1284 lines
126 KiB
Plaintext

# -----------------------------------------------------------------------------
# APC PowerNet & RFC 1628 UPS Trap Definition File
# -----------------------------------------------------------------------------
# Copyright (c) 2007 American Power Conversion, Inc.
#
# Name : apctraps387.tdf
#
# Generated by script: totdf.awk
#
# Input File: powernetPS.mib
#
# Created: Wednesday, January, 03, 2007
#
# Revision History:
# -----------------------------------------------------------------------------
#
# APC PowerNet Traps
#
#
[DeviceClassSection]
1=1.3.6.1.4.1.318
[1.3.6.1.4.1.318]
FirstEntry=Default,NONE
LastEntry=NONE,1000
Default=G0,FirstEntry,4,LOG,NOMAP,NOBELL,NONE,NONE,NONE,NONE,System: Unknown trap.
G0=G1,Default,0,LOG,MAP,NOBELL,NONE,NONE,NONE,NONE,System: Cold start.
G1=G4,0,0,LOG,MAP,NOBELL,NONE,NONE,NONE,NONE,System: Warm start.
G4=1,1,1,LOG,MAP,NOBELL,NONE,NONE,NONE,NONE,System: SNMP authentication failure.
1=2,G4,0,LOG,MAP,NOBELL,PLUS,8,NONE,X3180001,APC UPS: Communication lost
2=3,1,0,LOG,MAP,NOBELL,PLUS,33,NONE,X3180002,APC UPS: Overload
3=4,2,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180003,APC UPS: Failed self-test
4=5,3,0,LOG,MAP,NOBELL,PLUS,38,NONE,X3180004,APC UPS: batteries are discharged
5=6,4,1,LOG,MAP,BELL,PLUS,9,NONE,X3180005,APC UPS: On battery
6=7,5,1,LOG,MAP,NOBELL,PLUS,34,NONE,X3180006,APC UPS: SmartBoost(TM)
7=8,6,0,LOG,MAP,NOBELL,PLUS,11,NONE,X3180007,APC UPS: Low battery
8=9,7,2,LOG,MAP,NOBELL,MINUS,1,NONE,X3180008,APC UPS: Communication established
9=10,8,2,LOG,MAP,NOBELL,MINUS,5,NONE,X3180009,APC UPS: Utility power restored
10=11,9,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180010,APC UPS: Passed self-test
11=12,10,2,LOG,MAP,NOBELL,MINUS,7,NONE,X3180011,APC UPS: Returned from Low-Battery condition
12=13,11,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180012,APC UPS: Turned off
13=14,12,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180013,APC UPS: Entered sleep mode
14=15,13,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180014,APC UPS: Wake up
15=16,14,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180015,APC UPS: Starting reboot
16=17,15,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180016,APC UPS: DIP switch altered
17=18,16,0,LOG,MAP,NOBELL,PLUS,36,NONE,X3180017,APC UPS: UPS batteries need replacement
18=19,17,0,LOG,MAP,NOBELL,PLUS,19,1,X3180018,APC Environment: Contact $1 fault
19=20,18,2,LOG,MAP,NOBELL,MINUS,18,1,X3180019,APC Environment: Contact $1 fault cleared.
20=21,19,0,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180020,APC UPS: On bypass due to internal fault
21=22,20,1,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180021,APC UPS: On bypass by user via software or panel
22=23,21,1,LOG,MAP,NOBELL,PLUS,23,NONE,X3180022,APC UPS: On bypass initiated by user
23=24,22,2,LOG,MAP,NOBELL,MINUS,22,NONE,X3180023,APC UPS: UPS has returned from bypass
24=25,23,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180024,APC UPS: Base module bypass power supply needs repair
25=26,24,0,LOG,MAP,NOBELL,PLUS,637,NONE,X3180025,APC UPS: Base module fan needs repair
26=27,25,0,LOG,MAP,NOBELL,PLUS,27,NONE,X3180026,APC UPS: Communication lost with battery packs
27=28,26,2,LOG,MAP,NOBELL,MINUS,26,NONE,X3180027,APC UPS: Communication established with battery packs
28=29,27,2,LOG,MAP,NOBELL,PLUS,37,NONE,X3180028,APC UPS: Calibration initiated
29=30,28,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180029,APC SNMP Agent: Agent restarting
30=31,29,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180030,APC UPS: A UPS is turned on.
31=32,30,1,LOG,MAP,NOBELL,PLUS,35,NONE,X3180031,APC UPS: SmartTrim(TM) reducing
32=33,31,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180032,APC CODE: Authentication on agent code image is done.
33=34,32,2,LOG,MAP,NOBELL,MINUS,2,NONE,X3180033,APC UPS: Overload cleared.
34=35,33,2,LOG,MAP,NOBELL,MINUS,6,NONE,X3180034,APC UPS: SmartBoost(TM) off.
35=36,34,2,LOG,MAP,NOBELL,MINUS,31,NONE,X3180035,APC UPS: SmartTrim(TM) reducing off
36=37,35,2,LOG,MAP,NOBELL,MINUS,17,NONE,X3180036,APC UPS: Bad battery replaced
37=38,36,2,LOG,MAP,NOBELL,MINUS,28,NONE,X3180037,APC UPS: Calibration end
38=39,37,2,LOG,MAP,NOBELL,MINUS,4,NONE,X3180038,APC UPS: Discharge cleared.
39=41,38,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180039,APC UPS: A graceful shutdown has been initiated.
41=42,39,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180041,APC PDU: Outlet $1 has been turned on.
42=43,41,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180042,APC PDU: Outlet $1 has turned off.
43=44,42,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180043,APC PDU: Outlet $1 has rebooted.
44=45,43,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180044,APC: The SNMP configuration has been changed.
45=46,44,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180045,APC PDU: Outlet $1 configuration has been changed.
46=47,45,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180046,APC: Access violation via the console.
47=48,46,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180047,APC: Access violation via HTTP.
48=49,47,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180048,APC: Password change for the device.
49=50,48,1,LOG,MAP,NOBELL,MINUS,50,NONE,X3180049,APC UPS: Bad output voltage.
50=51,49,2,LOG,MAP,NOBELL,PLUS,49,NONE,X3180050,APC UPS: The bad voltage output condition has been cleared.
51=52,50,1,LOG,MAP,NOBELL,MINUS,52,NONE,X3180051,APC UPS: The battery charger has failed.
52=53,51,2,LOG,MAP,NOBELL,PLUS,51,NONE,X3180052,APC UPS: The battery charger failure condition cleared
53=54,52,1,LOG,MAP,NOBELL,MINUS,54,NONE,X3180053,APC UPS: The battery temperature threshold has been violated.
54=55,53,2,LOG,MAP,NOBELL,PLUS,53,NONE,X3180054,APC UPS: The battery over temperature has been cleared.
55=56,54,1,LOG,MAP,NOBELL,MINUS,56,NONE,X3180055,APC UPS: SmartBoost(TM) or SmartTrim(TM) relay fault.
56=57,55,2,LOG,MAP,NOBELL,PLUS,55,NONE,X3180056,APC UPS: SmartBoost(TM) or SmartTrim(TM) relay fault cleared.
57=58,56,0,LOG,MAP,NOBELL,PLUS,58,NONE,X3180057,APC Environmental Monitor: Probe 1 humidity threshold violation
58=59,57,2,LOG,MAP,NOBELL,MINUS,57,NONE,X3180058,APC Environmental Monitor: Probe 1 humidity violation cleared
59=60,58,0,LOG,MAP,NOBELL,PLUS,60,NONE,X3180059,APC Environmental Monitor: Probe 1 temperature violation
60=61,59,2,LOG,MAP,NOBELL,MINUS,59,NONE,X3180060,APC Environmental Monitor: Probe 1 temperature violation cleared
61=62,60,0,LOG,MAP,NOBELL,PLUS,62,NONE,X3180061,APC Environmental Monitor: Probe 2 humidity violation
62=63,61,2,LOG,MAP,NOBELL,MINUS,61,NONE,X3180062,APC Environmental Monitor: Probe 2 humidity violation cleared
63=64,62,0,LOG,MAP,NOBELL,PLUS,64,NONE,X3180063,APC Environmental Monitor: Probe 2 temperature violation
64=65,63,2,LOG,MAP,NOBELL,MINUS,63,NONE,X3180064,APC Environmental Monitor: Probe 2 temperature violation cleared
65=66,64,2,LOG,MAP,NOBELL,MINUS,66,NONE,X3180065,APC Environmental Monitor: Communication established
66=67,65,0,LOG,MAP,NOBELL,PLUS,65,NONE,X3180066,APC Environmental Monitor: Communication failure
67=68,66,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180067,APC UPS: The number of batteries has increased.
