
lgpPduPsTableCount OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of power sources in the lgpPduPsTable."
|
|
::= { lgpPduPowerSource 19 }
|
|
|
|
lgpPduPsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduPsEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of the PDU's power source(s).
|
|
The table contains zero, one, or more rows, depending
|
|
upon the number of PDUs being monitored and the number of
|
|
power sources installed for each PDU.
|
|
The NMS cannot create or delete rows in the table. The rows are
|
|
created by the agent based upon the capabilities of the PDUs
|
|
being monitored. Each row in the table represents a PDU's
|
|
Power Source."
|
|
::= { lgpPduPowerSource 20 }
|
|
|
|
lgpPduPsEntry OBJECT-TYPE
|
|
SYNTAX LgpPduPsEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpPduPsTable' (Power Source Table).
|
|
This table is indexed by both the 'lgpPduEntryIndex' which is
|
|
the sole index into the 'lgpPduTable' and the 'lgpPduPsEntryIndex'
|
|
which is a unique identifier for the Power Source within a
|
|
given PDU. Taken together these two indexes uniquely identify
|
|
a Power Source within this agent.
|
|
"
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex,
|
|
lgpPduPsEntryIndex
|
|
}
|
|
::= { lgpPduPsTable 1 }
|
|
|
|
LgpPduPsEntry ::= SEQUENCE
|
|
{
|
|
lgpPduPsEntryIndex Unsigned32,
|
|
lgpPduPsEntryId Unsigned32,
|
|
lgpPduPsEntrySysAssignLabel DisplayString,
|
|
lgpPduPsEntryModel DisplayString,
|
|
lgpPduPsEntryWiringType INTEGER,
|
|
lgpPduPsEntryEpInputRated Unsigned32,
|
|
lgpPduPsEntryEcInputRated Unsigned32,
|
|
lgpPduPsEntryFreqRated Unsigned32,
|
|
lgpPduPsEntryEnergyAccum Unsigned32,
|
|
lgpPduPsEntrySerialNum DisplayString,
|
|
lgpPduPsEntryFirmwareVersion DisplayString,
|
|
lgpPduPsEntryPwrTotal Unsigned32,
|
|
lgpPduPsEntryEcNeutral Unsigned32,
|
|
lgpPduPsEntryEcNeutralThrshldOvrWarn Unsigned32,
|
|
lgpPduPsEntryEcNeutralThrshldOvrAlarm Unsigned32
|
|
}
|
|
|
|
lgpPduPsEntryIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a unique identifier for the Power Source within a
|
|
given PDU. This is one of two indexes used to indicate the row of
|
|
the 'lgpPduTable'."
|
|
::= { lgpPduPsEntry 5 }
|
|
|
|
lgpPduPsEntryId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a unique entry id representing a given PDU power source
|
|
for the PDU."
|
|
::= { lgpPduPsEntry 10 }
|
|
|
|
lgpPduPsEntrySysAssignLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System assigned identifier for this power source. The value
|
|
is independent of any user assigned label or tag. The exact format
|
|
of this label is system dependent and is subject to change,
|
|
therefore, it should not be referenced for programmatic use."
|
|
::= { lgpPduPsEntry 15 }
|
|
|
|
lgpPduPsEntryModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the model name (identifier) of the power supply."
|
|
::= { lgpPduPsEntry 20 }
|
|
|
|
lgpPduPsEntryWiringType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
single-phase-3-wire-L1-N-PE(1),
|
|
two-phase-3-wire-L1-L2-PE(2),
|
|
three-phase-4-wire-L1-L2-L3-PE(3),
|
|
three-phase-5-wire-L1-L2-L3-N-PE(4),
|
|
two-phase-4-wire-L1-L2-N-PE(5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU's power supply physical wiring type.
|
|
not-specified
|
|
The type has not been specified/configured. The end_user
|
|
must configure this object to specify the physical wiring
|
|
type.
|
|
single-phase-3-wire-L1-N-PE
|
|
Single Phase input with 3 wires (Line 1, Neutral and
|
|
Protective Earth).
|
|
two-phase-3-wire-L1-L2-PE
|
|
Two Phase input with 3 wires (Line 1, Line 2, and
|
|
Protective Earth).
|
|
three-phase-4-wire-L1-L2-L3-PE
|
|
Three Phase input with 4 wires (Line 1, Line 2, Line 3,
|
|
and Protective Earth).
|
|
three-phase-5-wire-L1-L2-L3-N-PE
|
|
Three Phase input with 5 wires (Line 1, Line 2, Line 3,
|
|
Neutral and Protective Earth).
|
|
two-phase-4-wire-L1-L2-N-PE
|
|
Two Phase input with 4 wires (Line 1, Line 2, Neutral,
|
|
and Protective Earth)."
|
|
::= { lgpPduPsEntry 25 }
|
|
|
|
lgpPduPsEntryEpInputRated OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated Input Line Voltage for the power source (i.e. this is the
|
|
nominal line input voltage; it is NOT a measured voltage).
|
|
|
|
The value is defined to be the rated line voltage
|
|
(either line-to-neutral or line-to-line depending upon the
|
|
power source's type)."
|
|
::= { lgpPduPsEntry 30 }
|
|
|
|
lgpPduPsEntryEcInputRated OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the rated input line current for the module
|
|
(it is NOT the measured current)."
|
|
::= { lgpPduPsEntry 35 }
|
|
|
|
lgpPduPsEntryFreqRated OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated input line frequency for this power source
|
|
(i.e. This is the expected line frequency; it is NOT a
|
|
measured frequency; it is typically 50 Hz or 60 Hz)."
|
|
::= { lgpPduPsEntry 40 }
|
|
|
|
lgpPduPsEntryEnergyAccum OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Kilowatt-Hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total accumulated energy, measured at the power source input, since
|
|
the last energy reset. Writing a value of 0 (zero) to this
|
|
causes the accumulated energy to be reset. Writing a non-zero
|
|
value is invalid and shall result in a write error and the
|
|
total energy value remains unchanged.
|
|
|
|
If the energy has not been reset and has not wrapped,
|
|
then this is the total energy since installation.
|
|
|
|
This value persists across boot events."
|
|
::= { lgpPduPsEntry 50 }
|
|
|
|
lgpPduPsEntrySerialNum OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a unique serial number of the power supply. This number
|
|
is assigned to the power supply at the time of manufacture."
|
|
::= { lgpPduPsEntry 55 }
|
|
|
|
lgpPduPsEntryFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the version of the firmware installed on the PDU's
|
|
power supply."
|
|
::= { lgpPduPsEntry 60 }
|
|
|
|
lgpPduPsEntryPwrTotal OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total input power for this power supply. This is the sum of the
|
|
power for all phases"
|
|
::= { lgpPduPsEntry 65 }
|
|
|
|
lgpPduPsEntryEcNeutral OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The neutral current measured at the PDU's power source."
|
|
::= { lgpPduPsEntry 70 }
|
|
|
|
lgpPduPsEntryEcNeutralThrshldOvrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current warning is activated. If the
|
|
measured neutral current (lgpPduPsEntryEcNeutral) is above this
|
|
percentage of the full scale rated value
|
|
(lgpPduPsEntryEcInputRated), an over neutral current warning
|
|
(lgpConditionSource1NeutralOverCurrent) is activated."
|
|
::= { lgpPduPsEntry 75 }
|
|
|
|
lgpPduPsEntryEcNeutralThrshldOvrAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current alarm is activated. If the
|
|
measured neutral current (lgpPduPsEntryEcNeutral) is above this
|
|
percentage of the full scale rated value
|
|
(lgpPduPsEntryEcInputRated), an over neutral current alarm
|
|
(lgpConditionSource1NeutralOverCurrent) is activated."
|
|
::= { lgpPduPsEntry 80 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
-- PDU - Power Source Line/Phase Table.
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduPsLineTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduPsLineEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of PDU's power source line/phase
|
|
measurements. The table contains zero, one, or many rows, depending
|
|
upon the number of PDU's Power Sources being monitored.
|
|
The NMS cannot create or delete rows in the table.
|
|
The rows are created by the agent based upon the capabilities of the
|
|
managed PDU's power supply(s). Each row in the table represents a
|
|
particular phase/line measurement of a power supply for a
|
|
given PDU."
|
|
::= { lgpPduPowerSource 40 }
|
|
|
|
lgpPduPsLineEntry OBJECT-TYPE
|
|
SYNTAX LgpPduPsLineEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpPduPsLineTable'.
|
|
The table is index by three indexes which taken together
|
|
uniquely identify line/phase information for a given power source
|
|
within a PDU. The 'lgpPduEntryIndex' is an index into the
|
|
'lgpPduTable'. This identifies the PDU that the power source
|
|
is on. The 'lgpPduPsEntryIndex' is an index that together with
|
|
the 'lgpPduEntryIndex' uniquely identifies the power source
|
|
within the PDU that the row in this table represents. The final
|
|
index 'lgpPduPsLineEntryIndex' identifies the particular
|
|
line/phase that the measurement applies to within the identified
|
|
power source."
