#-MIBFILE: cpqpower.mib
CPQPOWER-MIB DEFINITIONS ::= BEGIN
compaq OBJECT IDENTIFIER ::= { enterprises 232 }
DisplayString ::=
OCTET STRING
PhysAddress ::=
OCTET STRING
mib-2 OBJECT IDENTIFIER ::= { mgmt 1 }
interfaces OBJECT IDENTIFIER ::= { mib-2 2 }
ifTable OBJECT IDENTIFIER ::= { interfaces 2 }
ifEntry OBJECT IDENTIFIER ::= { ifTable 1 }
ifIndex OBJECT IDENTIFIER ::= { ifEntry 1 }
mib-2 OBJECT IDENTIFIER ::= { mgmt 1 }
ifDescr OBJECT IDENTIFIER ::= { ifEntry 2 }
system OBJECT IDENTIFIER ::= { mib-2 1 }
sysName OBJECT IDENTIFIER ::= { system 5 }
sysDescr OBJECT IDENTIFIER ::= { system 1 }
sysContact OBJECT IDENTIFIER ::= { system 4 }
sysLocation OBJECT IDENTIFIER ::= { system 6 }
cpqPower OBJECT IDENTIFIER ::= { compaq 165 }
powerDevice OBJECT IDENTIFIER ::= { cpqPower 1 }
trapInfo OBJECT IDENTIFIER ::= { powerDevice 1 }
managementModuleIdent OBJECT IDENTIFIER ::= { powerDevice 2 }
pdu OBJECT IDENTIFIER ::= { cpqPower 2 }
pduIdent OBJECT IDENTIFIER ::= { pdu 1 }
pduInput OBJECT IDENTIFIER ::= { pdu 2 }
pduOutput OBJECT IDENTIFIER ::= { pdu 3 }
ups OBJECT IDENTIFIER ::= { cpqPower 3 }
upsIdent OBJECT IDENTIFIER ::= { ups 1 }
upsBattery OBJECT IDENTIFIER ::= { ups 2 }
upsInput OBJECT IDENTIFIER ::= { ups 3 }
upsOutput OBJECT IDENTIFIER ::= { ups 4 }
upsBypass OBJECT IDENTIFIER ::= { ups 5 }
upsEnvironment OBJECT IDENTIFIER ::= { ups 6 }
upsTest OBJECT IDENTIFIER ::= { ups 7 }
upsControl OBJECT IDENTIFIER ::= { ups 8 }
upsConfig OBJECT IDENTIFIER ::= { ups 9 }
upsRecep OBJECT IDENTIFIER ::= { ups 10 }
upsTopology OBJECT IDENTIFIER ::= { ups 11 }
pdr OBJECT IDENTIFIER ::= { cpqPower 4 }
pdrIdent OBJECT IDENTIFIER ::= { pdr 1 }
pdrPanel OBJECT IDENTIFIER ::= { pdr 2 }
pdrBreaker OBJECT IDENTIFIER ::= { pdr 3 }
mpdu OBJECT IDENTIFIER ::= { cpqPower 5 }
mpduIdent OBJECT IDENTIFIER ::= { mpdu 1 }
mpduOutput OBJECT IDENTIFIER ::= { mpdu 2 }
mpduDeviceIdent OBJECT IDENTIFIER ::= { mpdu 3 }
mpduSmExtBarOutlet OBJECT IDENTIFIER ::= { mpdu 4 }
trapCode OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "A number identifying the event for the trap that was sent.
Mapped unique trap code per unique event to be used by ISEE's
decoder ring."
::= { trapInfo 1 }
trapDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION "A string identifying the event for that last trap that was sent."
::= { trapInfo 2 }
trapDeviceMgmtUrl OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION "A string contains the URL for the management software."
::= { trapInfo 3 }
trapDeviceDetails OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION "A string details information about the UPS such as SN (serial number),
PN (part number), and MN (Model Name)."
::= { trapInfo 4 }
trapDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION "A string contains the name of the HP Management Module."
::= { trapInfo 5 }
deviceManufacturer OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device manufacturer."
::= { managementModuleIdent 1 }
deviceModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device model."
::= { managementModuleIdent 2 }
deviceFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device firmware version(s)."
::= { managementModuleIdent 3 }
deviceHardwareVersion OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device hardware version."
::= { managementModuleIdent 4 }
deviceIdentName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "A string identifying the device."
::= { managementModuleIdent 5 }
devicePartNumber OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device part number."
::= { managementModuleIdent 6 }
deviceSerialNumber OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device serial number."
::= { managementModuleIdent 7 }
deviceMACAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device MAC address."
::= { managementModuleIdent 8 }
numOfPdu OBJECT-TYPE
SYNTAX INTEGER (0..63)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of PDUs."
::= { pduIdent 1 }
pduIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduIdentEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Aggregate Object with number of entries equal to
NumOfPdu and including the PduIdent group."
::= { pduIdent 2 }
pduIdentEntry OBJECT-TYPE
SYNTAX PduIdentEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The ident table entry containing the name,
model, manufacturer, firmware version, part number, etc."
INDEX { pduIdentIndex }
::= { pduIdentTable 1 }
pduIdentEntry ::=
SEQUENCE {
pduIdentIndex INTEGER,
pduName DisplayString,
pduModel DisplayString,
pduManufacturer DisplayString,
pduFirmwareVersion DisplayString,
pduPartNumber DisplayString,
pduSerialNumber DisplayString,
pduStatus INTEGER,
pduControllable INTEGER
}
pduIdentIndex OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Index for the PduIdentEntry table."
::= { pduIdentEntry 1 }
pduName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The string identify the device."
::= { pduIdentEntry 2 }
pduModel OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device Model."
::= { pduIdentEntry 3 }
pduManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device Manufacturer Name (e.g. Hewlett-Packard)."
::= { pduIdentEntry 4 }
pduFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The firmware revision level of the device."
::= { pduIdentEntry 5 }
pduPartNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device part number."
::= { pduIdentEntry 6 }
pduSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The deice serial number."
::= { pduIdentEntry 7 }
pduStatus OBJECT-TYPE
SYNTAX INTEGER {
other(1),
ok(2),
degraded(3),
failed(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of
failed(4) indicates the device is operating with critical indicators."
::= { pduIdentEntry 8 }
pduControllable OBJECT-TYPE
SYNTAX INTEGER {
yes(1),
no(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "This object indicates whether or not the device is controllable."
::= { pduIdentEntry 9 }
pduInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduInputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Aggregate Object with number of entries equal to
NumOfPdu and including the PduInput group."