68=69,67,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180068,APC UPS: The number of batteries has decreased.
69=70,68,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180069,APC UPS: The number of power modules has increased.
70=71,69,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180070,APC UPS: The number of power modules has decreased.
71=72,70,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180071,APC UPS: An intelligence module has been inserted.
72=73,71,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180072,APC UPS: An intelligence module has been removed.
73=74,72,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180073,APC UPS: A redundant intelligence module has been inserted.
74=75,73,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180074,APC UPS: A redundant intelligence module has been removed.
75=76,74,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180075,APC UPS: An external battery frame has been added.
76=77,75,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180076,APC UPS: An external battery frame has been removed.
77=78,76,0,LOG,MAP,NOBELL,PLUS,78,1,X3180077,APC $2
78=79,77,2,LOG,MAP,NOBELL,MINUS,77,1,X3180078,APC $2
79=80,78,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180079,APC : The status of the device being monitored has changed.
80=81,79,1,LOG,MAP,NOBELL,PLUS,81,NONE,X3180080,APC UPS: No batteries attached.
81=82,80,2,LOG,MAP,NOBELL,MINUS,80,NONE,X3180081,APC UPS: The no batteries attached condition has been cleared.
82=83,81,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180082,APC: A new user has been added.
83=84,82,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180083,APC: A user has been deleted.
84=85,83,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180084,APC: A user has been modified.
85=86,84,2,LOG,MAP,NOBELL,MINUS,86,1,X3180085,APC: Communications established with the MasterSwitch VM.
86=87,85,0,LOG,MAP,NOBELL,PLUS,85,1,X3180086,APC: Communications lost with the MasterSwitch VM.
87=88,86,0,LOG,MAP,NOBELL,PLUS,88,1,X3180087,APC: The MasterSwitch VM is near or at an overload condition.
88=89,87,2,LOG,MAP,NOBELL,MINUS,87,1,X3180088,APC: The overload condition cleared on the MasterSwitch VM.
89=90,88,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180089,APC: An outlet on the MasterSwitch VM has turned on.
90=91,89,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180090,APC: An outlet on the MasterSwitch VM has turned off.
91=92,90,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180091,APC: A device configuration change on a MasterSwitch VM.
92=93,91,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180092,APC: An outlet configuration change on a MasterSwitch VM.
93=94,92,2,LOG,MAP,NOBELL,PLUS,94,NONE,X3180093,APC: The MasterSwitch VM has violated the low load threshold.
94=95,93,2,LOG,MAP,NOBELL,MINUS,93,NONE,X3180094,APC: The low load condition cleared on the MasterSwitch VM.
95=96,94,0,LOG,MAP,NOBELL,PLUS,96,NONE,X3180095,APC: The MasterSwitch VM is near or at an overload condition.
96=97,95,2,LOG,MAP,NOBELL,MINUS,95,NONE,X3180096,APC: The overload condition cleared on the MasterSwitch VM.
97=98,96,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180097,APC: The power supply status changed on MasterSwitch VM
98=99,97,2,LOG,MAP,NOBELL,MINUS,99,1,X3180098,APC: Communications established with the MasterSwitch plus.
99=100,98,0,LOG,MAP,NOBELL,PLUS,98,1,X3180099,APC: Communications lost with the MasterSwitch plus.
100=101,99,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180100,APC: An outlet on the MasterSwitch plus has turned on.
101=102,100,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180101,APC: An outlet on the MasterSwitch plus has turned off.
102=103,101,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180102,APC: A device configuration change on a MasterSwitch plus.
103=104,102,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180103,APC: An outlet configuration change on a MasterSwitch plus.
104=105,103,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180104,APC Redundant Switch: The Redundant Switch has switched source
105=106,104,0,LOG,MAP,NOBELL,PLUS,106,NONE,X3180105,APC Redundant Switch: The Redundant Switch has lost redundancy
106=107,105,2,LOG,MAP,NOBELL,MINUS,105,NONE,X3180106,APC Redundant Switch: Redundancy has been restored.
107=108,106,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180107,APC: A configuration change on a Redundant Switch.
108=109,107,2,LOG,MAP,NOBELL,MINUS,109,NONE,X3180108,APC: Communications established with the Redundant Switch.
109=110,108,0,LOG,MAP,NOBELL,PLUS,108,NONE,X3180109,APC: Communications lost with the Redundant Switch.
110=111,109,2,LOG,MAP,NOBELL,MINUS,111,NONE,X3180110,APC: Communications established with the DC power plant.
111=112,110,0,LOG,MAP,NOBELL,PLUS,110,NONE,X3180111,APC: Communications lost with the DC power plant.
112=113,111,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180112,APC: The active PIN on the DC controller has been changed.
113=114,112,0,LOG,MAP,NOBELL,PLUS,114,NONE,X3180113,APC: A Major alarm is active in the DC power plant.
114=115,113,2,LOG,MAP,NOBELL,MINUS,113,NONE,X3180114,APC: A Major alarm is no longer active in the DC power plant.
115=116,114,1,LOG,MAP,NOBELL,PLUS,116,NONE,X3180115,APC: A Minor alarm is active in the DC power plant.
116=117,115,2,LOG,MAP,NOBELL,MINUS,115,NONE,X3180116,APC: A Minor alarm is no longer active in the DC power plant.
117=118,116,1,LOG,MAP,NOBELL,PLUS,118,NONE,X3180117,APC: An output relay has gone on.
118=119,117,2,LOG,MAP,NOBELL,MINUS,117,NONE,X3180118,APC: An output relay has gone off.
119=120,118,1,LOG,MAP,NOBELL,PLUS,120,NONE,X3180119,APC: An input relay has gone on.
120=121,119,2,LOG,MAP,NOBELL,MINUS,119,NONE,X3180120,APC: An input relay has gone off.
121=122,120,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180121,APC UPS: The number of system power supplies has increased.
122=123,121,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180122,APC UPS: The number of system power supplies has decreased.
123=124,122,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180123,APC UPS: External Switch Gear $1 closed.
124=125,123,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180124,APC UPS: External Switch Gear $1 opened.
125=126,124,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180125,APC Device: $1
126=127,125,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180126,APC Automatic Transfer Switch: The ATS has switched source
127=128,126,0,LOG,MAP,NOBELL,PLUS,128,NONE,X3180127,APC Automatic Transfer Switch: The ATS has lost redundancy.
128=129,127,2,LOG,MAP,NOBELL,MINUS,127,NONE,X3180128,APC Automatic Transfer Switch: Redundancy has been restored.
129=130,128,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180129,APC Automatic Transfer Switch: ATS configuration changed.
130=131,129,2,LOG,MAP,NOBELL,MINUS,131,NONE,X3180130,APC Automatic Transfer Switch: Communications established.
131=132,130,0,LOG,MAP,NOBELL,PLUS,130,NONE,X3180131,APC Automatic Transfer Switch: Communications lost.
132=133,131,0,LOG,MAP,NOBELL,PLUS,133,NONE,X3180132,APC Automatic Transfer Switch: Output Current exceeded threshold
133=134,132,2,LOG,MAP,NOBELL,MINUS,132,NONE,X3180133,APC Automatic Transfer Switch: Output Current below threshold.
134=135,133,0,LOG,MAP,NOBELL,PLUS,135,1,X3180134,APC Automatic Transfer Switch: The ATS Power Supply has failed.
135=136,134,2,LOG,MAP,NOBELL,MINUS,134,1,X3180135,APC Automatic Transfer Switch: Power Supply Failure Cleared.
136=137,135,1,LOG,MAP,NOBELL,PLUS,137,NONE,X3180136,APC: A Mains Fail alarm is active in the DC power plant.
137=138,136,2,LOG,MAP,NOBELL,MINUS,136,NONE,X3180137,APC: Mains Fail alarm is no longer active in the DC power plant.
138=139,137,1,LOG,MAP,NOBELL,PLUS,139,NONE,X3180138,APC: A Fan Fail alarm is active in the DC power plant.