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex,
|
|
lgpPduPsEntryIndex,
|
|
lgpPduPsLineEntryIndex
|
|
}
|
|
::= { lgpPduPsLineTable 1 }
|
|
|
|
LgpPduPsLineEntry ::= SEQUENCE
|
|
{
|
|
lgpPduPsLineEntryIndex Unsigned32,
|
|
lgpPduPsLineEntryId Unsigned32,
|
|
lgpPduPsLineEntryLine INTEGER,
|
|
lgpPduPsLineEntryEpLNTenths Unsigned32,
|
|
lgpPduPsLineEntryEpLN Unsigned32,
|
|
lgpPduPsLineEntryEc Unsigned32,
|
|
lgpPduPsLineEntryEcHundredths Unsigned32,
|
|
|
|
lgpPduPsLineEntryEcThrshldUndrAlarm Unsigned32,
|
|
lgpPduPsLineEntryEcThrshldOvrWarn Unsigned32,
|
|
lgpPduPsLineEntryEcThrshldOvrAlarm Unsigned32,
|
|
lgpPduPsLineEntryEcAvailBeforeAlarm Unsigned32,
|
|
lgpPduPsLineEntryEcUsedBeforeAlarm Unsigned32,
|
|
lgpPduPsLineEntryEpLL Unsigned32,
|
|
lgpPduPsLineEntryEpLLTenths Unsigned32,
|
|
lgpPduPsLineEntryEcAvailBeforeAlarmHundredths Unsigned32
|
|
|
|
}
|
|
|
|
lgpPduPsLineEntryIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index that indicates the line/phase of the measurements
|
|
in the given row of the 'lgpPduPsLineTable'."
|
|
::= { lgpPduPsLineEntry 5 }
|
|
|
|
lgpPduPsLineEntryId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique identifier (within a PDU) for the PDU's power source.
|
|
The object may not be available in non-modular systems."
|
|
::= { lgpPduPsLineEntry 10 }
|
|
|
|
lgpPduPsLineEntryLine OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
phase1(1),
|
|
phase2(2),
|
|
phase3(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The line number (phase) that the measurement represents for all
|
|
measurements in a given row of the table. Note that this always
|
|
matches the lgpPduPsLineEntryIndex of the same row in the table.
|
|
The line/phases are as follows:
|
|
|
|
Line# Description
|
|
----- ---------------------------------------------------
|
|
1 Line 1-N (A) for Line-to-Neutral measurements
|
|
2 Line 2-N (B) for Line-to-Neutral measurements
|
|
3 Line 3-N (C) for Line-to-Neutral measurements
|
|
|
|
1 Line 1-2 (A-B) for Line-to-Line measurements
|
|
2 Line 2-3 (B-C) for Line-to-Line measurements
|
|
3 Line 3-1 (C-A) for Line-to-Line measurements
|
|
"
|
|
::= { lgpPduPsLineEntry 15 }
|
|
|
|
lgpPduPsLineEntryEpLNTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Volts-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alternating Current RMS Line to Neutral Electrical Potential
|
|
measurement.
|
|
The line/phase being measured is indicated by the corresponding
|
|
lgpPduPsLineEntryLine value of this row in the table."
|
|
::= { lgpPduPsLineEntry 19 }
|
|
|
|
lgpPduPsLineEntryEpLN OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Volts-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alternating Current RMS Line to Neutral Electrical Potential
|
|
measurement.
|
|
The line/phase being measured is indicated by the corresponding
|
|
lgpPduPsLineEntryLine value of this row in the table."
|
|
::= { lgpPduPsLineEntry 20 }
|
|
|
|
lgpPduPsLineEntryEc OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total input line-to-neutral electrical current.
|
|
The line/phase being measured is indicated by the corresponding
|
|
lgpPduPsLineEntryLine value of this row in the table."
|
|
::= { lgpPduPsLineEntry 21 }
|
|
|
|
lgpPduPsLineEntryEcHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total input line-to-neutral electrical current.
|
|
The line/phase being measured is indicated by the corresponding
|
|
lgpPduPsLineEntryLine value of this row in the table."
|
|
::= { lgpPduPsLineEntry 22 }
|
|
|
|
lgpPduPsLineEntryEcThrshldUndrAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an under current alarm is activated. If
|
|
the measured current (lgpPduPsLineEntryEc) is equal to or below
|
|
this percentage of the full scale rated value
|
|
(lgpPduPsEntryEcInputRated), an under current alarm
|
|
is activated."
|
|
::= { lgpPduPsLineEntry 35 }
|
|
|
|
lgpPduPsLineEntryEcThrshldOvrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current warning is activated. If
|
|
the measured current (lgpPduPsLineEntryEc) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduPsEntryEcInputRated), an over current warning
|
|
is activated."
|
|
::= { lgpPduPsLineEntry 36 }
|
|
|
|
lgpPduPsLineEntryEcThrshldOvrAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current alarm is activated. If
|
|
the measured current (lgpPduPsLineEntryEc) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduPsEntryEcInputRated), an over current alarm
|
|
is activated."
|
|
::= { lgpPduPsLineEntry 37 }
|
|
|
|
lgpPduPsLineEntryEcAvailBeforeAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount that the current/amperage may increase from its present
|
|
value before an over current alarm occurs."
|
|
::= { lgpPduPsLineEntry 38 }
|
|
|
|
lgpPduPsLineEntryEcUsedBeforeAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percent of current utilization relative to the over current
|
|
alarm threshold."
|
|
::= { lgpPduPsLineEntry 39 }
|
|
|
|
lgpPduPsLineEntryEpLL OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Volts-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line to Line Electrical Potential.
|
|
The line/phase being measured is indicated by the corresponding
|
|
lgpPduPsLineEntryLine value of this row in the table."
|
|
::= { lgpPduPsLineEntry 60 }
|
|
|
|
lgpPduPsLineEntryEpLLTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Volts-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line to Line Electrical Potential.
|
|
The line/phase being measured is indicated by the corresponding
|
|
lgpPduPsLineEntryLine value of this row in the table."
|
|
::= { lgpPduPsLineEntry 61 }
|
|
|
|
lgpPduPsLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount that the current/amperage may increase from its present
|
|
value before an over current alarm occurs."
|
|
::= { lgpPduPsLineEntry 62 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
-- PDU Receptacle Branch
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduReceptacleBranch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains information about PDU receptacle branches."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below."
|
|
::= { lgpPdu 40 }
|
|
|
|
lgpPduRbTableCount OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of receptacle branches in the lgpPduRbTable."
|
|
::= { lgpPduReceptacleBranch 19 }
|
|
|
|
lgpPduRbTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduRbEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of PDU Receptacle branches.
|
|
The table contains zero, one, or many rows, depending
|
|
upon the number of PDUs being managed and how many
|
|
receptacle branches each PDU has installed.
|
|
The NMS cannot create or delete rows in the table. The rows are
|
|
created by the agent based upon the capabilities of the PDUs
|
|
being managed. Each row in the table represents a receptacle branch
|
|
for a given PDU. The PDU that a branch is installed
|
|
on is indicated by the column lgpPduEntryIndex. The branch
|
|
within the lgpPduEntryIndex PDU is indicated by the column
|
|
lgpPduRbEntryIndex."
|
|
::= { lgpPduReceptacleBranch 20 }
|
|
|
|
lgpPduRbEntry OBJECT-TYPE
|
|
SYNTAX LgpPduRbEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpPduRbTable'. The table is indexed
|
|
by both the 'lgpPduEntryIndex' and 'lgpPduRbEntryIndex'. The
|
|
lgpPduEntryIndex specifies the PDU, defined in the lgpPduTable
|
|
that the branch is on. The lgpPduRbEntryIndex uniquely identifies
|
|
the branch within that PDU. Taken together the two indexes
|
|
uniquely identify a branch being monitored by this agent.
|
|
"
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex,
|
|
lgpPduRbEntryIndex
|
|
}
|
|
::= { lgpPduRbTable 1 }
|
|
|
|
LgpPduRbEntry ::= SEQUENCE
|
|
{
|
|
lgpPduRbEntryIndex Unsigned32,
|
|
lgpPduRbEntryId Unsigned32,
|
|
lgpPduRbEntryUsrLabel DisplayString,
|
|
lgpPduRbEntrySysAssignLabel DisplayString,
|
|
lgpPduRbEntryPositionRelative Unsigned32,
|
|
lgpPduRbEntrySerialNum DisplayString,
|
|
lgpPduRbEntryModel DisplayString,
|
|
lgpPduRbEntryFirmwareVersion DisplayString,
|
|
lgpPduRbEntryUsrTag1 DisplayString,
|
|
lgpPduRbEntryUsrTag2 DisplayString,
|
|
lgpPduRbEntryReceptacleType INTEGER,
|
|
lgpPduRbEntryCapabilities INTEGER,
|
|
lgpPduRbEntryLineSource INTEGER,
|
|
lgpPduRbEntryRcpCount Unsigned32,
|
|
lgpPduRbEntryEpRated Unsigned32,
|
|
lgpPduRbEntryEcRated Unsigned32,
|
|
lgpPduRbEntryFreqRated Unsigned32,
|
|
lgpPduRbEntryEnergyAccum Unsigned32,
|
|
lgpPduRbEntryEpLNTenths Unsigned32,
|
|
lgpPduRbEntryPwr Unsigned32,
|
|
lgpPduRbEntryAp Unsigned32,
|
|
lgpPduRbEntryPf Integer32,
|
|
lgpPduRbEntryEcHundredths Unsigned32,
|
|
lgpPduRbEntryEcThrshldUndrAlm Unsigned32,
|
|
lgpPduRbEntryEcThrshldOvrWarn Unsigned32,
|
|
lgpPduRbEntryEcThrshldOvrAlm Unsigned32,
|
|
lgpPduRbEntryEcAvailBeforeAlarmHundredths Unsigned32,
|
|
lgpPduRbEntryEcUsedBeforeAlarm Unsigned32,
|
|
lgpPduRbEntryEpLLTenths Unsigned32
|
|
}
|
|
|
|
lgpPduRbEntryIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index that indicates the row of the
|
|
'lgpPduRbTable'"
|
|
::= { lgpPduRbEntry 1 }
|
|
|
|
lgpPduRbEntryId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique id representing the receptacle branch within the
|
|
collection of branches being monitored by this agent. The
|
|
uniqueness of this id is within the PDUs being managed by
|
|
a single agent."