::= { pduInput 1 }
pduInputEntry OBJECT-TYPE
SYNTAX PduInputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The input table entry containing the voltage and
current for the PDU"
INDEX { pduInputIndex }
::= { pduInputTable 1 }
pduInputEntry ::=
SEQUENCE {
pduInputIndex INTEGER,
inputVoltage INTEGER,
inputCurrent INTEGER
}
pduInputIndex OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Index for the PduInputEntry table."
::= { pduInputEntry 1 }
inputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input voltage from the PDU meters in volts."
::= { pduInputEntry 2 }
inputCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input current from the PDU meters in amps."
::= { pduInputEntry 3 }
pduOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Aggregate Object with number of entries equal to
NumOfPdu and including the PduInput group."
::= { pduOutput 1 }
pduOutputEntry OBJECT-TYPE
SYNTAX PduOutputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The input table entry containing the name,
heat load, current load, power load, firmware, etc."
INDEX { pduOutputIndex }
::= { pduOutputTable 1 }
pduOutputEntry ::=
SEQUENCE {
pduOutputIndex INTEGER,
pduOutputLoad INTEGER,
pduOutputHeat INTEGER,
pduOutputPower INTEGER,
pduOutputNumBreakers INTEGER
}
pduOutputIndex OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Index for the PduOutputEntry table."
::= { pduOutputEntry 1 }
pduOutputLoad OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device output load in percent of rated capacity. A value of -1 will be
returned if the heat load is unable to be measured."
::= { pduOutputEntry 2 }
pduOutputHeat OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The total heat load measured on the PDU in BTUs. A value of -1 will be
returned if the heat load is unable to be measured."
::= { pduOutputEntry 3 }
pduOutputPower OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The total power load measured on the PDU in watts. A value of -1 will be
returned if the power load is unable to be measured."
::= { pduOutputEntry 4 }
pduOutputNumBreakers OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of breakers for the device. This variable indicates the number
of rows in the breakers table."
::= { pduOutputEntry 5 }
pduOutputBreakerTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutputBreakerEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "List of breaker table entries. The number of entries is given by pduOutputNumBreakers ."
::= { pduOutput 2 }
pduOutputBreakerEntry OBJECT-TYPE
SYNTAX PduOutputBreakerEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "An entry containing information applicable to an breaker."
INDEX { pduOutputIndex , breakerIndex }
::= { pduOutputBreakerTable 1 }
pduOutputBreakerEntry ::=
SEQUENCE {
breakerIndex INTEGER,
breakerVoltage INTEGER,
breakerCurrent INTEGER,
breakerPercentLoad INTEGER,
breakerStatus INTEGER
}
breakerIndex OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The breaker identifier."
::= { pduOutputBreakerEntry 1 }
breakerVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The breaker voltage in volts."
::= { pduOutputBreakerEntry 2 }
breakerCurrent OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The breaker current draw in Amps."
::= { pduOutputBreakerEntry 3 }
breakerPercentLoad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The breaker load in percent."
::= { pduOutputBreakerEntry 4 }
breakerStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
overloadWarning(2),
overloadCritical(3),
voltageRangeWarning(4),
voltageRangeCritical(5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "This object indicates the status of the breaker. A value of normal(1)
indicates the breaker is operating normally. A value of overloadWarning(2)
indicates the breaker has an overload warning. A value of overloadCritical(3)
indicates the breaker is overloaded. A value of voltageRangeWarning(4)
indicates the breaker voltage is out of tolerance by 10-20%. A value of
voltageRangeCritical(5) indicates the breaker voltage is out of tolerance
by more than 20%. Note: Overload status has priority over voltage tolerance
status."
::= { pduOutputBreakerEntry 5 }
upsIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS Manufacturer Name (e.g. Hewlett-Packard)."
::= { upsIdent 1 }
upsIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS Model;Part number;Serial number (e.g. HP R5500 XR;204451-B21;B00123456W)."
::= { upsIdent 2 }
upsIdentSoftwareVersions OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The firmware revision level(s) of the UPS microcontroller(s)."
::= { upsIdent 3 }
upsIdentOemCode OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION "A binary code indicating vendor. This should be a ?0x0c? for HP"
::= { upsIdent 4 }
upsBatTimeRemaining OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Battery run time in seconds before UPS turns off due
to low battery."
::= { upsBattery 1 }
upsBatVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Battery voltage as reported by the UPS meters."
::= { upsBattery 2 }
upsBatCurrent OBJECT-TYPE
SYNTAX INTEGER (-2147483648..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Battery Current as reported by the UPS metering.
Current is positive when discharging, negative
when recharging the battery."
::= { upsBattery 3 }
upsBatCapacity OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Battery percent charge."
::= { upsBattery 4 }
upsBatteryAbmStatus OBJECT-TYPE
SYNTAX INTEGER {
batteryCharging(1),
batteryDischarging(2),
batteryFloating(3),
batteryResting(4),
unknown(5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "Gives the status of the Advanced Battery Management;
batteryFloating(3) status means that the charger is temporarily
charging the battery to its float voltage; batteryResting(4) is the
state when the battery is fully charged and none of the other actions
(charging/discharging/floating) is being done."
::= { upsBattery 5 }
upsInputFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The utility line frequency in tenths of Hz."
::= { upsInput 1 }
upsInputLineBads OBJECT-TYPE
SYNTAX Counter
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of times the Input was out of tolerance
in voltage or frequency."
::= { upsInput 2 }
upsInputNumPhases OBJECT-TYPE
SYNTAX INTEGER (0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION "(null)"
::= { upsInput 3 }
upsInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsInputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Aggregate Object with number of entries equal to
NumPhases and including the UpsInput group."
::= { upsInput 4 }
upsInputEntry OBJECT-TYPE
SYNTAX UpsInputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The input table entry containing the current, voltage, etc."
INDEX { upsInputPhase }
::= { upsInputTable 1 }
upsInputEntry ::=
SEQUENCE {
upsInputPhase INTEGER,
upsInputVoltage INTEGER,
upsInputCurrent INTEGER,
upsInputWatts INTEGER
}
upsInputPhase OBJECT-TYPE
SYNTAX INTEGER (0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of the phase. Serves as index for input table."
::= { upsInputEntry 1 }
upsInputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input voltage from the UPS meters in volts."
::= { upsInputEntry 2 }
upsInputCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input current from the UPS meters in amps."
::= { upsInputEntry 3 }
upsInputWatts OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input real power in watts."
::= { upsInputEntry 4 }
upsInputSource OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
primaryUtility(3),
bypassFeed(4),
secondaryUtility(5),
generator(6),
flywheel(7),
fuelcell(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "The present external source of input power. The enumeration
none(2) indicates that there is no external source of
power, for example, the UPS is On Battery (an internal source).