139=140,138,2,LOG,MAP,NOBELL,MINUS,138,NONE,X3180139,APC: A Fan Fail alarm is no longer active in the DC power plant.
140=141,139,1,LOG,MAP,NOBELL,PLUS,141,NONE,X3180140,APC: Rect. Overtemp alarm is active in the power plant.
141=142,140,2,LOG,MAP,NOBELL,MINUS,140,NONE,X3180141,APC: Rect. Overtmp alarm is no longer active in the power plant.
142=143,141,1,LOG,MAP,NOBELL,PLUS,143,NONE,X3180142,APC: A Current Limit alarm is active in the power plant.
143=144,142,2,LOG,MAP,NOBELL,MINUS,141,NONE,X3180143,APC: Current Limit alarm is no longer active in the power plant.
144=145,143,1,LOG,MAP,NOBELL,PLUS,145,NONE,X3180144,APC: A Rect. Fail alarm is active in the power plant.
145=146,144,2,LOG,MAP,NOBELL,MINUS,144,NONE,X3180145,APC: Rect. Fail alarm is no longer active in the power plant.
146=147,145,1,LOG,MAP,NOBELL,PLUS,147,NONE,X3180146,APC: Multiple Rect. Fail alarm is active in the powerplant.
147=148,146,2,LOG,MAP,NOBELL,MINUS,146,NONE,X3180147,APC: Multiple Rect Fail alarm is no longer active in powerplant.
148=149,147,1,LOG,MAP,NOBELL,PLUS,149,NONE,X3180148,APC: Batt. Breaker alarm is active in the power plant.
149=150,148,2,LOG,MAP,NOBELL,MINUS,148,NONE,X3180149,APC: Batt. Breaker alarm is no longer active in the power plant.
150=151,149,1,LOG,MAP,NOBELL,PLUS,151,NONE,X3180150,APC: A Rect. OVP alarm is active in the power plant.
151=152,150,2,LOG,MAP,NOBELL,MINUS,150,NONE,X3180151,APC: A Rect. OVP alarm is no longer active in the power plant.
152=153,151,1,LOG,MAP,NOBELL,PLUS,153,NONE,X3180152,APC: A LVD Imminent alarm is active in the powerplant.
153=154,152,2,LOG,MAP,NOBELL,MINUS,152,NONE,X3180153,APC: A LVD Imminent alarm is no longer active in the powerplant.
154=155,153,1,LOG,MAP,NOBELL,PLUS,155,NONE,X3180154,APC: A Fuse/CB alarm is active in the DC power plant.
155=156,154,2,LOG,MAP,NOBELL,MINUS,154,NONE,X3180155,APC: A Fuse/CB alarm is no longer active in the DC power plant.
156=157,155,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180156,APC: A Battery Test failed in the DC power plant.
157=158,156,1,LOG,MAP,NOBELL,PLUS,158,NONE,X3180157,APC: A Temperature alarm is active in the power plant.
158=159,157,2,LOG,MAP,NOBELL,MINUS,157,NONE,X3180158,APC: A Temperature alarm is no longer active in the power plant.
159=160,158,1,LOG,MAP,NOBELL,PLUS,160,NONE,X3180159,APC: A Humidity alarm is active in the DC power plant.
160=161,159,2,LOG,MAP,NOBELL,MINUS,159,NONE,X3180160,APC: A Humidity alarm is no longer active in the DC power plant.
161=162,160,2,LOG,MAP,NOBELL,MINUS,160,NONE,X3180161,APC: Power plant bridging board communications established.
162=163,161,0,LOG,MAP,NOBELL,PLUS,161,NONE,X3180162,APC: Power plant bridging board communications lost.
163=164,162,0,LOG,MAP,NOBELL,PLUS,164,NONE,X3180163,APC IEM: High temperature violation of $1 $2 on probe $3, $4.
164=165,163,2,LOG,MAP,NOBELL,MINUS,163,NONE,X3180164,APC IEM: High temperature violation on probe $1, $2, cleared.
165=166,164,0,LOG,MAP,NOBELL,PLUS,166,NONE,X3180165,APC IEM: Low temperature of $1 $2 on probe $3, $4.
166=167,165,2,LOG,MAP,NOBELL,MINUS,165,NONE,X3180166,APC IEM: Low temperature violation on probe $1, $2, cleared.
167=168,166,0,LOG,MAP,NOBELL,PLUS,168,NONE,X3180167,APC IEM: High humidity of $1 percent humidity on probe $2, $3.
168=169,167,2,LOG,MAP,NOBELL,MINUS,167,NONE,X3180168,APC IEM: High humidity violation on probe $1, $2, cleared.
169=170,168,0,LOG,MAP,NOBELL,PLUS,170,NONE,X3180169,APC IEM: Low humidity of $1 percent humidity on probe $2, $3.
170=171,169,2,LOG,MAP,NOBELL,MINUS,169,NONE,X3180170,APC IEM: Low humidity violation on probe $1, $2, cleared.
171=172,170,1,LOG,MAP,NOBELL,PLUS,172,NONE,X3180171,APC IEM: Probe disconnected.
172=173,171,2,LOG,MAP,NOBELL,MINUS,171,NONE,X3180172,APC IEM: Probe Connected.
173=174,172,0,LOG,MAP,NOBELL,PLUS,174,NONE,X3180173,APC IEM: Contact $1, $2, fault.
174=175,173,2,LOG,MAP,NOBELL,MINUS,173,NONE,X3180174,APC IEM: Fault cleared on contact $1, $2.
175=176,174,0,LOG,MAP,NOBELL,PLUS,176,NONE,X3180175,APC IEM: Output relay $1, $2, has faulted because $3.
176=177,175,2,LOG,MAP,NOBELL,MINUS,175,NONE,X3180176,APC IEM: Output relay, $1, $2, fault cleared.
177=178,176,2,LOG,MAP,NOBELL,PLUS,178,NONE,X3180177,BatMan : Unit $1 Communications Established.
178=179,177,0,LOG,MAP,NOBELL,MINUS,177,NONE,X3180178,BatMan : Unit $1 Communications Lost.
179=180,178,0,LOG,MAP,NOBELL,PLUS,180,NONE,X3180179,BatMan : Unit $1 Knee Alarm Detected.
180=181,179,2,LOG,MAP,NOBELL,MINUS,179,NONE,X3180180,BatMan : Unit $1 Knee Alarm Cleared.
181=182,180,1,LOG,MAP,NOBELL,PLUS,182,NONE,X3180181,BatMan : Unit $1 Charger Alarm Detected.
182=183,181,2,LOG,MAP,NOBELL,MINUS,181,NONE,X3180182,BatMan : Unit $1 Charger Alarm Cleared.
183=184,182,1,LOG,MAP,NOBELL,PLUS,184,NONE,X3180183,BatMan : Unit $1 Battery Alarm Detected.
184=185,183,2,LOG,MAP,NOBELL,MINUS,183,NONE,X3180184,BatMan : Unit $1 Battery Alarm Cleared.
185=186,184,1,LOG,MAP,NOBELL,PLUS,186,NONE,X3180185,BatMan : Unit $1 Environment Alarm Detected.
186=187,185,2,LOG,MAP,NOBELL,MINUS,185,NONE,X3180186,BatMan : Unit $1 Environment Alarm Cleared.
187=188,186,2,LOG,MAP,NOBELL,PLUS,188,NONE,X3180187,BatMan : Unit $1 Maintenance Due Alarm Detected.
188=189,187,2,LOG,MAP,NOBELL,MINUS,187,NONE,X3180188,BatMan : Unit $1 Maintenance Due Alarm Cleared.
189=190,188,2,LOG,MAP,NOBELL,MINUS,190,NONE,X3180189,APC PDU [$1, $2]: Communication Established.
190=191,189,0,LOG,MAP,NOBELL,PLUS,189,NONE,X3180190,APC PDU [$1, $2]: Communication Lost.
191=192,190,0,LOG,MAP,NOBELL,PLUS,192,NONE,X3180191,APC PDU [$1, $2]: Utility Line Undervoltage L$3.
192=193,191,2,LOG,MAP,NOBELL,MINUS,191,NONE,X3180192,APC PDU [$1, $2]: Utility Line Undervoltage Cleared L$3.
193=194,192,0,LOG,MAP,NOBELL,PLUS,194,NONE,X3180193,APC PDU [$1, $2]: Utility Line Overvoltage L$3.