|
|
::= { lgpPduRbEntry 5 }
|
|
|
|
lgpPduRbEntryUsrLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user assigned label representing the receptacle branch."
|
|
::= { lgpPduRbEntry 8 }
|
|
|
|
lgpPduRbEntrySysAssignLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System assigned identifier for this receptacle branch. The value
|
|
is independent of any user assigned label or tag. The exact format
|
|
of this label is system dependent and is subject to change,
|
|
therefore, it should not be referenced for programmatic use."
|
|
::= { lgpPduRbEntry 20 }
|
|
|
|
lgpPduRbEntryPositionRelative OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a one-based value that indicates the relative
|
|
position of the branch within the PDU."
|
|
::= { lgpPduRbEntry 25 }
|
|
|
|
lgpPduRbEntrySerialNum OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A globally unique serial number for this branch. This number
|
|
is assigned to the branch at the time of manufacture and can not
|
|
be modified. NOTE: Generally only PDUs with replaceable
|
|
receptacle branches will have serial numbers."
|
|
::= { lgpPduRbEntry 30 }
|
|
|
|
lgpPduRbEntryModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the model designation for this receptacle branch."
|
|
::= { lgpPduRbEntry 35 }
|
|
|
|
lgpPduRbEntryFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the firmware version number of the control software
|
|
running on the receptacle branch. Only PDUs with
|
|
replaceable receptacle branches will typically support this
|
|
object."
|
|
::= { lgpPduRbEntry 40 }
|
|
|
|
lgpPduRbEntryUsrTag1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a user assigned Tag for the receptacle branch. This
|
|
value may be useful for end-user grouping or asset tracking
|
|
purposes. The value for this tag does not need to be unique
|
|
for this unit or across other units."
|
|
::= { lgpPduRbEntry 41 }
|
|
|
|
lgpPduRbEntryUsrTag2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a user assigned Tag for the receptacle branch. This
|
|
value may be useful for end-user grouping or asset tracking
|
|
purposes. The value for this tag does not need to be unique
|
|
for this unit or across other units."
|
|
::= { lgpPduRbEntry 42 }
|
|
|
|
lgpPduRbEntryReceptacleType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
nema-5-20R-20-Amp(1),
|
|
iec-C13-sheet-F-10-Amp(2),
|
|
iec-C19-sheet-J-16-Amp(3),
|
|
iec-C13-sheet-F-10-Amp-and-iec-C19-sheet-J-16-Amp(4),
|
|
nema-5-20R-20-Amp-and-iec-C13-sheet-F-10-Amp(5),
|
|
nema-5-20R-20-Amp-and-iec-C19-sheet-J-16-Amp(6),
|
|
cee-7-type-E-schuko(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This enumeration represents the type of receptacles installed
|
|
on this receptacle branch. All receptacles on this branch are
|
|
of this type/style.
|
|
|
|
not-specified
|
|
If this value is returned, either the receptacle type has
|
|
not been specified/configured or the agent monitoring this
|
|
PDU does not have a SNMP enumeration defined to the type.
|
|
"
|
|
::= { lgpPduRbEntry 45 }
|
|
|
|
lgpPduRbEntryCapabilities OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
no-optional-capabilities(1),
|
|
measurement-only(2),
|
|
measurement-and-control(3),
|
|
control-only(4),
|
|
current-measurement-only(5),
|
|
current-measurement-and-control(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Receptacle branch capabilities describes what an individual branch
|
|
is capable of.
|
|
|
|
no-optional-capabilities
|
|
The branch is unable to report measurements and lacks
|
|
control capabilities.
|
|
measurement-only
|
|
The branch is capable of reporting multiple measurements.
|
|
measurement-and-control
|
|
The branch is capable of reporting multiple measurements
|
|
and controlling the state.
|
|
control-only
|
|
The branch is capable of controlling the state.
|
|
current-measurement-only
|
|
The branch is capable of reporting the current/amperage only.
|
|
current-measurement-and-control
|
|
The branch is capable of reporting the current/amperage and
|
|
has the ability to control the state."
|
|
::= { lgpPduRbEntry 50 }
|
|
|
|
lgpPduRbEntryLineSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
line-1-neutral(1),
|
|
line-2-neutral(2),
|
|
line-3-neutral(3),
|
|
line-1-line-2(4),
|
|
line-2-line-3(5),
|
|
line-3-line-1(6),
|
|
line-1-line-2-and-line-1-neutral(7),
|
|
line-2-line-3-and-line-2-neutral(8),
|
|
line-3-line-1-and-line-3-neutral(9),
|
|
unknown-line-neutral(10),
|
|
unknown-line-line(11)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This represents the line source that is supplying power to this
|
|
receptacle branch.
|
|
not-specified
|
|
The line source supplying power to the load for this
|
|
receptacle branch has not been specified/configured.
|
|
line-1-N
|
|
The load for this receptacle branch is supplied by
|
|
a line-to-neutral configuration. (line 1 to neutral).
|
|
line-2-N
|
|
The load for this receptacle branch is supplied by
|
|
a line-to-neutral configuration. (line 2 to neutral).
|
|
line-3-N
|
|
The load for this receptacle branch is supplied by
|
|
a line-to-neutral configuration. (line 3 to neutral).
|
|
line-1-line-2
|
|
The load for this receptacle branch is supplied by
|
|
a line-to-line configuration (line 1 to line 2).
|
|
line-2-line-3
|
|
The load for this receptacle branch is supplied by
|
|
a line-to-line configuration (line 2 to line 3).
|
|
line-3-line-1
|
|
The load for this receptacle branch is supplied by
|
|
a line-to-line configuration (line 3 to line 1).
|
|
line-1-line-2-and-line-1-neutral
|
|
The load for this mixed receptacle branch is supplied by
|
|
a line-to-line and line-to-neutral configuration
|
|
(line 1 to line 2 and line 1 to neutral).
|
|
line-2-line-3-and-line-2-neutral
|
|
The load for this mixed receptacle branch is supplied by
|
|
a line-to-line and line-to-neutral configuration
|
|
(line 2 to line 3 and line 2 to neutral).
|
|
line-3-line-1-and-line-3-neutral
|
|
The load for this mixed receptacle branch is supplied by
|
|
a line-to-line and line-to-neutral configuration
|
|
(line 3 to line 1 and line 3 to neutral).
|
|
unknown-line-neutral
|
|
The load for this branch is supplied by
|
|
a line-to-neutral configuration. The system is unable to
|
|
determine which lines are supporting the load.
|
|
unknown-line-line
|
|
The load for this branch is supplied by
|
|
a line-to-line configuration. The system is unable to
|
|
determine which lines are supporting the load.
|
|
"
|
|
::= { lgpPduRbEntry 55 }
|
|
|
|
lgpPduRbEntryRcpCount OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of receptacles on this receptacle branch."
|
|
::= { lgpPduRbEntry 60 }
|
|
|
|
lgpPduRbEntryEpRated OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated Line Voltage for the receptacle branch and its associated
|
|
receptacles (i.e. This is the nominal line voltage that is
|
|
available to the connected load; it is NOT a measured voltage.)"
|
|
::= { lgpPduRbEntry 70 }
|
|
|
|
lgpPduRbEntryEcRated OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the rated input line current for the module
|
|
(it is NOT the measured current)."
|
|
::= { lgpPduRbEntry 75 }
|
|
|
|
lgpPduRbEntryFreqRated OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the rated electrical frequency for the receptacle branch
|
|
and its associated receptacles"
|
|
::= { lgpPduRbEntry 80 }
|
|
|
|
lgpPduRbEntryEnergyAccum OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Kilowatt-Hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total accumulated energy, measured at the receptacle branch input,
|
|
since the last energy reset. Writing a value of 0 (zero) to this
|
|
causes the accumulated energy to be reset. Writing a non-zero
|
|
value is invalid and shall result in a write error and the
|
|
total energy value remains unchanged.
|
|
|
|
If the energy has not been reset and has not wrapped, then this
|
|
is the total energy since installation.