The bypassFeed(4) can only be used when the Bypass source is known
to be a separate utility feed than the primaryUtility(3)."
::= { upsInput 5 }
upsOutputLoad OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS output load in percent of rated capacity."
::= { upsOutput 1 }
upsOutputFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured UPS output frequency in tenths of Hz."
::= { upsOutput 2 }
upsOutputNumPhases OBJECT-TYPE
SYNTAX INTEGER (0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of metered output phases, serves as the table
index."
::= { upsOutput 3 }
upsOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsOutputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Aggregate Object with number of entries equal to NumPhases
and including the UpsOutput group."
::= { upsOutput 4 }
upsOutputEntry OBJECT-TYPE
SYNTAX UpsOutputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Table Entry containing voltage, current, etc."
INDEX { upsOutputPhase }
::= { upsOutputTable 1 }
upsOutputEntry ::=
SEQUENCE {
upsOutputPhase INTEGER,
upsOutputVoltage INTEGER,
upsOutputCurrent INTEGER,
upsOutputWatts INTEGER
}
upsOutputPhase OBJECT-TYPE
SYNTAX INTEGER (0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number {1..3} of the output phase."
::= { upsOutputEntry 1 }
upsOutputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output voltage from the UPS metering in volts."
::= { upsOutputEntry 2 }
upsOutputCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured UPS output current in amps."
::= { upsOutputEntry 3 }
upsOutputWatts OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured real output power in watts."
::= { upsOutputEntry 4 }
upsOutputSource OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
booster(6),
reducer(7),
parallelCapacity(8),
parallelRedundant(9),
highEfficiencyMode(10)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker."
::= { upsOutput 5 }
upsBypassFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The bypass frequency in tenths of Hz."
::= { upsBypass 1 }
upsBypassNumPhases OBJECT-TYPE
SYNTAX INTEGER (0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of lines in the UPS bypass table."
::= { upsBypass 2 }
upsBypassTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsBypassEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "(null)"
::= { upsBypass 3 }
upsBypassEntry OBJECT-TYPE
SYNTAX UpsBypassEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Entry in the UpsBypassTable."
INDEX { upsBypassPhase }
::= { upsBypassTable 1 }
upsBypassEntry ::=
SEQUENCE {
upsBypassPhase INTEGER,
upsBypassVoltage INTEGER
}
upsBypassPhase OBJECT-TYPE
SYNTAX INTEGER (0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Bypass Phase, index for the table."
::= { upsBypassEntry 1 }
upsBypassVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured UPS bypass voltage in volts."
::= { upsBypassEntry 2 }
upsEnvAmbientTemp OBJECT-TYPE
SYNTAX INTEGER (-100..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading of the ambient temperature in the vicinity of the
UPS or SNMP agent."
::= { upsEnvironment 1 }
upsEnvAmbientLowerLimit OBJECT-TYPE
SYNTAX INTEGER (-100..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Lower Limit of the ambient temperature; if UpsEnvAmbientTemp
falls below this value, the UpsAmbientTempBad alarm will occur."
::= { upsEnvironment 2 }
upsEnvAmbientUpperLimit OBJECT-TYPE
SYNTAX INTEGER (-100..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Upper Limit of the ambient temperature; if UpsEnvAmbientTemp
rises above this value, the UpsAmbientTempBad alarm will occur.
This value should be greater than UpsEnvAmbientLowerLimit."
::= { upsEnvironment 3 }
upsEnvAmbientHumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading of the ambient humidity in the vicinity of the
UPS or SNMP agent."
::= { upsEnvironment 4 }
upsEnvRemoteTemp OBJECT-TYPE
SYNTAX INTEGER (-100..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading of a remote temperature sensor connected to the
UPS or SNMP agent."
::= { upsEnvironment 5 }
upsEnvRemoteHumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading of a remote humidity sensor connected to the
UPS or SNMP agent."
::= { upsEnvironment 6 }
upsEnvNumContacts OBJECT-TYPE
SYNTAX INTEGER (1..1024)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of Contacts in the UpsContactsTable.
This object indicates the number of rows in the
UpsContactsTable."
::= { upsEnvironment 7 }
upsContactsTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsContactsTableEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "A list of Contact Sensing table entries.
The number of entries is given by the value of
UpsEnvNumContacts."
::= { upsEnvironment 8 }
upsContactsTableEntry OBJECT-TYPE
SYNTAX UpsContactsTableEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "An entry containing information applicable
to a particular Contact input."
INDEX { upsContactIndex }
::= { upsContactsTable 1 }
upsContactsTableEntry ::=
SEQUENCE {
upsContactIndex INTEGER,
upsContactType INTEGER,
upsContactState INTEGER,
upsContactDescr DisplayString
}
upsContactIndex OBJECT-TYPE
SYNTAX INTEGER (1..1024)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Contact identifier; identical to the Contact Number."
::= { upsContactsTableEntry 1 }
upsContactType OBJECT-TYPE
SYNTAX INTEGER {
normallyOpen(1),
normallyClosed(2),
anyChange(3),
notUsed(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "The normal state for this contact. The 'other'
state is the Active state for generating the UpstdContactActiveNotice
trap. If anyChange(3) is selected, then this trap is sent
any time the contact changes to either Open or Closed.
No traps are sent if the Contact is set to notUsed(4).
In many cases, the configuration for Contacts may be done by other
means, so this object may be read-only."
::= { upsContactsTableEntry 2 }
upsContactState OBJECT-TYPE
SYNTAX INTEGER {
open(1),
closed(2),
openWithNotice(3),
closedWithNotice(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "The current state of the Contact input;
the value is based on the open/closed input state
and the setting for UpsContactType.
When entering the openWithNotice(3) and closedWithNotice(4)
states, no entries added to the UpsAlarmTable, but
the UpstdContactActiveNotice trap is sent."
::= { upsContactsTableEntry 3 }
upsContactDescr OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "A label identifying the Contact. This object should be
set by the administrator."
::= { upsContactsTableEntry 4 }
upsEnvRemoteTempLowerLimit OBJECT-TYPE
SYNTAX INTEGER (-100..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Lower Limit of the remote temperature; if UpsEnvRemoteTemp
falls below this value, the UpsRemoteTempBad alarm will occur."
::= { upsEnvironment 9 }
upsEnvRemoteTempUpperLimit OBJECT-TYPE
SYNTAX INTEGER (-100..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Upper Limit of the remote temperature; if UpsEnvRemoteTemp
rises above this value, the UpsRemoteTempBad alarm will occur.
This value should be greater than UpsEnvRemoteTempLowerLimit."