194=195,193,2,LOG,MAP,NOBELL,MINUS,193,NONE,X3180194,APC PDU [$1, $2]: Utility Line Overvoltage Cleared L$3.
195=196,194,0,LOG,MAP,NOBELL,PLUS,196,NONE,X3180195,APC PDU [$1, $2]: Ground Overcurrent.
196=197,195,2,LOG,MAP,NOBELL,MINUS,195,NONE,X3180196,APC PDU [$1, $2]: Ground Overcurrent Cleared.
197=198,196,0,LOG,MAP,NOBELL,PLUS,198,NONE,X3180197,APC PDU [$1, $2]: Circuit Panel Input Undervoltage L$3.
198=199,197,2,LOG,MAP,NOBELL,MINUS,197,NONE,X3180198,APC PDU [$1, $2]: Circuit Panel Input Undervoltage Cleared L$3.
199=200,198,0,LOG,MAP,NOBELL,PLUS,200,NONE,X3180199,APC PDU [$1, $2]: Circuit Panel Input Overvoltage L$3.
200=201,199,2,LOG,MAP,NOBELL,MINUS,199,NONE,X3180200,APC PDU [$1, $2]: Circuit Panel Input Overvoltage Cleared L$3.
201=202,200,0,LOG,MAP,NOBELL,PLUS,202,NONE,X3180201,APC PDU [$1, $2]: Circuit Panel Input Undercurrent L$3.
202=203,201,2,LOG,MAP,NOBELL,MINUS,201,NONE,X3180202,APC PDU [$1, $2]: Circuit Panel Input Undercurrent Cleared L$3.
203=204,202,0,LOG,MAP,NOBELL,PLUS,204,NONE,X3180203,APC PDU [$1, $2]: Circuit Panel Input Overcurrent L$3.
204=205,203,2,LOG,MAP,NOBELL,MINUS,203,NONE,X3180204,APC PDU [$1, $2]: Circuit Panel Input Overcurrent Cleared L$3.
205=206,204,0,LOG,MAP,NOBELL,PLUS,206,NONE,X3180205,APC PDU [$1, $2]: Circuit Panel Input Frequency Out Of Range.
206=207,205,2,LOG,MAP,NOBELL,MINUS,205,NONE,X3180206,APC PDU [$1, $2]: Circuit Panel Input Frequency No Longer Out Of Range.
207=208,206,0,LOG,MAP,NOBELL,PLUS,208,NONE,X3180207,APC PDU [$1, $2]: Circuit Panel Input Neutral Overcurrent.
208=209,207,2,LOG,MAP,NOBELL,MINUS,207,NONE,X3180208,APC PDU [$1, $2]: Circuit Panel Input Neutral Overcurrent Cleared.
209=210,208,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180209,APC PDU [$1, $2]: System Off.
210=211,209,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180210,APC PDU [$1, $2]: On Battery Mode.
211=212,210,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180211,APC PDU [$1, $2]: Maintenance Bypass Mode.
212=213,211,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180212,APC PDU [$1, $2]: Atypical Bypass Mode.
213=214,212,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180213,APC PDU [$1, $2]: No Panel Feed Mode.
214=215,213,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180214,APC PDU [$1, $2]: Ups Operation Mode.
215=216,214,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180215,APC PDU [$1, $2]: Forced Bypass Mode.
216=217,215,0,LOG,MAP,NOBELL,PLUS,217,NONE,X3180216,APC PDU [$1, $2]: Input Transformer Over Temperature.
217=218,216,2,LOG,MAP,NOBELL,MINUS,216,NONE,X3180217,APC PDU [$1, $2]: Input Transformer Over Temperature Cleared.
218=219,217,0,LOG,MAP,NOBELL,PLUS,219,NONE,X3180218,APC PDU [$1, $2]: UPS Input Voltage L$3-N Lost.
219=220,218,2,LOG,MAP,NOBELL,MINUS,218,NONE,X3180219,APC PDU [$1, $2]: UPS Input Voltage L$3-N Restored.
220=221,219,0,LOG,MAP,NOBELL,PLUS,221,NONE,X3180220,APC PDU [$1, $2]: Contact $3 Abnormal.
221=222,220,2,LOG,MAP,NOBELL,MINUS,220,NONE,X3180221,APC PDU [$1, $2]: Contact $3 Normal.
222=223,221,1,LOG,MAP,NOBELL,PLUS,223,3,X3180222,APC Rack PDU: Violation of bank or phase low load threshold.
223=224,222,2,LOG,MAP,NOBELL,MINUS,222,3,X3180223,APC Rack PDU: Bank or phase low load condition cleared.
224=225,223,1,LOG,MAP,NOBELL,PLUS,225,3,X3180224,APC Rack PDU: Bank or phase near an overload condition.
225=226,224,2,LOG,MAP,NOBELL,MINUS,224,3,X3180225,APC Rack PDU: Bank or phase near overload condition has cleared.
226=227,225,0,LOG,MAP,NOBELL,PLUS,227,3,X3180226,APC Rack PDU: Bank or phase overload condition.
227=228,226,2,LOG,MAP,NOBELL,MINUS,226,3,X3180227,APC Rack PDU: Bank or phase overload condition has cleared.
228=229,227,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180228,APC ARU [$4]: ARU Device configuration change.
229=230,228,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180229,APC RM PDU [$1, $2]: Communication Lost.
230=231,229,2,LOG,MAP,NOBELL,MINUS,231,NONE,X3180230,APC EMS [$2]: Communications Established.
231=232,230,0,LOG,MAP,NOBELL,PLUS,230,NONE,X3180231,APC EMS [$2]: Communications Lost.
232=233,231,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180232,APC EMS [$2]: Probe $3 Connected.
233=234,232,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180233,APC EMS [$2]: Probe $3 Disconnected.
234=235,233,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180234,APC EMS [$2]: Sensor $3 Connected.
235=236,234,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180235,APC EMS [$2]: Sensor $3 Disconnected.
236=237,235,0,LOG,MAP,NOBELL,PLUS,237,3,X3180236,APC EMS [$2]: Sensor $3 Fault.
237=238,236,2,LOG,MAP,NOBELL,MINUS,236,3,X3180237,APC EMS [$2]: Sensor $3 Fault Cleared.
238=239,237,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180238,APC EMS [$2]: Beacon Connected.
239=240,238,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180239,APC EMS [$2]: Beacon Disconnected.
240=241,239,2,LOG,MAP,NOBELL,PLUS,241,NONE,X3180240,APC EMS [$2]: Beacon On.
241=242,240,2,LOG,MAP,NOBELL,MINUS,240,NONE,X3180241,APC EMS [$2]: Beacon Off.
242=243,241,0,LOG,MAP,NOBELL,PLUS,243,NONE,X3180242,APC EMS [$2]: Major Alarm.
243=244,242,2,LOG,MAP,NOBELL,MINUS,242,NONE,X3180243,APC EMS [$2]: Major Alarm Cleared.
244=245,243,0,LOG,MAP,NOBELL,PLUS,245,NONE,X3180244,APC EMS [$2]: Minor Alarm.
245=246,244,2,LOG,MAP,NOBELL,MINUS,244,NONE,X3180245,APC EMS [$2]: Minor Alarm Cleared.
246=247,245,1,LOG,MAP,NOBELL,PLUS,247,3,X3180246,APC EMS [$2]: Outlet $3 to abnormal state $5.
247=248,246,2,LOG,MAP,NOBELL,MINUS,246,3,X3180247,APC EMS [$2]: Outlet $3 to normal state $5.
248=249,247,1,LOG,MAP,NOBELL,PLUS,249,3,X3180248,APC EMS [$2]: Contact $3 to abnormal state $5.
249=250,248,2,LOG,MAP,NOBELL,MINUS,248,3,X3180249,APC EMS [$2]: Contact $3 to normal state $5.
250=251,249,1,LOG,MAP,NOBELL,PLUS,251,3,X3180250,APC EMS [$2]: Relay $3 to abnormal state $5.
251=252,250,2,LOG,MAP,NOBELL,MINUS,250,3,X3180251,APC EMS [$2]: Relay $3 to normal state $5.
252=253,251,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180252,APC EMS [$2]: Device configuration change.