|
|
|
|
This value persists across boot events.
|
|
|
|
NOTE: Resetting this value does not reset the values for the
|
|
individual receptacles."
|
|
::= { lgpPduRbEntry 85 }
|
|
|
|
lgpPduRbEntryEpLNTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Electrical Potential
|
|
measured in Volts RMS (Root Mean Squared)."
|
|
::= { lgpPduRbEntry 100 }
|
|
|
|
lgpPduRbEntryPwr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Real Power (Wattage)"
|
|
::= { lgpPduRbEntry 115 }
|
|
|
|
lgpPduRbEntryAp OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "VoltAmp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Apparent Power (VA)"
|
|
::= { lgpPduRbEntry 120 }
|
|
|
|
lgpPduRbEntryPf OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.01 Power Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Power Factor of the
|
|
receptacle branches' input."
|
|
::= { lgpPduRbEntry 125 }
|
|
|
|
lgpPduRbEntryEcHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Electrical Current
|
|
measured in Amperes RMS (Root Mean Squared)."
|
|
::= { lgpPduRbEntry 130 }
|
|
|
|
lgpPduRbEntryEcThrshldUndrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an under current alarm is activated. If
|
|
the measured current (lgpPduRbEntryEc) is equal to or below
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an under current alarm
|
|
is activated"
|
|
::= { lgpPduRbEntry 135 }
|
|
|
|
lgpPduRbEntryEcThrshldOvrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current warning is activated. If
|
|
the measured current (lgpPduRbEntryEc) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an over current warning
|
|
is activated"
|
|
::= { lgpPduRbEntry 140 }
|
|
|
|
lgpPduRbEntryEcThrshldOvrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current alarm is activated. If
|
|
the measured current (lgpPduRbEntryEcLN) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an over current alarm
|
|
is activated"
|
|
::= { lgpPduRbEntry 145 }
|
|
|
|
lgpPduRbEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount that the current/amperage may increase from its present
|
|
value before an over current alarm occurs."
|
|
::= { lgpPduRbEntry 150 }
|
|
|
|
lgpPduRbEntryEcUsedBeforeAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percent of current utilization relative to the over current
|
|
alarm threshold."
|
|
::= { lgpPduRbEntry 160 }
|
|
|
|
lgpPduRbEntryEpLLTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The line-to-line measurement of the Electrical Potential
|
|
measured in Volts RMS (Root Mean Squared)."
|
|
::= { lgpPduRbEntry 170 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
-- PDU Receptacle Branch - Line/Phase Measurements.
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduRbLineTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduRbLineEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This table contains a list of PDU receptacle branch line/phase
|
|
measurements. The table contains zero, one, or many rows, depending
|
|
upon the number of PDUs and the number of receptacle branches
|
|
on each PDU that are being monitored.
|
|
|
|
The NMS cannot create or delete rows in the table.
|
|
The rows are created by the agent based upon the capabilities of the
|
|
PDU(s) being monitored. Each row in the table represents a
|
|
particular phase/line measurement of a PDU Receptacle
|
|
Branch.
|
|
|
|
Rows in the table are uniquely identified by three indexes representing
|
|
respectively the PDU (lgpPduEntryIndex), the receptacle
|
|
branch (lgpPduRbEntryIndex) and the line/phase being
|
|
measured (lgpPduRbLineEntryIndex).
|
|
"
|
|
::= { lgpPduReceptacleBranch 40 }
|
|
|
|
lgpPduRbLineEntry OBJECT-TYPE
|
|
SYNTAX LgpPduRbLineEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpPduRbLineTable'. The table is
|
|
indexed by three indexes. The 'lgpPduEntryIndex' references
|
|
a PDU in the 'lgpPduTable' to which this receptacle branch
|
|
line/phase measurement belongs. The 'lgpPduRbEntryIndex' together
|
|
with the 'lgpPduEntryIndex' references the receptacle branch
|
|
in the 'lgpPduRbTable'. The 'lgpPduRbLineEntryIndex' represents
|
|
the line/phase of the measurements in the row of this table.
|
|
Together these three indexes uniquely identify a phase/line
|
|
measurement on a receptacle branch within a PDU being monitored
|
|
by this agent.
|
|
"
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex,
|
|
lgpPduRbEntryIndex,
|
|
lgpPduRbLineEntryIndex
|
|
}
|
|
::= { lgpPduRbLineTable 1 }
|
|
|
|
LgpPduRbLineEntry ::= SEQUENCE
|
|
{
|
|
lgpPduRbLineEntryIndex Unsigned32,
|
|
lgpPduRbLineEntryId Unsigned32,
|
|
lgpPduRbLineEntryLine INTEGER,
|
|
lgpPduRbLineEntryEpLNTenths Unsigned32,
|
|
lgpPduRbLineEntryEpLN Unsigned32,
|
|
lgpPduRbLineEntryEc Unsigned32,
|
|
lgpPduRbLineEntryPwr Unsigned32,
|
|
lgpPduRbLineEntryAp Unsigned32,
|
|
lgpPduRbLineEntryPf Integer32,
|
|
lgpPduRbLineEntryEcHundredths Unsigned32,
|
|
lgpPduRbLineEntryEcThrshldUndrAlm Unsigned32,
|
|
lgpPduRbLineEntryEcThrshldOvrWarn Unsigned32,
|
|
lgpPduRbLineEntryEcThrshldOvrAlm Unsigned32,
|
|
lgpPduRbLineEntryEcAvailBeforeAlarmHundredths Unsigned32,
|
|
lgpPduRbLineEntryEcAvailBeforeAlarm Unsigned32,
|
|
lgpPduRbLineEntryEcUsedBeforeAlarm Unsigned32,
|
|
lgpPduRbLineEntryEpLL Unsigned32,
|
|
lgpPduRbLineEntryEpLLTenths Unsigned32
|
|
}
|
|
|
|
lgpPduRbLineEntryIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This is the index that indicates the row of the
|
|
'lgpPduRbLineTable'"
|
|
::= { lgpPduRbLineEntry 1 }
|
|
|
|
lgpPduRbLineEntryId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Runtime assigned branch identifier."
|
|
::= { lgpPduRbLineEntry 5 }
|
|
|
|
lgpPduRbLineEntryLine OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
phase1(1),
|
|
phase2(2),
|
|
phase3(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line number or phase that the measurement for this
|
|
receptacle branch represents for each measurement in this row of
|
|
the table. The phases are as follows:
|
|
Line# Description
|
|
----- ---------------------------------------------------
|
|
1 Line 1-N (A) for Line-to-Neutral measurements
|
|
2 Line 2-N (B) for Line-to-Neutral measurements
|
|
3 Line 3-N (C) for Line-to-Neutral measurements
|
|
|
|
1 Line 1-2 (A-B) for Line-to-Line measurements
|
|
2 Line 2-3 (B-C) for Line-to-Line measurements
|
|
3 Line 3-1 (C-A) for Line-to-Line measurements
|
|
"
|
|
::= { lgpPduRbLineEntry 10 }
|
|
|
|
lgpPduRbLineEntryEpLNTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Electrical Potential
|
|
measured in Volts RMS (Root Mean Squared)."
|
|
::= { lgpPduRbLineEntry 19 }
|
|
|
|
lgpPduRbLineEntryEpLN OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Electrical Potential
|
|
measured in Volts RMS (Root Mean Squared)."
|
|
::= { lgpPduRbLineEntry 20 }
|
|
|
|
lgpPduRbLineEntryEc OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Electrical Current
|
|
measured in Amperes RMS (Root Mean Squared)."
|
|
::= { lgpPduRbLineEntry 21 }
|
|
|
|
lgpPduRbLineEntryPwr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Real Power (Wattage)"
|
|
::= { lgpPduRbLineEntry 22 }
|
|
|
|
lgpPduRbLineEntryAp OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "VoltAmp"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Apparent Power (VA)"
|
|
::= { lgpPduRbLineEntry 23 }
|
|
|
|
lgpPduRbLineEntryPf OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.01 Power Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Power Factor of the
|
|
receptacle branches' input."
|
|
::= { lgpPduRbLineEntry 24 }
|
|
|
|
lgpPduRbLineEntryEcHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-neutral measurement of the Electrical Current
|
|
measured in Amperes RMS (Root Mean Squared)."
|
|
::= { lgpPduRbLineEntry 25 }
|
|
|
|
lgpPduRbLineEntryEcThrshldUndrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The threshold at which an under current alarm is activated. If
|
|
the measured current (lgpPduRbLineEntryEc) is equal to or below
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an under current alarm
|
|
is activated"
|
|
::= { lgpPduRbLineEntry 35 }
|
|
|
|
lgpPduRbLineEntryEcThrshldOvrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The threshold at which an over current warning is activated. If
|
|
the measured current (lgpPduRbLineEntryEc) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an over current warning
|
|
is activated"
|
|
::= { lgpPduRbLineEntry 36 }
|
|
|
|
lgpPduRbLineEntryEcThrshldOvrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The threshold at which an over current alarm is activated. If
|
|
the measured current (lgpPduRbLineEntryEcLN) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an over current alarm
|
|
is activated"
|
|
::= { lgpPduRbLineEntry 37 }
|
|
|
|
lgpPduRbLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The amount that the current/amperage may increase from its present
|
|
value before an over current alarm occurs."