::= { upsEnvironment 10 }
upsEnvRemoteHumidityLowerLimit OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Lower Limit of the remote humidity reading; if UpsEnvRemoteHumidity
falls below this value, the UpsRemoteHumidityBad alarm will occur."
::= { upsEnvironment 11 }
upsEnvRemoteHumidityUpperLimit OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Upper Limit of the remote humidity reading; if UpsEnvRemoteHumidity
rises above this value, the UpsRemoteHumidityBad alarm will occur.
This value should be greater than UpsEnvRemoteHumidityLowerLimit."
::= { upsEnvironment 12 }
upsTestBattery OBJECT-TYPE
SYNTAX INTEGER {
startTest(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "Setting this variable to startTest initiates the
battery test. All other set values are invalid."
::= { upsTest 1 }
upsTestBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
passed(2),
failed(3),
inProgress(4),
notSupported(5),
inhibited(6),
scheduled(7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "Reading this enumerated value gives an indication of the
UPS Battery test status."
::= { upsTest 2 }
upsTestTrap OBJECT-TYPE
SYNTAX INTEGER {
startTestTrap(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "Setting this variable to startTestTrap initiates a TrapTest
is sent out from HPMM. All other set values are invalid."
::= { upsTest 3 }
upsControlOutputOffDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Setting this value to other than zero will cause the UPS
output to turn off after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
shutdown."
::= { upsControl 1 }
upsControlOutputOnDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Setting this value to other than zero will cause the UPS
output to turn on after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
startup."
::= { upsControl 2 }
upsControlOutputOffTrapDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "When UpsControlOutputOffDelay reaches this value, a trap will
be sent."
::= { upsControl 3 }
upsControlOutputOnTrapDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS optional
DESCRIPTION "When UpsControlOutputOnDelay reaches this value, a
UpsOutputOff trap will be sent."
::= { upsControl 4 }
upsControlToBypassDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Setting this value to other than zero will cause the UPS
output to go to Bypass after the number of seconds.
If the Bypass is unavailable, this may cause the UPS
to not supply power to the load.
Setting it to 0 will cause an attempt to abort a pending
shutdown."
::= { upsControl 5 }
upsLoadShedSecsWithRestart OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Unlike UpsControlOutputOffDelay, which might or might not,
this object always maps to the XCP 0x8A Load Dump & Restart command,
so the desired shutdown and restart behavior is guaranteed to happen.
Once set, this command cannot be aborted.
This is the preferred Control object to use when performing an On
Battery OS Shutdown."
::= { upsControl 6 }
upsConfigOutputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The nominal UPS Output voltage per phase in volts."
::= { upsConfig 1 }
upsConfigInputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The nominal UPS Input voltage per phase in volts."
::= { upsConfig 2 }
upsConfigOutputWatts OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The nominal UPS available real power output in watts."
::= { upsConfig 3 }
upsConfigOutputFreq OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The nominal output frequency in tenths of Hz."
::= { upsConfig 4 }
upsConfigDateAndTime OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..22))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Date and time information for the UPS. Setting this variable
will initiate a set UPS date and time to this value. Reading
this variable will return the UPS time and date. This value
is not referenced to sysUpTime. It is simply the clock value
from the UPS real time clock.
Format is as follows: MM/DD/YYYY:HH:MM:SS."
::= { upsConfig 5 }
upsConfigLowOutputVoltageLimit OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Lower limit for acceptable Output Voltage, per the UPS
specifications."
::= { upsConfig 6 }
upsConfigHighOutputVoltageLimit OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Upper limit for acceptable Output Voltage, per the UPS
specifications."
::= { upsConfig 7 }
upsNumReceptacles OBJECT-TYPE
SYNTAX INTEGER (0..64)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of independently controllable Receptacles, as described in the
UpsRecepTable."
::= { upsRecep 1 }
upsRecepTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsRecepEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Aggregate Object with number of entries equal to
NumReceptacles and including the UpsRecep group."
::= { upsRecep 2 }
upsRecepEntry OBJECT-TYPE
SYNTAX UpsRecepEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Recep table entry, etc."
INDEX { upsRecepIndex }
::= { upsRecepTable 1 }
upsRecepEntry ::=
SEQUENCE {
upsRecepIndex INTEGER,
upsRecepStatus INTEGER,
upsRecepOffDelaySecs INTEGER,
upsRecepOnDelaySecs INTEGER,
upsRecepAutoOffDelay INTEGER,
upsRecepAutoOnDelay INTEGER,
upsRecepShedSecsWithRestart INTEGER
}
upsRecepIndex OBJECT-TYPE
SYNTAX INTEGER (1..64)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of the Receptacle. Serves as index for Receptacle table."
::= { upsRecepEntry 1 }
upsRecepStatus OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2),
pendingOff(3),
pendingOn(4),
unknown(5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown."
::= { upsRecepEntry 2 }
upsRecepOffDelaySecs OBJECT-TYPE
SYNTAX INTEGER (-1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to
turn off after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abort a pending shutdown.
When this object is set while the UPS is On Battery, it is not necessary
to set UpsRecepOnDelaySecs, since the outlet will turn back on
automatically when power is available again."
::= { upsRecepEntry 3 }
upsRecepOnDelaySecs OBJECT-TYPE
SYNTAX INTEGER (-1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION " The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to
turn on after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abort a pending restart."
::= { upsRecepEntry 4 }
upsRecepAutoOffDelay OBJECT-TYPE
SYNTAX INTEGER (-1..32767)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should
never be turned Off automatically, but must be turned Off only by command.
Values from 0 to 30 are valid, but probably innappropriate.
The AutoOffDelay can be used to prioritize loads in the event of a prolonged
power outage; less critical loads will turn off earlier to extend battery
time for the more critical loads. If the utility power is restored before the
AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off."
::= { upsRecepEntry 5 }
upsRecepAutoOnDelay OBJECT-TYPE
SYNTAX INTEGER (-1..32767)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never
be turned On automatically, but only when specifically commanded to do so.
A value of 0 means that the Receptacle should come On immediately
at power-up or for an On command."
::= { upsRecepEntry 6 }
upsRecepShedSecsWithRestart OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Unlike UpsRecepOffDelaySecs, which might or might not,
this object always maps to the XCP 0x8A Load Dump & Restart command,
so the desired shutdown and restart behavior is guaranteed to happen.
Once set, this command cannot be aborted."
::= { upsRecepEntry 7 }
upsTopologyType OBJECT-TYPE
SYNTAX INTEGER (0..32767)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Value which denotes the type of UPS by its power topology. Values are the
same as those described in the XCP Topology block's Overall Topology field."