253=254,252,0,LOG,MAP,NOBELL,PLUS,254,5,X3180253,APC ENV [$2]: Overtemp ($3,$4) on Probe $5).
254=255,253,2,LOG,MAP,NOBELL,MINUS,253,5,X3180254,APC ENV [$2]: Overtemp ($3,$4) on Probe $5 cleared.
255=256,254,0,LOG,MAP,NOBELL,PLUS,256,5,X3180255,APC ENV [$2]: Undertemp ($3,$4) on Probe $5.
256=257,255,2,LOG,MAP,NOBELL,MINUS,255,5,X3180256,APC ENV [$2]: Undertemp ($3,$4) on Probe $5 cleared.
257=258,256,0,LOG,MAP,NOBELL,PLUS,258,4,X3180257,APC ENV [$2]: Over Humidity ($3) on Probe $4.
258=259,257,2,LOG,MAP,NOBELL,MINUS,257,4,X3180258,APC ENV [$2]: Over Humidity ($3) on Probe $4 cleared.
259=260,258,0,LOG,MAP,NOBELL,PLUS,260,4,X3180259,APC ENV [$2]: Under Humidity ($3) on Probe $4.
260=261,259,2,LOG,MAP,NOBELL,MINUS,259,4,X3180260,APC ENV [$2]: Under Humidity ($3) on Probe $4 cleared.
261=266,260,2,LOG,MAP,NOBELL,MINUS,NONE,NONE,X3180261,APC NL [$2]: Communication Established.
266=267,261,2,LOG,MAP,NOBELL,MINUS,267,NONE,X3180266,APC Rack PDU: Communication established.
267=268,266,0,LOG,MAP,NOBELL,PLUS,266,NONE,X3180267,APC Rack PDU: Communication lost.
268=269,267,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180268,APC Switched Rack PDU: An outlet has turned on.
269=270,268,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180269,APC Switched Rack PDU: An outlet has turned off.
270=271,269,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180270,APC Rack PDU: Device configuration change made.
271=272,270,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180271,APC Switched Rack PDU: Outlet configuration change made.
272=273,271,1,LOG,MAP,NOBELL,PLUS,273,3,X3180272,APC Rack PDU: Violation of low load threshold.
273=274,272,2,LOG,MAP,NOBELL,MINUS,272,3,X3180273,APC Rack PDU: Low load condition cleared.
274=275,273,1,LOG,MAP,NOBELL,PLUS,275,3,X3180274,APC Rack PDU: Near an overload condition.
275=276,274,2,LOG,MAP,NOBELL,MINUS,274,3,X3180275,APC Rack PDU: Near overload condition has cleared.
276=277,275,0,LOG,MAP,NOBELL,PLUS,277,3,X3180276,APC Rack PDU: Overload condition.
277=278,276,2,LOG,MAP,NOBELL,MINUS,276,3,X3180277,APC Rack PDU: Overload condition has cleared.
278=279,277,0,LOG,MAP,NOBELL,PLUS,279,NONE,X3180278,APC Rack PDU: Power Supply 1 is in FAIL state.
279=280,278,2,LOG,MAP,NOBELL,MINUS,278,NONE,X3180279,APC Rack PDU: Power Supply 1 is operating normally.
280=281,279,0,LOG,MAP,NOBELL,PLUS,281,NONE,X3180280,APC Rack PDU: Power Supply 2 is in FAIL state.
281=282,280,2,LOG,MAP,NOBELL,MINUS,280,NONE,X3180281,APC Rack PDU: Power Supply 2 is operating normally.
282=283,281,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180282,APC Rack PDU: Phase configuration change made.
283=284,282,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180283,APC Switched Rack PDU: Cancel Pending Command made.
284=285,283,2,LOG,MAP,NOBELL,MINUS,285,1,X3180284,APC ARU [$4]: Communication Established.
285=286,284,0,LOG,MAP,NOBELL,PLUS,284,1,X3180285,APC ARU [$4]: Communication Lost.
286=287,285,0,LOG,MAP,NOBELL,PLUS,287,3,X3180286,APC ARU [$4]: Fan Fail.
287=288,286,2,LOG,MAP,NOBELL,MINUS,286,3,X3180287,APC ARU [$4]: Fan Fail Cleared.
288=289,287,0,LOG,MAP,NOBELL,PLUS,289,3,X3180288,APC ARU [$4]: Smoke Alarm.
289=290,288,2,LOG,MAP,NOBELL,MINUS,288,3,X3180289,APC ARU [$4]: Smoke Alarm Cleared.
290=291,289,1,LOG,MAP,NOBELL,PLUS,291,3,X3180290,APC ARU [$4]: High Temperature Alarm.
291=292,290,2,LOG,MAP,NOBELL,MINUS,290,3,X3180291,APC ARU [$4]: High Temperature Alarm Cleared.
292=293,291,0,LOG,MAP,NOBELL,PLUS,293,3,X3180292,APC ARU [$4]: Exhaust Temperature Alarm.
293=294,292,2,LOG,MAP,NOBELL,MINUS,292,3,X3180293,APC ARU [$4]: Exhaust Temperature Alarm Cleared.
294=295,293,2,LOG,MAP,NOBELL,MINUS,295,1,X3180294,APC ENV [$4]: Communication Established.
295=296,294,0,LOG,MAP,NOBELL,PLUS,294,1,X3180295,APC ENV [$4]: Communication Lost.
296=297,295,0,LOG,MAP,NOBELL,PLUS,297,1,X3180296,APC EMS [$2]: Alink Power Overload.
297=298,296,2,LOG,MAP,NOBELL,MINUS,296,1,X3180297,APC EMS [$2]: Alink Power Overload Cleared.
298=299,297,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180298,APC UPS: Outlet Group $1 turned on.
299=300,298,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180299,APC UPS: Outlet Group $1 turned off.
300=301,299,0,LOG,MAP,NOBELL,PLUS,301,1,X3180300,APC Symmetra MW UPS: A critical condition has been detected.
301=302,300,2,LOG,MAP,NOBELL,MINUS,300,1,X3180301,APC Symmetra MW UPS: A critical condition has been cleared.
302=303,301,1,LOG,MAP,NOBELL,PLUS,303,1,X3180302,APC Symmetra MW UPS: A warning condition has been detected.
303=304,302,2,LOG,MAP,NOBELL,MINUS,302,1,X3180303,APC Symmetra MW UPS: A warning condition has been cleared.
304=305,303,2,LOG,MAP,NOBELL,PLUS,305,1,X3180304,APC Symmetra MW UPS: Informational condition detected.
305=306,304,2,LOG,MAP,NOBELL,MINUS,304,1,X3180305,APC Symmetra MW UPS: Informational condition cleared.
306=307,305,0,LOG,MAP,NOBELL,PLUS,307,2,X3180306,APC Air: $1
307=308,306,2,LOG,MAP,NOBELL,MINUS,306,2,X3180307,APC Air: $1
308=309,307,1,LOG,MAP,NOBELL,PLUS,309,2,X3180308,APC Air: $1
309=310,308,2,LOG,MAP,NOBELL,MINUS,308,2,X3180309,APC Air: $1
310=311,309,2,LOG,MAP,NOBELL,PLUS,311,2,X3180310,APC Air: $1
311=312,310,2,LOG,MAP,NOBELL,MINUS,310,2,X3180311,APC Air: $1
312=313,311,0,LOG,MAP,NOBELL,PLUS,313,3,X3180312,APC XPDU [$2]: Input voltage $4 below threshold $5.
313=314,312,2,LOG,MAP,NOBELL,MINUS,312,3,X3180313,APC XPDU [$2]: Main input low voltage $4 alarm cleared.
314=315,313,0,LOG,MAP,NOBELL,PLUS,315,3,X3180314,APC XPDU [$2]: Main input voltage $4 above threshold $5.
315=316,314,2,LOG,MAP,NOBELL,MINUS,314,3,X3180315,APC XPDU [$2]: Main input high voltage $4 alarm cleared.
316=317,315,0,LOG,MAP,NOBELL,PLUS,317,3,X3180316,APC XPDU [$2]: Bypass voltage $4 below threshold $5.
317=318,316,2,LOG,MAP,NOBELL,MINUS,316,3,X3180317,APC XPDU [$2]: Bypass low voltage $4 alarm cleared.
318=319,317,0,LOG,MAP,NOBELL,PLUS,319,3,X3180318,APC XPDU [$2]: Bypass voltage $4 above threshold $5.