|
|
::= { lgpPduRbLineEntry 39 }
|
|
|
|
lgpPduRbLineEntryEcAvailBeforeAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The amount that the current/amperage may increase from its present
|
|
value before an over current alarm occurs."
|
|
::= { lgpPduRbLineEntry 40 }
|
|
|
|
lgpPduRbLineEntryEcUsedBeforeAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The percent of current utilization relative to the over current
|
|
alarm threshold."
|
|
::= { lgpPduRbLineEntry 41 }
|
|
|
|
lgpPduRbLineEntryEpLL OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-line measurement of the Electrical Potential
|
|
measured in Volts RMS (Root Mean Squared)."
|
|
::= { lgpPduRbLineEntry 60 }
|
|
|
|
lgpPduRbLineEntryEpLLTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 VoltRMS"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The line-to-line measurement of the Electrical Potential
|
|
measured in Volts RMS (Root Mean Squared)."
|
|
::= { lgpPduRbLineEntry 61 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
-- PDU Receptacle (RCP) - Table
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduReceptacle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains information about PDU receptacles."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below."
|
|
::= { lgpPdu 50 }
|
|
|
|
lgpPduRcpTableCount OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of receptacles in the lgpPduRcpTable."
|
|
::= { lgpPduReceptacle 19 }
|
|
|
|
lgpPduRcpTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduRcpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of PDU receptacle entries.
|
|
The table contains numerous rows representing an individual
|
|
receptacle, depending upon the number and configuration of
|
|
the PDU(s) being monitored by the agent.
|
|
|
|
The NMS cannot create or delete rows in the table. The rows are
|
|
created by the agent based upon the capabilities of the managed
|
|
PDU(s). Each row in the table represents a receptacle in
|
|
the system.
|
|
"
|
|
::= { lgpPduReceptacle 20 }
|
|
|
|
lgpPduRcpEntry OBJECT-TYPE
|
|
SYNTAX LgpPduRcpEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpPduRcpTable'. This table is indexed
|
|
by three indexes. The 'lgpPduEntryIndex' references a PDU in
|
|
the 'lgpPduTable' that a given row in this table represents.
|
|
The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex'
|
|
specifies a row in the 'lgpPduRbTable' that the receptacle
|
|
belongs. The 'lgpPduRcpEntryIndex' identifies the particular
|
|
receptacle within the branch.
|
|
"
|
|
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex,
|
|
lgpPduRbEntryIndex,
|
|
lgpPduRcpEntryIndex
|
|
}
|
|
::= { lgpPduRcpTable 1 }
|
|
|
|
LgpPduRcpEntry ::= SEQUENCE
|
|
{
|
|
lgpPduRcpEntryIndex Unsigned32,
|
|
lgpPduRcpEntryId Unsigned32,
|
|
lgpPduRcpEntryUsrLabel DisplayString,
|
|
lgpPduRcpEntryUsrTag1 DisplayString,
|
|
lgpPduRcpEntryUsrTag2 DisplayString,
|
|
lgpPduRcpEntrySysAssignLabel DisplayString,
|
|
lgpPduRcpEntryPosition Unsigned32,
|
|
lgpPduRcpEntryType INTEGER,
|
|
lgpPduRcpEntryLineSource INTEGER,
|
|
lgpPduRcpEntryCapabilities INTEGER,
|
|
lgpPduRcpEntryEp Unsigned32,
|
|
lgpPduRcpEntryEpTenths Unsigned32,
|
|
lgpPduRcpEntryEc Unsigned32,
|
|
lgpPduRcpEntryEcHundredths Unsigned32,
|
|
lgpPduRcpEntryPwrOut Unsigned32,
|
|
lgpPduRcpEntryApOut Unsigned32,
|
|
lgpPduRcpEntryPf Unsigned32,
|
|
lgpPduRcpEntryFreq Unsigned32,
|
|
lgpPduRcpEntryEnergyAccum Unsigned32,
|
|
lgpPduRcpEntryPwrOnDelay Unsigned32,
|
|
lgpPduRcpEntryPwrState INTEGER,
|
|
lgpPduRcpEntryControl INTEGER,
|
|
lgpPduRcpEntryControlLock INTEGER,
|
|
lgpPduRcpEntryEcThrshldUnderAlarm Unsigned32,
|
|
lgpPduRcpEntryEcThrshldOverWarn Unsigned32,
|
|
lgpPduRcpEntryEcThrshldOverAlarm Unsigned32,
|
|
lgpPduRcpEntryEcAvailBeforeAlarmHundredths Unsigned32,
|
|
lgpPduRcpEntryEcAvailBeforeAlarm Unsigned32,
|
|
lgpPduRcpEntryEcUsedBeforeAlarm Unsigned32,
|
|
lgpPduRcpEntryEcCrestFactor Unsigned32,
|
|
lgpPduRcpEntryBlinkLED INTEGER
|
|
}
|
|
|
|
lgpPduRcpEntryIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index that indicates the receptacle position on the
|
|
receptacle branch. This along with the other two indexes on the
|
|
lgpPduRcpTable uniquely identify the receptacle in this table."
|
|
::= { lgpPduRcpEntry 1 }
|
|
|
|
lgpPduRcpEntryId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A runtime assigned receptacle identification number."
|
|
::= { lgpPduRcpEntry 5 }
|
|
|
|
lgpPduRcpEntryUsrLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User assigned label for this receptacle."
|
|
::= { lgpPduRcpEntry 10 }
|
|
|
|
lgpPduRcpEntryUsrTag1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User assigned Tag to assist in identifying or grouping this
|
|
receptacle within the end-users domain."
|
|
::= { lgpPduRcpEntry 15 }
|
|
|
|
lgpPduRcpEntryUsrTag2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User assigned Tag to assist in identifying or grouping this
|
|
receptacle within the end-users domain."
|
|
::= { lgpPduRcpEntry 20 }
|
|
|
|
lgpPduRcpEntrySysAssignLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System assigned identifier representing the receptacle. The value
|
|
is independent of any user assigned label or tag. The exact format
|
|
of this label is system dependent and is subject to change,
|
|
therefore, it should not be referenced for programmatic use."
|
|
::= { lgpPduRcpEntry 25 }
|
|
|
|
lgpPduRcpEntryPosition OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A number representing the position of the receptacle within the
|
|
receptacle branch."
|
|
::= { lgpPduRcpEntry 30 }
|
|
|
|
lgpPduRcpEntryType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
nema-5-20R-20-Amp(1),
|
|
iec-C13-sheet-F-10-Amp(2),
|
|
iec-C19-sheet-J-16-Amp(3),
|
|
cee-7-type-E-schuko(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type or form of receptacle. The enumerations are specified
|
|
in well-known industry standard terms and abbreviations."
|
|
::= { lgpPduRcpEntry 40 }
|
|
|
|
lgpPduRcpEntryLineSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
line-1-N(1),
|
|
line-2-N(2),
|
|
line-3-N(3),
|
|
line-1-line-2(4),
|
|
line-2-line-3(5),
|
|
line-3-line-1(6),
|
|
unknown-line-neutral(7),
|
|
unknown-line-line(8)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This represents the line source that is supplying power to this
|
|
receptacle.
|
|
not-specified
|
|
The line source supplying power to the load for this
|
|
receptacle has not been specified/configured.
|
|
line-1-N
|
|
The load for this receptacle is supplied by
|
|
a line-to-neutral configuration. (line 1 to neutral).
|
|
line-2-N
|
|
The load for this receptacle is supplied by
|
|
a line-to-neutral configuration. (line 2 to neutral).
|
|
line-3-N
|
|
The load for this receptacle is supplied by
|
|
a line-to-neutral configuration. (line 3 to neutral).
|
|
line-1-line-2
|
|
The load for this receptacle is supplied by
|
|
a line-to-line configuration (line 1 to line 2).
|
|
line-2-line-3
|
|
The load for this receptacle is supplied by
|
|
a line-to-line configuration (line 2 to line 3).
|
|
line-3-line-1
|
|
The load for this receptacle is supplied by
|
|
a line-to-line configuration (line 3 to line 1).
|
|
unknown-line-neutral
|
|
The load for this receptacle is supplied by
|
|
a line-to-neutral configuration. The system is unable to
|
|
determine which lines are supporting the load.
|
|
unknown-line-line
|
|
The load for this receptacle is supplied by
|
|
a line-to-line configuration. The system is unable to
|
|
determine which lines are supporting the load.
|
|
"
|
|
::= { lgpPduRcpEntry 45 }
|
|
|
|
lgpPduRcpEntryCapabilities OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
no-optional-capabilities(1),
|
|
measurement-only(2),
|
|
measurement-and-control(3),
|
|
control-only(4),
|
|
current-measurement-only(5),
|
|
current-measurement-and-control(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Receptacle capabilities describes what an individual receptacle is
|
|
capable of.
|
|
|
|
no-optional-capabilities
|
|
The receptacle is unable to report measurements and lacks
|
|
control capabilities.
|
|
measurement-only
|
|
The receptacle is capable of reporting multiple measurements.