::= { upsTopology 1 }
upsTopoMachineCode OBJECT-TYPE
SYNTAX INTEGER (0..32767)
ACCESS read-only
STATUS mandatory
DESCRIPTION "ID Value which denotes the Compaq/HP model of the UPS for software. Values
are the same as those described in the XCP Configuration block's Machine Code
field."
::= { upsTopology 2 }
upsTopoUnitNumber OBJECT-TYPE
SYNTAX INTEGER (0..64)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Identifies which unit and what type of data is being reported.
A value of 0 means that this MIB information comes from the top-level system
view (eg, manifold module or system bypass cabinet reporting total system
output). Standalone units also use a value of 0, since they are the 'full
system' view.
A value of 1 or higher indicates the number of the module in the system
which is reporting only its own data in the HP MIB objects."
::= { upsTopology 3 }
upsTopoPowerStrategy OBJECT-TYPE
SYNTAX INTEGER {
highAlert(1),
standard(2),
enableHighEfficiency(3),
immediateHighEfficiency(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION "Value which denotes which Power Strategy is currently set for the UPS.
The values are:
highAlert(1) - The UPS shall optimize its operating state to maximize its
power-protection levels. This mode will be held for at most 24 hours.
standard(2) - Balanced, normal power protection strategy. UPS will not enter
HE operating mode from this setting.
enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to
optimize its operating state to maximize its efficiency, when
conditions change to permit it (as determined by the UPS).
forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
and if conditions permit, requires the UPS to enter High Efficiency
mode now, without delay (for as long as utility conditions permit).
After successfully set to forceHighEfficiency(4),
UpsTopoPowerStrategy changes to value enableHighEfficiency(3).
UpsOutputSource will indicate if the UPS status is actually operating in
High Efficiency mode."
::= { upsTopology 4 }
pdrName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The string identify the device."
::= { pdrIdent 1 }
pdrModel OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device Model."
::= { pdrIdent 2 }
pdrManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device Manufacturer Name (e.g. Hewlett-Packard)."
::= { pdrIdent 3 }
pdrFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The firmware revision level of the device."
::= { pdrIdent 4 }
pdrPartNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device part number."
::= { pdrIdent 5 }
pdrSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDR's serial number."
::= { pdrIdent 6 }
pdrVARating OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The VA Rating of this PDR (all phases)"
::= { pdrIdent 7 }
pdrNominalOutputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The nominal Output Voltage may differ from the nominal
Input Voltage if the PDR has an input transformer"
::= { pdrIdent 8 }
pdrNumPhases OBJECT-TYPE
SYNTAX INTEGER (1..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of phases for this PDR"
::= { pdrIdent 9 }
pdrNumPanels OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of panels or subfeeds in this PDR"
::= { pdrIdent 10 }
pdrNumBreakers OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of breakers in this PDR"
::= { pdrIdent 11 }
pdrPanelTable OBJECT-TYPE
SYNTAX SEQUENCE OF PdrPanelEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Aggregate Object with number of entries equal to
pdrNumPanels"
::= { pdrPanel 1 }
pdrPanelEntry OBJECT-TYPE
SYNTAX PdrPanelEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The panel table entry containing all power parameters
for each panel."
INDEX { pdrPanelIndex }
::= { pdrPanelTable 1 }
pdrPanelEntry ::=
SEQUENCE {
pdrPanelIndex INTEGER,
pdrPanelFrequency INTEGER,
pdrPanelPower INTEGER,
pdrPanelRatedCurrent INTEGER,
pdrPanelMonthlyKWH INTEGER,
pdrPanelYearlyKWH INTEGER,
pdrPanelTotalKWH INTEGER,
pdrPanelVoltageA INTEGER,
pdrPanelVoltageB INTEGER,
pdrPanelVoltageC INTEGER,
pdrPanelCurrentA INTEGER,
pdrPanelCurrentB INTEGER,
pdrPanelCurrentC INTEGER,
pdrPanelLoadA INTEGER,
pdrPanelLoadB INTEGER,
pdrPanelLoadC INTEGER
}
pdrPanelIndex OBJECT-TYPE
SYNTAX INTEGER (0..10)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Index for the pdrPanelEntry table."
::= { pdrPanelEntry 1 }
pdrPanelFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The present frequency reading for the panel voltage."
::= { pdrPanelEntry 2 }
pdrPanelPower OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The present power of the panel."
::= { pdrPanelEntry 3 }
pdrPanelRatedCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The present rated current of the panel."
::= { pdrPanelEntry 4 }
pdrPanelMonthlyKWH OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The accumulated KWH for this panel since the beginning of this
calendar month or since the last reset."
::= { pdrPanelEntry 5 }
pdrPanelYearlyKWH OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The accumulated KWH for this panel since the beginning of this
calendar year or since the last reset."
::= { pdrPanelEntry 6 }
pdrPanelTotalKWH OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The accumulated KWH for this panel since it was put into service
or since the last reset."
::= { pdrPanelEntry 7 }
pdrPanelVoltageA OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured panel output voltage."
::= { pdrPanelEntry 8 }
pdrPanelVoltageB OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured panel output voltage."
::= { pdrPanelEntry 9 }
pdrPanelVoltageC OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured panel output voltage."
::= { pdrPanelEntry 10 }
pdrPanelCurrentA OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured panel output current."
::= { pdrPanelEntry 11 }
pdrPanelCurrentB OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured panel output current."
::= { pdrPanelEntry 12 }
pdrPanelCurrentC OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured panel output current."
::= { pdrPanelEntry 13 }
pdrPanelLoadA OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The percentage of load is the ratio of each output
current to the rated output current to the panel."
::= { pdrPanelEntry 14 }
pdrPanelLoadB OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The percentage of load is the ratio of each output
current to the rated output current to the panel."
::= { pdrPanelEntry 15 }
pdrPanelLoadC OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The percentage of load is the ratio of each output
current to the rated output current to the panel."
::= { pdrPanelEntry 16 }
pdrBreakerTable OBJECT-TYPE
SYNTAX SEQUENCE OF PdrBreakerEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "List of breaker table entries. The number of entries
is given by pdrNumBreakers for this panel."
::= { pdrBreaker 1 }
pdrBreakerEntry OBJECT-TYPE
SYNTAX PdrBreakerEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a
particular output breaker of a particular panel."