319=320,318,2,LOG,MAP,NOBELL,MINUS,318,3,X3180319,APC XPDU [$2]: Bypass high voltage $4 alarm cleared.
320=321,319,0,LOG,MAP,NOBELL,PLUS,321,3,X3180320,APC XPDU [$2]: Output voltage $4 below threshold $5.
321=322,320,2,LOG,MAP,NOBELL,MINUS,320,3,X3180321,APC XPDU [$2]: Output low voltage $4 alarm cleared.
322=323,321,0,LOG,MAP,NOBELL,PLUS,323,3,X3180322,APC XPDU [$2]: Output voltage $4 above threshold $5.
323=324,322,2,LOG,MAP,NOBELL,MINUS,322,3,X3180323,APC XPDU [$2]: Output high voltage $4 alarm cleared.
324=325,323,0,LOG,MAP,NOBELL,PLUS,325,3,X3180324,APC XPDU [$2]: Output current $4 below threshold $5.
325=326,324,2,LOG,MAP,NOBELL,MINUS,324,3,X3180325,APC XPDU [$2]: Output low current $4 alarm cleared.
326=327,325,0,LOG,MAP,NOBELL,PLUS,327,3,X3180326,APC XPDU [$2]: Output current $4 above threshold $5.
327=328,326,2,LOG,MAP,NOBELL,MINUS,326,3,X3180327,APC XPDU [$2]: Output high current $4 alarm cleared.
328=329,327,0,LOG,MAP,NOBELL,PLUS,329,1,X3180328,APC XPDU [$2]: Output frequency out-of-range.
329=330,328,2,LOG,MAP,NOBELL,MINUS,328,1,X3180329,APC XPDU [$2]: Output frequency in range.
330=331,329,0,LOG,MAP,NOBELL,PLUS,331,3,X3180330,APC XPDU [$2]: Earth ground current $3 above threshold $4.
331=332,330,2,LOG,MAP,NOBELL,MINUS,330,3,X3180331,APC XPDU [$2]: Earth ground high current $3 alarm cleared.
332=333,331,0,LOG,MAP,NOBELL,PLUS,333,3,X3180332,APC XPDU [$2]: Contact $3 to abnormal state $5.
333=334,332,2,LOG,MAP,NOBELL,MINUS,332,3,X3180333,APC XPDU [$2]: Contact $3 to normal state $5.
334=335,333,1,LOG,MAP,NOBELL,PLUS,335,NONE,X3180334,APC XPDU [$2]: Output neutral current $3 above threshold $4.
335=336,334,2,LOG,MAP,NOBELL,MINUS,334,NONE,X3180335,APC XPDU [$2]: Output neutral high current $3 alarm cleared.
336=337,335,0,LOG,MAP,NOBELL,PLUS,337,1,X3180336,APC XPDU [$2]: Cooling fan failure.
337=338,336,2,LOG,MAP,NOBELL,MINUS,336,1,X3180337,APC XPDU [$2]: Cooling fan alarm cleared.
338=339,337,0,LOG,MAP,NOBELL,PLUS,339,1,X3180338,APC XPDU [$2]: Transformer over temp alarm.
339=340,338,2,LOG,MAP,NOBELL,MINUS,338,1,X3180339,APC XPDU [$2]: Isolation transformer temperature alarm cleared.
340=341,339,1,LOG,MAP,NOBELL,PLUS,341,3,X3180340,APC XPDU [$2]: Branch circuit current $4 below threshold $5.
341=342,340,2,LOG,MAP,NOBELL,MINUS,340,3,X3180341,APC XPDU [$2]: Branch circuit low current $3 alarm cleared.
342=343,341,1,LOG,MAP,NOBELL,PLUS,343,3,X3180342,APC XPDU [$2]: Branch circuit current $4 above threshold $5.
343=344,342,2,LOG,MAP,NOBELL,MINUS,342,3,X3180343,APC XPDU [$2]: Branch circuit current $4 alarm cleared.
344=345,343,0,LOG,MAP,NOBELL,PLUS,479,1,X3180344,APC XPDU [$2]: Communication error.
345=346,344,0,LOG,MAP,NOBELL,PLUS,346,3,X3180345,APC EMS [$2]: Hardware is in an abnormal state.
346=347,345,2,LOG,MAP,NOBELL,MINUS,345,3,X3180346,APC EMS [$2]: Hardware is in its normal state.
347=348,346,0,LOG,MAP,NOBELL,PLUS,348,2,X3180347,APC Custom Event #$2: $1
348=349,347,2,LOG,MAP,NOBELL,MINUS,347,2,X3180348,APC Custom Event #$2: $1
349=350,348,1,LOG,MAP,NOBELL,PLUS,350,2,X3180349,APC Custom Event #$2: $1
350=351,349,2,LOG,MAP,NOBELL,MINUS,349,2,X3180350,APC Custom Event #$2: $1
351=352,350,2,LOG,MAP,NOBELL,PLUS,352,2,X3180351,APC Custom Event #$2: $1
352=353,351,2,LOG,MAP,NOBELL,MINUS,351,2,X3180352,APC Custom Event #$2: $1
353=354,352,1,LOG,MAP,NOBELL,MINUS,354,NONE,X3180353,APC UPS: The internal over temperature condition exists.
354=355,353,2,LOG,MAP,NOBELL,PLUS,353,NONE,X3180354,APC UPS: The internal over temperature condition cleared.
355=356,354,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180355,APC UPS: The MPU has been reset.
356=357,355,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180356,APC UPS: The Output Switch is closed.
357=358,356,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180357,APC UPS: The Output Switch is open.
358=359,357,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180358,APC UPS: A calibration value in the stack was changed.
359=360,358,0,LOG,MAP,NOBELL,PLUS,360,5,X3180359,APC ENV [$2]: Over max temp ($3,$4) on Probe $5).
360=361,359,2,LOG,MAP,NOBELL,MINUS,359,5,X3180360,APC ENV [$2]: Over max temp ($3,$4) on Probe $5 cleared.
361=362,360,0,LOG,MAP,NOBELL,PLUS,362,5,X3180361,APC ENV [$2]: Under min temp ($3,$4) on Probe $5.
362=363,361,2,LOG,MAP,NOBELL,MINUS,361,5,X3180362,APC ENV [$2]: Under min temp ($3,$4) on Probe $5 cleared.
363=364,362,0,LOG,MAP,NOBELL,PLUS,364,4,X3180363,APC ENV [$2]: Over max Humidity ($3) on Probe $4.
364=365,363,2,LOG,MAP,NOBELL,MINUS,363,4,X3180364,APC ENV [$2]: Over max Humidity ($3) on Probe $4 cleared.
365=366,364,0,LOG,MAP,NOBELL,PLUS,366,4,X3180365,APC ENV [$2]: Under min Humidity ($3) on Probe $4.
366=367,365,2,LOG,MAP,NOBELL,MINUS,365,4,X3180366,APC ENV [$2]: Under min Humidity ($3) on Probe $4 cleared.
367=368,366,0,LOG,MAP,NOBELL,PLUS,368,5,X3180367,APC ENV [$2]: ST inc. temp rate ($3,$4) on Probe $5.
368=369,367,2,LOG,MAP,NOBELL,MINUS,367,5,X3180368,APC ENV [$2]: ST inc. temp rate ($3,$4) on Probe $5 cleared.
369=370,368,0,LOG,MAP,NOBELL,PLUS,370,5,X3180369,APC ENV [$2]: ST dec. temp rate ($3,$4) on Probe $5.
370=371,369,2,LOG,MAP,NOBELL,MINUS,369,5,X3180370,APC ENV [$2]: ST dec. temp rate ($3,$4) on Probe $5 cleared.
371=372,370,0,LOG,MAP,NOBELL,PLUS,372,5,X3180371,APC ENV [$2]: LT inc. temp rate ($3,$4) on Probe $5.
372=373,371,2,LOG,MAP,NOBELL,MINUS,371,5,X3180372,APC ENV [$2]: LT inc. temp rate ($3,$4) on Probe $5 cleared.
373=374,372,0,LOG,MAP,NOBELL,PLUS,374,5,X3180373,APC ENV [$2]: LT dec. temp rate ($3,$4) on Probe $5.
374=375,373,2,LOG,MAP,NOBELL,MINUS,373,5,X3180374,APC ENV [$2]: LT dec. temp rate ($3,$4) on Probe $5 cleared.