|
|
measurement-and-control
|
|
The receptacle is capable of reporting multiple measurements
|
|
and controlling the state.
|
|
control-only
|
|
The receptacle is capable of controlling the state.
|
|
current-measurement-only
|
|
The receptacle is capable of reporting the current/amperage
|
|
only.
|
|
current-measurement-and-control
|
|
The receptacle is capable of reporting the current/amperage and
|
|
has the ability to control the state."
|
|
::= { lgpPduRcpEntry 50 }
|
|
|
|
lgpPduRcpEntryEp OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Volts-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage being delivered to the load attached to the receptacle.
|
|
Alternating Current RMS Electrical Potential measurement."
|
|
::= { lgpPduRcpEntry 55 }
|
|
|
|
lgpPduRcpEntryEpTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Volts-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage being delivered to the load attached to the receptacle.
|
|
Alternating Current RMS Electrical Potential measurement."
|
|
::= { lgpPduRcpEntry 56 }
|
|
|
|
lgpPduRcpEntryEc OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current (amperage) being delivered to the load attached to
|
|
the receptacle. Electrical Current is measured in
|
|
Amperes RMS (Root Mean Squared)."
|
|
::= { lgpPduRcpEntry 60 }
|
|
|
|
lgpPduRcpEntryEcHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amp-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current (amperage) being delivered to the load attached to
|
|
the receptacle. Electrical Current is measured in
|
|
Amperes RMS (Root Mean Squared)."
|
|
::= { lgpPduRcpEntry 61 }
|
|
|
|
lgpPduRcpEntryPwrOut OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Real Power (watts) being delivered to the load attached to
|
|
the receptacle."
|
|
::= { lgpPduRcpEntry 65 }
|
|
|
|
lgpPduRcpEntryApOut OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Volt-Amp-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent Power (volt-amps) being delivered to the load
|
|
attached to the receptacle."
|
|
::= { lgpPduRcpEntry 70 }
|
|
|
|
lgpPduRcpEntryPf OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS ".01 Power Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Receptacle Power Factor, which is the ratio of real power
|
|
to apparent power (i.e. ratio of watts to volts-amps)."
|
|
::= { lgpPduRcpEntry 75 }
|
|
|
|
lgpPduRcpEntryFreq OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured line frequency being delivered to the load
|
|
attached to the receptacle."
|
|
::= { lgpPduRcpEntry 80 }
|
|
|
|
lgpPduRcpEntryEnergyAccum OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Kilowatt-Hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total accumulated energy, measured at the module input, since
|
|
the last energy reset. Writing a value of 0 (zero) to this
|
|
causes the accumulated energy to be reset. Writing a non-zero
|
|
value is invalid and shall result in a write error and the
|
|
total energy value remains unchanged.
|
|
|
|
If the energy has not been reset and has not wrapped,
|
|
then this is the total energy since installation.
|
|
|
|
This value persists across boot events."
|
|
::= { lgpPduRcpEntry 85 }
|
|
|
|
lgpPduRcpEntryPwrOnDelay OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time to wait before power is applied to the
|
|
receptacle after a power strip is turned on or rebooted.
|
|
This can be used to stagger the powering of multiple
|
|
receptacles in order to prevent a large initial current
|
|
draw."
|
|
::= { lgpPduRcpEntry 90 }
|
|
|
|
lgpPduRcpEntryPwrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(0),
|
|
off(1),
|
|
on(2),
|
|
off-pending-on-delay(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"unknown
|
|
The current power state is unknown.
|
|
off
|
|
The current power state of the receptacle is OFF.
|
|
on
|
|
The current power state of the receptacle is ON.
|
|
off-pending-on-delay
|
|
The current power state of the receptacle is OFF. The power
|
|
will be ON at the expiration of the ON delay of this
|
|
receptacle."
|
|
::= { lgpPduRcpEntry 95 }
|
|
|
|
lgpPduRcpEntryControl OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
off(0),
|
|
on(1),
|
|
cycle-power(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object represents the current and persistent (configured)
|
|
power state of the receptacle. The receptacle can also be
|
|
controlled by writing to this object.
|
|
off
|
|
The current and persisted (configured) power state of the
|
|
receptacle is 'off'. When writing 'off' to this object the
|
|
receptacle, if ON, will be turned OFF and its persistent
|
|
(configured) power state will be set to 'off'.
|
|
on
|
|
The current and persisted (configured) power state of the
|
|
receptacle is 'on'. When writing 'on' to this object the
|
|
receptacle, if 'off', will be turned 'on' and its persistent
|
|
(configured) power state will be set to 'on'.
|
|
cycle-power
|
|
The receptacle is currently in a power-cycle state. The
|
|
power to the receptacle is being turned off momentarily and
|
|
will then revert to being 'on'.
|
|
When writing 'cycle-power' to this OBJECT if the receptacle is
|
|
'on' it will be momentarily turned 'off' and then revert to the
|
|
'on' state. The receptacle's persistent (configured) power
|
|
state will be left unchanged ('on').
|
|
|
|
If the receptacle is OFF writing cycle-power has no
|
|
affect on the receptacle.
|
|
"
|
|
::= { lgpPduRcpEntry 100 }
|
|
|
|
lgpPduRcpEntryControlLock OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(0),
|
|
unlocked(1),
|
|
locked(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object represents the locked state of the receptacle.
|
|
|
|
unknown
|
|
The lock state of the receptacle is not known at this time.
|
|
locked
|
|
If the receptacle is 'locked' then its current persisted
|
|
(configured) state can not be changed.
|
|
unlocked
|
|
If the receptacle is 'unlocked', then a user with proper
|
|
permissions may change the receptacles state."
|
|
::= { lgpPduRcpEntry 105 }
|
|
|
|
lgpPduRcpEntryEcThrshldUnderAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an under current alarm is activated. If
|
|
the measured current (lgpPduRbLineEntryEcLL) is equal to or below
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an under current alarm
|
|
is activated"
|
|
::= { lgpPduRcpEntry 150 }
|
|
|
|
lgpPduRcpEntryEcThrshldOverWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current warning is activated. If
|
|
the measured current (lgpPduRbLineEntryEcLL) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an over current warning
|
|
is activated"
|
|
::= { lgpPduRcpEntry 151 }
|
|
|
|
lgpPduRcpEntryEcThrshldOverAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold at which an over current alarm is activated. If
|
|
the measured current (lgpPduRbLineEntryEcLL) is equal to or over
|
|
this percentage of the full scale rated value
|
|
(lgpPduRbEntryEcRated), an over current alarm
|
|
is activated"
|
|
::= { lgpPduRcpEntry 152 }
|
|
|
|
lgpPduRcpEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount that the current/amperage may increase from its present
|
|
value before an over current alarm occurs."
|
|
::= { lgpPduRcpEntry 159 }
|
|
|
|
lgpPduRcpEntryEcAvailBeforeAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Amps-AC-RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount that the current/amperage may increase from its present
|
|
value before an over current alarm occurs."
|
|
::= { lgpPduRcpEntry 160 }
|
|
|
|
lgpPduRcpEntryEcUsedBeforeAlarm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percent of current utilization relative to the over current
|
|
alarm threshold."
|
|
::= { lgpPduRcpEntry 161 }
|
|
|
|
lgpPduRcpEntryEcCrestFactor OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.01"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Receptacle current crest factor, which is the peak amplitude of the
|
|
current waveform divided by the RMS value of the waveform."
|
|
::= { lgpPduRcpEntry 162 }
|
|
|
|
lgpPduRcpEntryBlinkLED OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
noAction(1),
|
|
blinkLED(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Blink the receptacle LED. Writing blinkLED(2) will cause the LED
|
|
to blink for a predefined duration of time. Reading this object
|
|
will always return noAction(1)."
|
|
::= { lgpPduRcpEntry 200 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- PDU Auxiliary Sensors
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPduAuxiliarySensors OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains information about PDU Auxiliary Sensors."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below."
|
|
::= { lgpPdu 60 }
|
|
|
|
lgpPduAuxSensorCount OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of auxiliary sensors in the lgpPduAuxSensorTable."
|
|
::= { lgpPduAuxiliarySensors 5 }
|
|
|
|
lgpPduAuxSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduAuxSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This table contains a list of the PDU's Auxiliary Sensors.
|
|
The table contains zero, one, or more rows, depending
|
|
upon the number of PDUs being monitored and the number of
|
|
auxiliary sensors installed for each PDU.
|
|
The NMS cannot create or delete rows in the table. The rows are
|
|
created by the agent based upon the capabilities of the PDUs
|
|
being monitored. Each row in the table represents an auxiliary
|
|
sensor in a PDU."
|
|
::= { lgpPduAuxiliarySensors 10 }
|
|
|
|
lgpPduAuxSensorEntry OBJECT-TYPE
|
|
SYNTAX LgpPduAuxSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpPduAuxSensorTable'.
|
|
This table is indexed by both the 'lgpPduEntryIndex' which is
|
|
the sole index into the 'lgpPduTable' and the
|
|
'lgpPduAuxSensorIndex'which is a unique identifier for the
|
|
auxiliary sensor attached to the given PDU. Taken together these
|
|
two indexes uniquely identify an Auxiliary Sensor within this
|
|
agent."