INDEX { pdrPanelIndex , pdrBreakerIndex }
::= { pdrBreakerTable 1 }
pdrBreakerEntry ::=
SEQUENCE {
pdrBreakerIndex INTEGER,
pdrBreakerPanel INTEGER,
pdrBreakerNumPosition INTEGER,
pdrBreakerNumPhases INTEGER,
pdrBreakerNumSequence INTEGER,
pdrBreakerRatedCurrent INTEGER,
pdrBreakerMonthlyKWH INTEGER,
pdrBreakerYearlyKWH INTEGER,
pdrBreakerTotalKWH INTEGER,
pdrBreakerCurrent INTEGER,
pdrBreakerCurrentPercent INTEGER,
pdrBreakerPower INTEGER,
pdrBreakerPercentWarning INTEGER,
pdrBreakerPercentOverload INTEGER
}
pdrBreakerIndex OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The index of breakers. 42 breakers in each panel,
arranged in odd and even columns"
::= { pdrBreakerEntry 1 }
pdrBreakerPanel OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The index of panel that these breakers are installed on."
::= { pdrBreakerEntry 2 }
pdrBreakerNumPosition OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The position of this breaker in the panel, 1-phase breaker
or n-m breaker for 2-phase or n-m-k breaker for 3-phase."
::= { pdrBreakerEntry 3 }
pdrBreakerNumPhases OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of phase for this particular breaker."
::= { pdrBreakerEntry 4 }
pdrBreakerNumSequence OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The sequence of this breaker. i.e. 1 for single phase
1,2 for 2-phase or 1,2,3 for 3-phase."
::= { pdrBreakerEntry 5 }
pdrBreakerRatedCurrent OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The rated current in Amps for this particular breaker."
::= { pdrBreakerEntry 6 }
pdrBreakerMonthlyKWH OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The accumulated KWH for this breaker since the beginning of this
calendar month or since the last reset."
::= { pdrBreakerEntry 7 }
pdrBreakerYearlyKWH OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The accumulated KWH for this breaker since the beginning of this
calendar year or since the last reset."
::= { pdrBreakerEntry 8 }
pdrBreakerTotalKWH OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The accumulated KWH for this breaker since it was put into service
or since the last reset."
::= { pdrBreakerEntry 9 }
pdrBreakerCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output current for this breaker Current."
::= { pdrBreakerEntry 10 }
pdrBreakerCurrentPercent OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The ratio of output current over rated
current for each breaker."
::= { pdrBreakerEntry 11 }
pdrBreakerPower OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The power for this breaker in Watts."
::= { pdrBreakerEntry 12 }
pdrBreakerPercentWarning OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The percentage of Warning set for this breaker."
::= { pdrBreakerEntry 13 }
pdrBreakerPercentOverload OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The percentage of Overload set for this breaker."
::= { pdrBreakerEntry 14 }
mpduNumMPDU OBJECT-TYPE
SYNTAX INTEGER (0..63)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of Modular PDUs (Core) detected."
::= { mpduIdent 1 }
mpduIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF MpduIdentEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Indexed by mpduNumMPDU. So aggregate objects for each entry equal to mpduNumMPDU
before go to the next entry. i.e if 4 MPDU detected, display 4 indexes, 4
Manufacturers, 4 Models..., start with 1."
::= { mpduIdent 2 }
mpduIdentEntry OBJECT-TYPE
SYNTAX MpduIdentEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The table entry containing the identifications of each MPDU as well
as names of PDR panel, location of MPDU in a Data Center."
INDEX { mpduIdentIndex }
::= { mpduIdentTable 1 }
mpduIdentEntry ::=
SEQUENCE {
mpduIdentIndex INTEGER,
mpduManufacturer DisplayString,
mpduModel DisplayString,
mpduName DisplayString,
mpduFirmwareVersion DisplayString,
mpduHardwareVersion DisplayString,
mpduPartNumber DisplayString,
mpduSerialNumber DisplayString,
mpduUUID DisplayString,
mpduIP DisplayString,
mpduMACAddress DisplayString,
mpduControlStatus DisplayString,
mpduRegion DisplayString,
mpduType DisplayString,
mpduPowerRating DisplayString,
mpduInputRating DisplayString,
mpduInputPlug DisplayString,
mpduNumBreakers INTEGER,
mpduNumOutlet INTEGER,
mpduUHeight INTEGER,
mpduRedundantStatus DisplayString
}
mpduIdentIndex OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Index for the MpduIdentEntry table. Start with 1"
::= { mpduIdentEntry 1 }
mpduManufacturer OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU manufacturer."
::= { mpduIdentEntry 2 }
mpduModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU model, marketing name."
::= { mpduIdentEntry 3 }
mpduName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU name, descriptive name or hostname"
::= { mpduIdentEntry 4 }
mpduFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU firmware version(s)."
::= { mpduIdentEntry 5 }
mpduHardwareVersion OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU hardware version."
::= { mpduIdentEntry 6 }
mpduPartNumber OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU part number."
::= { mpduIdentEntry 7 }
mpduSerialNumber OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU external serial number."
::= { mpduIdentEntry 8 }
mpduUUID OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU's UUID equals PN add SN."
::= { mpduIdentEntry 9 }
mpduIP OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU's assigned IP."
::= { mpduIdentEntry 10 }
mpduMACAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU MAC address."
::= { mpduIdentEntry 11 }
mpduControlStatus OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Core PDU Control Status: master or slave units."
::= { mpduIdentEntry 12 }
mpduRegion OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU's Region: NA, Intl, Japan..."
::= { mpduIdentEntry 13 }
mpduType OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU's Type: Delta, Wye, single, Wye+lowline."
::= { mpduIdentEntry 14 }
mpduPowerRating OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU's Power Rating in KVA (Name Plate). Value is presented
in 1/100 of the KVA. i.e. read 1750 means 17.50 KVA"
::= { mpduIdentEntry 15 }
mpduInputRating OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU's Input Current Rating in A (Name Plate)"
::= { mpduIdentEntry 16 }
mpduInputPlug OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The PDU's Input Plug: IEC60309 516P6,NEMA L15-30P..."
::= { mpduIdentEntry 17 }
mpduNumBreakers OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of breakers used in each MPDU (6 by default)."
::= { mpduIdentEntry 18 }
mpduNumOutlet OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of outlets of each MPDU (6 by default)."
::= { mpduIdentEntry 19 }
mpduUHeight OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The MPDU U Height (1U by default)."
::= { mpduIdentEntry 20 }
mpduRedundantStatus OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Status of Core PDU in paired or not: Stand-alone or Redundant."
::= { mpduIdentEntry 21 }
mpduOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF MpduOutputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Indexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU
multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detected,
display 6x4 indexes, 6x4 OutputStatus, 6x4 OutputBreakerRating...start with 1."
::= { mpduOutput 1 }
mpduOutputEntry OBJECT-TYPE
SYNTAX MpduOutputEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The output table entry containing the voltage, current, PF,
percent load, VA, Watts for the Modular PDU."