375=376,374,0,LOG,MAP,NOBELL,PLUS,376,2,X3180375,APC BMS: $1
376=377,375,2,LOG,MAP,NOBELL,MINUS,375,2,X3180376,APC BMS: $1
377=378,376,1,LOG,MAP,NOBELL,PLUS,378,2,X3180377,APC BMS: $1
378=379,377,2,LOG,MAP,NOBELL,MINUS,377,2,X3180378,APC BMS: $1
379=380,378,2,LOG,MAP,NOBELL,PLUS,380,2,X3180379,APC BMS: $1
380=381,379,2,LOG,MAP,NOBELL,MINUS,379,2,X3180380,APC BMS: $1
381=382,380,0,LOG,MAP,NOBELL,PLUS,382,3,X3180381,APC XATS [$2]: output voltage $4 below threshold $5.
382=383,381,2,LOG,MAP,NOBELL,MINUS,381,3,X3180382,APC XATS [$2]: output low voltage $4 alarm cleared.
383=384,382,0,LOG,MAP,NOBELL,PLUS,384,3,X3180383,APC XATS [$2]: output voltage $4 above threshold $5.
384=385,383,2,LOG,MAP,NOBELL,MINUS,383,3,X3180384,APC XATS [$2]: output high voltage $4 alarm cleared.
385=386,384,0,LOG,MAP,NOBELL,PLUS,386,3,X3180385,APC XATS [$2]: output current $4 below threshold $5.
386=387,385,2,LOG,MAP,NOBELL,MINUS,385,3,X3180386,APC XATS [$2]: output low current $4 alarm cleared.
387=388,386,0,LOG,MAP,NOBELL,PLUS,388,3,X3180387,APC XATS [$2]: Output current $4 above threshold $5.
388=389,387,2,LOG,MAP,NOBELL,MINUS,387,3,X3180388,APC XATS [$2]: output high current $4 alarm cleared.
389=390,388,0,LOG,MAP,NOBELL,PLUS,390,NONE,X3180389,APC XATS [$2]: output frequency $3 outside the threshold range $4.
390=391,389,2,LOG,MAP,NOBELL,MINUS,389,NONE,X3180390,APC XATS [$2]: output frequency in range.
391=392,390,0,LOG,MAP,NOBELL,PLUS,392,1,X3180391,APC XATS [$2]: Communication error.
392=393,391,2,LOG,MAP,NOBELL,MINUS,391,1,X3180392,APC XATS [$2]: Communication error cleared.
393=394,392,0,LOG,MAP,NOBELL,PLUS,394,1,X3180393,APC XATS [$2]: Data mismatch error.
394=395,393,2,LOG,MAP,NOBELL,MINUS,393,1,X3180394,APC XATS [$2]: Data mismatch error cleared.
395=396,394,1,LOG,MAP,NOBELL,PLUS,396,1,X3180395,APC XATS [$2]: No communication with generator.
396=397,395,2,LOG,MAP,NOBELL,MINUS,395,1,X3180396,APC XATS [$2]: Communication with generator established.
397=398,396,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180397,APC XATS [$2]: transferred to the neutral position while in $3 mode.
398=399,397,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180398,APC XATS [$2]: $5 transfer to source $4 while in $3 mode.
399=400,398,0,LOG,MAP,NOBELL,PLUS,400,3,X3180399,APC XATS [$2]: Internal fault detected $3.
400=401,399,2,LOG,MAP,NOBELL,MINUS,399,3,X3180400,APC XATS [$2]: Internal fault cleared $3.
401=402,400,2,LOG,MAP,NOBELL,PLUS,402,NONE,X3180401,APC XATS [$2]: Engine Start signal asserted.
402=403,401,2,LOG,MAP,NOBELL,MINUS,401,NONE,X3180402,APC XATS [$2]: Engine Stop signal asserted.
403=404,402,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180403,APC XATS [$2]: Generator failed to start.
404=405,403,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180404,APC XATS [$2]: Generator failed to stop.
405=406,404,0,LOG,MAP,NOBELL,PLUS,406,NONE,X3180405,APC XATS [$2]: XATS is not-in-automatic mode.
406=407,405,2,LOG,MAP,NOBELL,MINUS,405,NONE,X3180406,APC XATS [$2]: XATS in auto mode.
407=408,406,0,LOG,MAP,NOBELL,PLUS,408,NONE,X3180407,APC XATS [$2]: Emergency Power Off (EPO) tripped.
408=409,407,2,LOG,MAP,NOBELL,MINUS,407,NONE,X3180408,APC XATS [$2]: Emergency Power Off (EPO) reset.
409=410,408,1,LOG,MAP,NOBELL,PLUS,410,NONE,X3180409,APC XATS [$2]: Emergency Power Off (EPO) in test mode.
410=411,409,2,LOG,MAP,NOBELL,MINUS,409,NONE,X3180410,APC XATS [$2]: Emergency Power Off (EPO) enabled.
411=412,410,2,LOG,MAP,NOBELL,PLUS,412,3,X3180411,APC XATS [$2]: $3 test initiated.
412=413,411,2,LOG,MAP,NOBELL,MINUS,411,3,X3180412,APC XATS [$2]: $3 test canceled.
413=414,412,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180413,APC XATS [$2]: Initiated test failed.
414=415,413,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180414,APC XATS [$2]: Initiated test passed.
415=416,414,0,LOG,MAP,NOBELL,PLUS,416,3,X3180415,APC XATS [$2]: Contact $3 changed to abnormal state $5.
416=417,415,2,LOG,MAP,NOBELL,MINUS,415,3,X3180416,APC XATS [$2]: Contact $3 changed to normal state $5.
417=418,416,0,LOG,MAP,NOBELL,PLUS,418,1,X3180417,APC XATS [$2]: Generator/ATS start contact mismatch.
418=419,417,2,LOG,MAP,NOBELL,MINUS,417,1,X3180418,APC XATS [$2]: Generator/ATS start contact mismatch cleared.
419=420,418,1,LOG,MAP,NOBELL,PLUS,420,1,X3180419,APC XATS [$2]: Panel door is open alarm.
420=421,419,2,LOG,MAP,NOBELL,MINUS,419,1,X3180420,APC XATS [$2]: Panel door open alarm cleared.
421=422,420,1,LOG,MAP,NOBELL,PLUS,422,1,X3180421,APC XATS [$2]: DC backup failure.
422=423,421,2,LOG,MAP,NOBELL,MINUS,421,1,X3180422,APC XATS [$2]: DC backup alarm cleared.
423=424,422,0,LOG,MAP,NOBELL,PLUS,424,NONE,X3180423,APC XGEN [$2]: Generator low coolant level alarm.
424=425,423,2,LOG,MAP,NOBELL,MINUS,423,NONE,X3180424,APC XGEN [$2]: Generator low coolant level alarm cleared.
425=426,424,0,LOG,MAP,NOBELL,PLUS,426,NONE,X3180425,APC XGEN [$2]: Generator very low coolant level alarm.
426=427,425,2,LOG,MAP,NOBELL,MINUS,425,NONE,X3180426,APC XGEN [$2]: Generator very low coolant level alarm cleared.
427=428,426,0,LOG,MAP,NOBELL,PLUS,428,NONE,X3180427,APC XGEN [$2]: Generator high coolant temperature alarm.
428=429,427,2,LOG,MAP,NOBELL,MINUS,427,NONE,X3180428,APC XGEN [$2]: Generator high coolant temperature alarm cleared.
429=430,428,0,LOG,MAP,NOBELL,PLUS,430,NONE,X3180429,APC XGEN [$2]: Generator very high coolant temperature alarm.
430=431,429,2,LOG,MAP,NOBELL,MINUS,429,NONE,X3180430,APC XGEN [$2]: Generator very high coolant temperature alarm cleared.
431=432,430,1,LOG,MAP,NOBELL,PLUS,432,NONE,X3180431,APC XGEN [$2]: Generator low coolant temperature alarm.
432=433,431,2,LOG,MAP,NOBELL,MINUS,431,NONE,X3180432,APC XGEN [$2]: Generator low coolant temperature alarm cleared.
433=434,432,0,LOG,MAP,NOBELL,PLUS,434,NONE,X3180433,APC XGEN [$2]: Generator low oil level alarm.