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex,
|
|
lgpPduAuxSensorIndex
|
|
}
|
|
::= { lgpPduAuxSensorTable 1 }
|
|
|
|
LgpPduAuxSensorEntry ::= SEQUENCE
|
|
{
|
|
lgpPduAuxSensorIndex Unsigned32,
|
|
lgpPduAuxSensorMeasType INTEGER,
|
|
lgpPduAuxSensorId Unsigned32,
|
|
lgpPduAuxSensorSysAssignLabel DisplayString,
|
|
lgpPduAuxSensorPositionRelative Unsigned32,
|
|
lgpPduAuxSensorUsrLabel DisplayString,
|
|
lgpPduAuxSensorUsrTag1 DisplayString,
|
|
lgpPduAuxSensorUsrTag2 DisplayString,
|
|
lgpPduAuxSensorTempSerialNum DisplayString,
|
|
lgpPduAuxSensorHumSerialNum DisplayString,
|
|
lgpPduAuxSensorTempMeasurementDegF Integer32,
|
|
lgpPduAuxSensorTempThrshldUndrAlmDegF Integer32,
|
|
lgpPduAuxSensorTempThrshldOvrAlmDegF Integer32,
|
|
lgpPduAuxSensorTempThrshldUndrWarnDegF Integer32,
|
|
lgpPduAuxSensorTempThrshldOvrWarnDegF Integer32,
|
|
lgpPduAuxSensorTempMeasurementDegC Integer32,
|
|
lgpPduAuxSensorTempThrshldUndrAlmDegC Integer32,
|
|
lgpPduAuxSensorTempThrshldOvrAlmDegC Integer32,
|
|
lgpPduAuxSensorTempThrshldUndrWarnDegC Integer32,
|
|
lgpPduAuxSensorTempThrshldOvrWarnDegC Integer32,
|
|
lgpPduAuxSensorHumMeasurement Unsigned32,
|
|
lgpPduAuxSensorHumThrshldUndrAlm Unsigned32,
|
|
lgpPduAuxSensorHumThrshldOvrAlm Unsigned32,
|
|
lgpPduAuxSensorHumThrshldUndrWarn Unsigned32,
|
|
lgpPduAuxSensorHumThrshldOvrWarn Unsigned32
|
|
}
|
|
|
|
lgpPduAuxSensorIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"This is the index indicating the nth element of the table."
|
|
::= { lgpPduAuxSensorEntry 1 }
|
|
|
|
lgpPduAuxSensorMeasType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
temperature(1),
|
|
humidity(2),
|
|
temperature-and-humidity(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"not-specified
|
|
The type of sensor is unknown.
|
|
temperature
|
|
The sensor in this row of the table measures temperature.
|
|
humidity
|
|
The sensor in this row of the table measures relative humidity.
|
|
temperature-and-humidity
|
|
The sensor in this row of the table measures both temperature
|
|
and relative humidity."
|
|
::= { lgpPduAuxSensorEntry 5 }
|
|
|
|
lgpPduAuxSensorId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"System assigned auxiliary sensor identification number. The value
|
|
assigned is product specific."
|
|
::= { lgpPduAuxSensorEntry 10 }
|
|
|
|
lgpPduAuxSensorSysAssignLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Label assigned to the auxiliary sensor at runtime by the system.
|
|
The value is independent of any user assigned label or asset tag."
|
|
::= { lgpPduAuxSensorEntry 15 }
|
|
|
|
lgpPduAuxSensorPositionRelative OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Auxiliary sensor relative position. This is a one-based value
|
|
that indicates the sensor's position relative to the sensor string
|
|
connector."
|
|
::= { lgpPduAuxSensorEntry 20 }
|
|
|
|
lgpPduAuxSensorUsrLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"User assigned auxiliary sensor label."
|
|
::= { lgpPduAuxSensorEntry 25 }
|
|
|
|
lgpPduAuxSensorUsrTag1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"User assigned Tag to assist in identifying or grouping this
|
|
auxiliary sensor within the end-users domain."
|
|
::= { lgpPduAuxSensorEntry 30 }
|
|
|
|
lgpPduAuxSensorUsrTag2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"User assigned Tag to assist in identifying or grouping this
|
|
auxiliary sensor within the end-users domain."
|
|
::= { lgpPduAuxSensorEntry 35 }
|
|
|
|
lgpPduAuxSensorTempSerialNum OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The temperature sensor's globally unique serial number assigned at
|
|
the time of manufacture."
|
|
::= { lgpPduAuxSensorEntry 40 }
|
|
|
|
lgpPduAuxSensorHumSerialNum OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The humidity sensor's globally unique serial number assigned at
|
|
the time of manufacture."
|
|
::= { lgpPduAuxSensorEntry 45 }
|
|
|
|
lgpPduAuxSensorTempMeasurementDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Temperature measured at the temperature sensor reported in
|
|
degrees Fahrenheit."
|
|
::= { lgpPduAuxSensorEntry 50 }
|
|
|
|
lgpPduAuxSensorTempThrshldUndrAlmDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Under temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or below this value."
|
|
::= { lgpPduAuxSensorEntry 55 }
|
|
|
|
lgpPduAuxSensorTempThrshldOvrAlmDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Over temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxSensorEntry 60 }
|
|
|
|
lgpPduAuxSensorTempThrshldUndrWarnDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Under temperature warning threshold. A warning is activated if
|
|
the temperature is equal to or below this value."
|
|
::= { lgpPduAuxSensorEntry 65 }
|
|
|
|
lgpPduAuxSensorTempThrshldOvrWarnDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Over temperature warning threshold. A warning is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxSensorEntry 70 }
|
|
|
|
lgpPduAuxSensorTempMeasurementDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Temperature measured at the temperature sensor reported in
|
|
degrees Celsius."
|
|
::= { lgpPduAuxSensorEntry 75 }
|
|
|
|
lgpPduAuxSensorTempThrshldUndrAlmDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Under temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or below this value."
|
|
::= { lgpPduAuxSensorEntry 80 }
|
|
|
|
lgpPduAuxSensorTempThrshldOvrAlmDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Over temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxSensorEntry 85 }
|
|
|
|
lgpPduAuxSensorTempThrshldUndrWarnDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Under temperature warning threshold. A warning is activated if
|
|
the temperature is equal to or below this value."
|
|
::= { lgpPduAuxSensorEntry 90 }
|
|
|
|
lgpPduAuxSensorTempThrshldOvrWarnDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Over temperature warning threshold. A warning is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxSensorEntry 95 }
|
|
|
|
lgpPduAuxSensorHumMeasurement OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Relative Humidity measured at the humidity sensor."
|
|
::= { lgpPduAuxSensorEntry 100 }
|
|
|
|
lgpPduAuxSensorHumThrshldUndrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Under relative humidity alarm threshold. An alarm is activated
|
|
if the relative humidity is equal to or below this value."
|
|
::= { lgpPduAuxSensorEntry 105 }
|
|
|
|
lgpPduAuxSensorHumThrshldOvrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Over relative humidity alarm threshold. An alarm is activated
|
|
if the relative humidity is equal to or above this value."
|
|
::= { lgpPduAuxSensorEntry 110 }
|
|
|
|
lgpPduAuxSensorHumThrshldUndrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Under relative humidity warning threshold. A warning is activated
|
|
if the relative humidity is equal to or below this value."
|
|
::= { lgpPduAuxSensorEntry 115 }
|
|
|
|
lgpPduAuxSensorHumThrshldOvrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Over relative humidity warning threshold. A warning is activated
|
|
if the relative humidity is equal to or above this value."
|
|
::= { lgpPduAuxSensorEntry 120 }
|
|
|
|
lgpPduAuxMeasTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPduAuxMeasEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of the PDU's Auxiliary Sensor Measurements.
|
|
The table contains zero, one, or more rows, depending
|
|
upon the number of PDUs being monitored, the number of auxiliary
|
|
sensors installed for each PDU, and the number of measurements within
|
|
each sensor. The NMS cannot create or delete rows in the table. The
|
|
rows are created by the agent based upon the capabilities of the PDUs
|
|
being monitored. Each row in the table represents an auxiliary
|
|
sensor measurement in a PDU."
|
|
::= { lgpPduAuxiliarySensors 15 }
|
|
|
|
lgpPduAuxMeasEntry OBJECT-TYPE
|
|
SYNTAX LgpPduAuxMeasEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpPduAuxMeasTable'.
|
|
This table is indexed by 'lgpPduEntryIndex' which is
|
|
the sole index into the 'lgpPduTable', 'lgpPduAuxSensorIndex' which
|
|
is a unique identifier for the auxiliary sensor attached to the
|
|
given PDU, and 'lgpPduAuxMeasSensorMeasurementIndex' which is the
|
|
measurement's index identified on the sensor. Taken together these
|
|
three indexes uniquely identify an Auxiliary Sensor Measurement
|
|
within this agent."