INDEX { mpduIdentIndex , mpduOutputIndex }
::= { mpduOutputTable 1 }
mpduOutputEntry ::=
SEQUENCE {
mpduOutputIndex INTEGER,
mpduOutputStatus DisplayString,
mpduOutputBreakerRating INTEGER,
mpduOutputSmartDevice DisplayString,
mpduOutputPercentLoad INTEGER,
mpduOutputVoltage INTEGER,
mpduOutputCurrent INTEGER,
mpduOutputPowerVA INTEGER,
mpduOutputPowerWatt INTEGER,
mpduOutputPowerFactor INTEGER,
mpduOutputWarningThreshold INTEGER,
mpduOutputCriticalThreshold INTEGER
}
mpduOutputIndex OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Index for the MpduOutputEntry table."
::= { mpduOutputEntry 1 }
mpduOutputStatus OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The overall status of the device: off, on, problem."
::= { mpduOutputEntry 2 }
mpduOutputBreakerRating OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The rating of each MPDU Output in Ampere."
::= { mpduOutputEntry 3 }
mpduOutputSmartDevice OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "A smart cord device detected: False, True."
::= { mpduOutputEntry 4 }
mpduOutputPercentLoad OBJECT-TYPE
SYNTAX INTEGER (0..200)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The MPDU's each output load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value
of -1 will be returned if the current is unable to be measured."
::= { mpduOutputEntry 5 }
mpduOutputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value
of -1 will be returned if the voltage is unable to be measured."
::= { mpduOutputEntry 6 }
mpduOutputCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value
of -1 will be returned if the current is unable to be measured."
::= { mpduOutputEntry 7 }
mpduOutputPowerVA OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The total VA load (VI) measured on the PDU in VA. A value
of -1 will be returned if the power is unable to be calculated."
::= { mpduOutputEntry 8 }
mpduOutputPowerWatt OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The total power load measured on the PDU in Watts. A value
of -1 will be returned if the power is unable to be calculated."
::= { mpduOutputEntry 9 }
mpduOutputPowerFactor OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable
to be measured."
::= { mpduOutputEntry 10 }
mpduOutputWarningThreshold OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Report the User-set threshhold limit for Warning in percentage"
::= { mpduOutputEntry 11 }
mpduOutputCriticalThreshold OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Report the User-set threshhold limit for Critical in percentage"
::= { mpduOutputEntry 12 }
mpduDeviceIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF MpduDeviceIdentEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Indexed by mpduNumOutlet. So aggregate objects for each entry equal
to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry.
i.e if 4 MPDU detected, display 6x4 indexes, 6x4 mpduDeviceStatus, 6x4
DeviceUIDStatus...start with 1."
::= { mpduDeviceIdent 1 }
mpduDeviceIdentEntry OBJECT-TYPE
SYNTAX MpduDeviceIdentEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "The ident table entry containing the name, model,
manufacturer, firmware version, part number... for
each smart device, null value for unknown device."
INDEX { mpduIdentIndex , mpduDeviceIdentIndex }
::= { mpduDeviceIdentTable 1 }
mpduDeviceIdentEntry ::=
SEQUENCE {
mpduDeviceIdentIndex INTEGER,
mpduDeviceStatus DisplayString,
mpduDeviceUIDStatus DisplayString,
mpduDeviceNumOutlet INTEGER,
mpduDeviceUHeight INTEGER,
mpduDevicePowerRating DisplayString,
mpduDeviceManufacturer DisplayString,
mpduDeviceType DisplayString,
mpduDeviceModel DisplayString,
mpduDeviceName DisplayString,
mpduDeviceFirmwareVersion DisplayString,
mpduDeviceHardwareVersion DisplayString,
mpduDevicePartNumber DisplayString,
mpduDeviceSerialNumber DisplayString,
mpduDeviceUUID DisplayString
}
mpduDeviceIdentIndex OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Index is based on the total number of Smart Extension Bars plus
smart devices (with smart cord i.e. blades) detected."
::= { mpduDeviceIdentEntry 1 }
mpduDeviceStatus OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The overall status of the device: off, on, problem."
::= { mpduDeviceIdentEntry 2 }
mpduDeviceUIDStatus OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The overall status of the device UID: off, on, blink."
::= { mpduDeviceIdentEntry 3 }
mpduDeviceNumOutlet OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of outlets of detected the device. This variable
indicates the number of rows in the breakers table. Default is 5"
::= { mpduDeviceIdentEntry 4 }
mpduDeviceUHeight OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The U height of ext bar or device."
::= { mpduDeviceIdentEntry 5 }
mpduDevicePowerRating OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device's Power Rating in VA. Enter null if not detected."
::= { mpduDeviceIdentEntry 6 }
mpduDeviceManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device Manufacturer Name (e.g. Hewlett-Packard).
Enter null if not detected."
::= { mpduDeviceIdentEntry 7 }
mpduDeviceType OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device's Type: Ext Bar, server, or network device..."
::= { mpduDeviceIdentEntry 8 }
mpduDeviceModel OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device Model is Managed or Non-managed Ext Bar. Enter null if not detected."
::= { mpduDeviceIdentEntry 9 }
mpduDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The string identify the Device. i.e. 'BAR#1' (descriptive name)
Enter null if not detected."
::= { mpduDeviceIdentEntry 10 }
mpduDeviceFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The firmware revision level of Sm Ext Bar. Enter null if not detected."
::= { mpduDeviceIdentEntry 11 }
mpduDeviceHardwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The hardware version of Sm Ext Bar. Enter null if not detected."
::= { mpduDeviceIdentEntry 12 }
mpduDevicePartNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device's part number. Enter null if not detected."
::= { mpduDeviceIdentEntry 13 }
mpduDeviceSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device's serial number. Enter null if not detected"
::= { mpduDeviceIdentEntry 14 }
mpduDeviceUUID OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The device's UUID. Enter null if not detected"
::= { mpduDeviceIdentEntry 15 }
mpduSmExtBarOutletTable OBJECT-TYPE
SYNTAX SEQUENCE OF MpduSmExtBarOutletEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Indexed by mpduDeviceNumOutlet. So aggregate objects for each entry equal to
(mpduNumMPDU multiplies mpduNumOutlet multiplies mpduDeviceNumOutlet) before
go to the next entry. i.e if 4 MPDU detected, display 5x6x4 indexes, 5x6x4
mpduSmExtBarOutletStatus, 5x6x4 mpduSmExtBarOutletUIDStatus...start with 1."
::= { mpduSmExtBarOutlet 1 }
mpduSmExtBarOutletEntry OBJECT-TYPE
SYNTAX MpduSmExtBarOutletEntry
ACCESS read-only
STATUS mandatory
DESCRIPTION "Entries contain status, measurements for each outlet (no PowerVA)
Display null if it can't be measured or no device detected."
INDEX { mpduIdentIndex , mpduOutputIndex, mpduSmExtBarOutletIndex }
::= { mpduSmExtBarOutletTable 1 }
mpduSmExtBarOutletEntry ::=
SEQUENCE {
mpduSmExtBarOutletIndex INTEGER,
mpduSmExtBarOutletStatus DisplayString,
mpduSmExtBarOutletUIDStatus DisplayString,
mpduSmExtBarOutletRating INTEGER,
mpduSmExtBarOutletVoltage INTEGER,
mpduSmExtBarOutletCurrent INTEGER,
mpduSmExtBarOutletPowerWatt INTEGER,
mpduSmExtBarOutletPowerFactor INTEGER,
mpduSmExtBarOutletDeviceName DisplayString,
mpduSmExtBarOutletDeviceUUID DisplayString,
mpduSmExtBarOutletDeviceProduct DisplayString,
mpduSmExtBarOutletDeviceIP DisplayString,
mpduSmExtBarOutletAutoDiscovered INTEGER
}
mpduSmExtBarOutletIndex OBJECT-TYPE
SYNTAX INTEGER (0..300)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Index of Smart Extension Bar."
::= { mpduSmExtBarOutletEntry 1 }
mpduSmExtBarOutletStatus OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The overall status of the Smart Extension Bar's outlet: off, on, problem..."
::= { mpduSmExtBarOutletEntry 2 }
mpduSmExtBarOutletUIDStatus OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "The overall status of the Smart Extension Bar's UID: off, on, blink..."
::= { mpduSmExtBarOutletEntry 3 }
mpduSmExtBarOutletRating OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "Sm Ext Bar Outlet's Rating in Amp. A value of -1 will be returned
if the stick is unable to detect."
::= { mpduSmExtBarOutletEntry 4 }
mpduSmExtBarOutletVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The SM Ext Bar voltage in volts. Value is presented 1/10 of the Volt
i.e. 2098 is 209.8 V. A value of -1 will be returned if the voltage is unable
to be measured."
::= { mpduSmExtBarOutletEntry 5 }
mpduSmExtBarOutletCurrent OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The SM Ext Bar current draw in Amps. Value is presented in 1/100 of the Ampere
i.e. 127 is 1.27 A. A value of -1 will be returned if the current is unable
to be measured."
::= { mpduSmExtBarOutletEntry 6 }
mpduSmExtBarOutletPowerWatt OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Sm Ext Bar's Power measured in Watts. A value of -1 will be returned if the
power is unable to be measured."
::= { mpduSmExtBarOutletEntry 7 }
mpduSmExtBarOutletPowerFactor OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The outlet's power factor in 0.01 unit. It is presented in 1/100 of the unit.
i.e. 98 is 0.98. A value of -1 will be returned if the power factor is unable
to be measured."
::= { mpduSmExtBarOutletEntry 8 }
mpduSmExtBarOutletDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device (Blade/Server/Storage) Name that connects to this
Sm Ext Bar. Enter null if not detected"
::= { mpduSmExtBarOutletEntry 9 }
mpduSmExtBarOutletDeviceUUID OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device (Blade/Server/Storage) UUID that connects to this
Sm Ext Bar. Enter null if not detected"
::= { mpduSmExtBarOutletEntry 10 }
mpduSmExtBarOutletDeviceProduct OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device (Blade/Server/Storage) Model that connects to this
Sm Ext Bar. Enter null if not detected"
::= { mpduSmExtBarOutletEntry 11 }
mpduSmExtBarOutletDeviceIP OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Device (Blade/Server/Storage) IP of iLO that connects to this
Sm Ext Bar. Enter null if not detected"
::= { mpduSmExtBarOutletEntry 12 }
mpduSmExtBarOutletAutoDiscovered OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Boolean values of 0 or 1. 1 means this Sm Ext Bar Outlet is able to get information
from a blade with smart power supply (auto discovery is enabled)..."
::= { mpduSmExtBarOutletEntry 13 }
trapCritical TRAP-TYPE
ENTERPRISE cpqPower
VARIABLES { sysName, trapCode, trapDescription, trapDeviceName, trapDeviceDetails, trapDeviceMgmtUrl }
--#TYPE "Critical Alarm"
--#SEVERITY CRITICAL
--#CATEGORY "PowerDevice"
DESCRIPTION "A critical alarm has occurred. Action: Check the Trap Details for more information."
::= 1
trapWarning TRAP-TYPE
ENTERPRISE cpqPower
VARIABLES { sysName, trapCode, trapDescription, trapDeviceName, trapDeviceDetails, trapDeviceMgmtUrl }
--#TYPE "Warning Alarm"
--#SEVERITY MINOR
--#CATEGORY "PowerDevice"
DESCRIPTION "A warning alarm has occurred. Action: Check the Trap Details for more information."
::= 2
trapInformation TRAP-TYPE
ENTERPRISE cpqPower
VARIABLES { sysName, trapCode, trapDescription, trapDeviceName, trapDeviceDetails, trapDeviceMgmtUrl }
--#TYPE "Information Alarm"
--#SEVERITY INFORMATIONAL
--#CATEGORY "PowerDevice"
DESCRIPTION "An informational alarm has occurred. Action: Check the Trap Details for more information."
::= 3
trapCleared TRAP-TYPE
ENTERPRISE cpqPower
VARIABLES { sysName, trapCode, trapDescription, trapDeviceName, trapDeviceDetails, trapDeviceMgmtUrl }
--#TYPE "Cleared Alarm"
--#SEVERITY INFORMATIONAL
--#CATEGORY "PowerDevice"
DESCRIPTION "An alarm has cleared. Action: Check the Trap Details for more information."
::= 4
trapTest TRAP-TYPE
ENTERPRISE cpqPower
VARIABLES { sysName, trapCode, trapDescription, trapDeviceName, trapDeviceDetails, trapDeviceMgmtUrl }
--#TYPE "Test Trap"
--#SEVERITY INFORMATIONAL
--#CATEGORY "PowerDevice"
DESCRIPTION "Test trap sent to a trap receiver to check proper reception of traps"
::= 5
deviceTrapInitialization TRAP-TYPE
ENTERPRISE cpqPower
VARIABLES { sysName, deviceIdentName }
--#TYPE "Device Initialization"
--#SEVERITY INFORMATIONAL
--#CATEGORY "PowerDevice"
DESCRIPTION "This trap is sent each time a power device is initialized."
::= 6
END