|
|
INDEX
|
|
{
|
|
lgpPduEntryIndex,
|
|
lgpPduAuxMeasSensorIndex,
|
|
lgpPduAuxMeasSensorMeasurementIndex
|
|
}
|
|
::= { lgpPduAuxMeasTable 1 }
|
|
|
|
LgpPduAuxMeasEntry ::= SEQUENCE
|
|
{
|
|
lgpPduAuxMeasSensorIndex Unsigned32,
|
|
lgpPduAuxMeasSensorMeasurementIndex Unsigned32,
|
|
lgpPduAuxMeasType INTEGER,
|
|
lgpPduAuxMeasSensorSysAssignLabel DisplayString,
|
|
lgpPduAuxMeasUsrLabel DisplayString,
|
|
lgpPduAuxMeasUsrTag1 DisplayString,
|
|
lgpPduAuxMeasUsrTag2 DisplayString,
|
|
lgpPduAuxMeasSensorSerialNum DisplayString,
|
|
lgpPduAuxMeasTempDegF Integer32,
|
|
lgpPduAuxMeasTempThrshldUndrAlmDegF Integer32,
|
|
lgpPduAuxMeasTempThrshldOvrAlmDegF Integer32,
|
|
lgpPduAuxMeasTempThrshldUndrWarnDegF Integer32,
|
|
lgpPduAuxMeasTempThrshldOvrWarnDegF Integer32,
|
|
lgpPduAuxMeasTempDegC Integer32,
|
|
lgpPduAuxMeasTempThrshldUndrAlmDegC Integer32,
|
|
lgpPduAuxMeasTempThrshldOvrAlmDegC Integer32,
|
|
lgpPduAuxMeasTempThrshldUndrWarnDegC Integer32,
|
|
lgpPduAuxMeasTempThrshldOvrWarnDegC Integer32,
|
|
lgpPduAuxMeasHum Unsigned32,
|
|
lgpPduAuxMeasHumThrshldUndrAlm Unsigned32,
|
|
lgpPduAuxMeasHumThrshldOvrAlm Unsigned32,
|
|
lgpPduAuxMeasHumThrshldUndrWarn Unsigned32,
|
|
lgpPduAuxMeasHumThrshldOvrWarn Unsigned32,
|
|
lgpPduAuxMeasDrClosureState INTEGER,
|
|
lgpPduAuxMeasDrClosureConfig INTEGER,
|
|
lgpPduAuxMeasCntctClosureState INTEGER,
|
|
lgpPduAuxMeasCntctClosureConfig INTEGER
|
|
}
|
|
|
|
lgpPduAuxMeasSensorIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the sensor the measurement is accessed
|
|
from."
|
|
::= { lgpPduAuxMeasEntry 1 }
|
|
|
|
lgpPduAuxMeasSensorMeasurementIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the measurement's index identified on the sensor."
|
|
::= { lgpPduAuxMeasEntry 5 }
|
|
|
|
lgpPduAuxMeasType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
temperature(1),
|
|
humidity(2),
|
|
door-closure(3),
|
|
contact-closure(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"not-specified
|
|
The type of measurement is unknown.
|
|
temperature
|
|
The measurement in this row of the table measures temperature.
|
|
humidity
|
|
The measurement in this row of the table measures relative
|
|
humidity.
|
|
door-closure
|
|
The measurement in this row of the table measures the state of a
|
|
door.
|
|
contact-closure
|
|
The measurement in this row of the table measures the state of a
|
|
contact closure."
|
|
::= { lgpPduAuxMeasEntry 10 }
|
|
|
|
lgpPduAuxMeasSensorSysAssignLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Label assigned to the auxiliary sensor at runtime by the system.
|
|
The value is independent of any user assigned label or asset tag."
|
|
::= { lgpPduAuxMeasEntry 15 }
|
|
|
|
lgpPduAuxMeasUsrLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User assigned auxiliary sensor measurement label."
|
|
::= { lgpPduAuxMeasEntry 20 }
|
|
|
|
lgpPduAuxMeasUsrTag1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User assigned Tag to assist in identifying or grouping this
|
|
auxiliary sensor measurement within the end-users domain."
|
|
::= { lgpPduAuxMeasEntry 25 }
|
|
|
|
lgpPduAuxMeasUsrTag2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User assigned Tag to assist in identifying or grouping this
|
|
auxiliary sensor measurement within the end-users domain."
|
|
::= { lgpPduAuxMeasEntry 30 }
|
|
|
|
lgpPduAuxMeasSensorSerialNum OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor's globally unique serial number assigned at
|
|
the time of manufacture."
|
|
::= { lgpPduAuxMeasEntry 35 }
|
|
|
|
lgpPduAuxMeasTempDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measured at the temperature sensor reported in
|
|
degrees Fahrenheit."
|
|
::= { lgpPduAuxMeasEntry 40 }
|
|
|
|
lgpPduAuxMeasTempThrshldUndrAlmDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Under temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or below this value."
|
|
::= { lgpPduAuxMeasEntry 50 }
|
|
|
|
lgpPduAuxMeasTempThrshldOvrAlmDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxMeasEntry 55 }
|
|
|
|
lgpPduAuxMeasTempThrshldUndrWarnDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Under temperature warning threshold. A warning is activated if
|
|
the temperature is equal to or below this value."
|
|
::= { lgpPduAuxMeasEntry 60 }
|
|
|
|
lgpPduAuxMeasTempThrshldOvrWarnDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over temperature warning threshold. A warning is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxMeasEntry 65 }
|
|
|
|
lgpPduAuxMeasTempDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measured at the temperature sensor reported in
|
|
degrees Celsius."
|
|
::= { lgpPduAuxMeasEntry 70 }
|
|
|
|
lgpPduAuxMeasTempThrshldUndrAlmDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Under temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or below this value."
|
|
::= { lgpPduAuxMeasEntry 75 }
|
|
|
|
lgpPduAuxMeasTempThrshldOvrAlmDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over temperature alarm threshold. An alarm is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxMeasEntry 80 }
|
|
|
|
lgpPduAuxMeasTempThrshldUndrWarnDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Under temperature warning threshold. A warning is activated if
|
|
the temperature is equal to or below this value."
|
|
::= { lgpPduAuxMeasEntry 85 }
|
|
|
|
lgpPduAuxMeasTempThrshldOvrWarnDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over temperature warning threshold. A warning is activated if the
|
|
temperature is equal to or above this value."
|
|
::= { lgpPduAuxMeasEntry 90 }
|
|
|
|
lgpPduAuxMeasHum OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relative Humidity measured at the humidity sensor."
|
|
::= { lgpPduAuxMeasEntry 95 }
|
|
|
|
lgpPduAuxMeasHumThrshldUndrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Under relative humidity alarm threshold. An alarm is activated
|
|
if the relative humidity is equal to or below this value."
|
|
::= { lgpPduAuxMeasEntry 100 }
|
|
|
|
lgpPduAuxMeasHumThrshldOvrAlm OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over relative humidity alarm threshold. An alarm is activated
|
|
if the relative humidity is equal to or above this value."
|
|
::= { lgpPduAuxMeasEntry 105 }
|
|
|
|
lgpPduAuxMeasHumThrshldUndrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Under relative humidity warning threshold. A warning is activated
|
|
if the relative humidity is equal to or below this value."
|
|
::= { lgpPduAuxMeasEntry 110 }
|
|
|
|
lgpPduAuxMeasHumThrshldOvrWarn OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "0.1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over relative humidity warning threshold. A warning is activated
|
|
if the relative humidity is equal to or above this value."
|
|
::= { lgpPduAuxMeasEntry 115 }
|
|
|
|
lgpPduAuxMeasDrClosureState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
open(1),
|
|
closed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of a door sensor measurement.
|
|
not-specified
|
|
The door state is unknown.
|
|
open
|
|
The door is in the open state.
|
|
closed
|
|
The door is in the closed state."
|
|
::= { lgpPduAuxMeasEntry 120 }
|
|
|
|
lgpPduAuxMeasDrClosureConfig OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(0),
|
|
alarm-when-open(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configure door state alarms. This object provides the ability to
|
|
select when a door closure measurement should cause an alarm.
|
|
disabled
|
|
The door state will never result in alarm.
|
|
alarm-when-open
|
|
Activate an alarm when the door state becomes open."
|
|
::= { lgpPduAuxMeasEntry 125 }
|
|
|
|
lgpPduAuxMeasCntctClosureState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
open(1),
|
|
closed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of a contact closure sensor measurement.
|
|
not-specified
|
|
The contact closure state is unknown.
|
|
open
|
|
The contact closure is in the open state.
|
|
closed
|
|
The contact closure is in the closed state."
|
|
::= { lgpPduAuxMeasEntry 130 }
|
|
|
|
lgpPduAuxMeasCntctClosureConfig OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(0),
|
|
alarm-when-open(1),
|
|
alarm-when-closed(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configure contact closure state alarms. This object provides the
|
|
ability to select when a contact closure measurement should
|
|
activate an alarm.
|
|
disabled
|
|
The contact closure state will never result in alarm.
|
|
alarm-when-open
|
|
Activate an alarm when the contact closure state becomes
|
|
open.
|
|
alarm-when-closed
|
|
Activate an alarm when the contact closure state becomes
|
|
closed."
|
|
::= { lgpPduAuxMeasEntry 135 }
|
|
|
|
END
|
|
|