434=435,433,2,LOG,MAP,NOBELL,MINUS,433,NONE,X3180434,APC XGEN [$2]: Generator low oil level alarm cleared.
435=436,434,0,LOG,MAP,NOBELL,PLUS,436,NONE,X3180435,APC XGEN [$2]: Low battery voltage while cranking alarm.
436=437,435,2,LOG,MAP,NOBELL,MINUS,435,NONE,X3180436,APC XGEN [$2]: Low battery voltage while cranking alarm cleared.
437=438,436,0,LOG,MAP,NOBELL,PLUS,438,NONE,X3180437,APC XGEN [$2]: Generator v.low battery voltage while cranking alarm.
438=439,437,2,LOG,MAP,NOBELL,MINUS,437,NONE,X3180438,APC XGEN [$2]: Generator v.low battery voltage while cranking alarm cleared.
439=440,438,0,LOG,MAP,NOBELL,PLUS,440,4,X3180439,APC XGEN [$2]: Generator emergency stop engaged.
440=441,439,2,LOG,MAP,NOBELL,MINUS,439,4,X3180440,APC XGEN [$2]: Generator emergency stop condition cleared.
441=442,440,1,LOG,MAP,NOBELL,PLUS,442,NONE,X3180441,APC XGEN [$2]: Generator high battery voltage.
442=443,441,2,LOG,MAP,NOBELL,MINUS,441,NONE,X3180442,APC XGEN [$2]: Generator high battery voltage condition cleared.
443=444,442,0,LOG,MAP,NOBELL,PLUS,444,NONE,X3180443,APC XGEN [$2]: Generator low battery voltage.
444=445,443,2,LOG,MAP,NOBELL,MINUS,443,NONE,X3180444,APC XGEN [$2]: Generator low battery voltage condition cleared.
445=446,444,0,LOG,MAP,NOBELL,PLUS,446,NONE,X3180445,APC XGEN [$2]: Generator not-in-automatic mode.
446=447,445,2,LOG,MAP,NOBELL,MINUS,445,NONE,X3180446,APC XGEN [$2]: Generator automatic mode restored.
447=448,446,0,LOG,MAP,NOBELL,PLUS,448,NONE,X3180447,APC XGEN [$2]: Generator low oil pressure.
448=449,447,2,LOG,MAP,NOBELL,MINUS,447,NONE,X3180448,APC XGEN [$2]: Generator low oil pressure condition cleared.
449=450,448,0,LOG,MAP,NOBELL,PLUS,450,NONE,X3180449,APC XGEN [$2]: Generator v.low oil pressure.
450=451,449,2,LOG,MAP,NOBELL,MINUS,449,NONE,X3180450,APC XGEN [$2]: Generator v.low oil pressure condition cleared.
451=452,450,0,LOG,MAP,NOBELL,PLUS,452,NONE,X3180451,APC XGEN [$2]: Generator is in overload event.
452=453,451,2,LOG,MAP,NOBELL,MINUS,451,NONE,X3180452,APC XGEN [$2]: Generator is in overload event cleared.
453=454,452,0,LOG,MAP,NOBELL,PLUS,454,NONE,X3180453,APC XGEN [$2]: State of the Generator AC voltage.
454=455,453,2,LOG,MAP,NOBELL,MINUS,453,NONE,X3180454,APC XGEN [$2]: State of the Generator AC voltage cleared.
455=456,454,0,LOG,MAP,NOBELL,PLUS,456,NONE,X3180455,APC XGEN [$2]: State of the Generator AC voltage.
456=457,455,2,LOG,MAP,NOBELL,MINUS,455,NONE,X3180456,APC XGEN [$2]: State of the Generator AC voltage cleared.
457=458,456,0,LOG,MAP,NOBELL,PLUS,458,NONE,X3180457,APC XGEN [$2]: Generator overspeed condition.
458=459,457,2,LOG,MAP,NOBELL,MINUS,457,NONE,X3180458,APC XGEN [$2]: Generator overspeed condition cleared.
459=460,458,0,LOG,MAP,NOBELL,PLUS,460,NONE,X3180459,APC XGEN [$2]: Generator engine is cold, may not start.
460=461,459,2,LOG,MAP,NOBELL,MINUS,459,NONE,X3180460,APC XGEN [$2]: Engine is cold to start condition cleared.
461=462,460,0,LOG,MAP,NOBELL,PLUS,462,NONE,X3180461,APC XGEN [$2]: Generator output breaker open alarm.
462=463,461,2,LOG,MAP,NOBELL,MINUS,461,NONE,X3180462,APC XGEN [$2]: Generator output breaker open alarm cleared.
463=464,462,1,LOG,MAP,NOBELL,PLUS,464,NONE,X3180463,APC XGEN [$2]: Low fuel level alarm.
464=465,463,2,LOG,MAP,NOBELL,MINUS,463,NONE,X3180464,APC XGEN [$2]: Low fuel level alarm cleared.
465=466,464,0,LOG,MAP,NOBELL,PLUS,466,NONE,X3180465,APC XGEN [$2]: Very Low fuel level alarm.
466=467,465,2,LOG,MAP,NOBELL,MINUS,465,NONE,X3180466,APC XGEN [$2]: Very Low fuel level alarm cleared.
467=468,466,1,LOG,MAP,NOBELL,PLUS,468,NONE,X3180467,APC XGEN [$2]: Low run time alarm.
468=469,467,2,LOG,MAP,NOBELL,MINUS,467,NONE,X3180468,APC XGEN [$2]: Low run time alarm cleared.
469=470,468,0,LOG,MAP,NOBELL,PLUS,470,NONE,X3180469,APC XGEN [$2]: Very low run time alarm.
470=471,469,2,LOG,MAP,NOBELL,MINUS,469,NONE,X3180470,APC XGEN [$2]: Very low run time alarm cleared.
471=472,470,1,LOG,MAP,NOBELL,PLUS,472,NONE,X3180471,APC XATS [$2]: Generator scheduled maintenance is due.
472=473,471,2,LOG,MAP,NOBELL,MINUS,471,NONE,X3180472,APC XATS [$2]: Generator service due alarm is cleared.
473=474,472,0,LOG,MAP,NOBELL,PLUS,474,NONE,X3180473,APC XGEN [$2]: Generator shutdown.
474=475,473,2,LOG,MAP,NOBELL,MINUS,473,NONE,X3180474,APC XGEN [$2]: Generator shutdown is cleared.
475=476,474,0,LOG,MAP,NOBELL,PLUS,476,NONE,X3180475,APC XGEN [$2]: Generator batt. charger is nonfunctional.
476=477,475,2,LOG,MAP,NOBELL,MINUS,475,NONE,X3180476,APC XGEN [$2]: Fault in the generator battery charger is cleared.
477=478,476,1,LOG,MAP,NOBELL,PLUS,478,3,X3180477,APC XGEN [$2]: Generator generic event.
478=479,477,2,LOG,MAP,NOBELL,MINUS,477,NONE,X3180478,APC XGEN [$2]: Generic generator event is cleared.
479=480,478,2,LOG,MAP,NOBELL,MINUS,344,NONE,X3180479,APC XPDU [$2]: Communication error cleared.
480=481,479,0,LOG,MAP,NOBELL,PLUS,481,3,X3180480,APC XPDU [$2]: System state change alarm $3.
481=482,480,2,LOG,MAP,NOBELL,MINUS,480,3,X3180481,APC XPDU [$2]: Normal system state change $3.
482=483,481,1,LOG,MAP,NOBELL,PLUS,483,NONE,X3180482,APC XPDU [$2]: Emergency Power Off (EPO) in test mode.
483=484,482,2,LOG,MAP,NOBELL,MINUS,482,NONE,X3180483,APC XPDU [$2]: Emergency Power Off (EPO) enabled.
484=485,483,0,LOG,MAP,NOBELL,PLUS,485,3,X3180484,APC XPDU [$2]: Check fuse $3.
485=486,484,2,LOG,MAP,NOBELL,MINUS,484,3,X3180485,APC XPDU [$2]: Check fuse $3 alarm cleared.
486=487,485,0,LOG,MAP,NOBELL,PLUS,487,3,X3180486,APC XPDU [$2]: Breaker $3 alarm $4.
487=488,486,2,LOG,MAP,NOBELL,MINUS,486,3,X3180487,APC XPDU [$2]: Breaker position alarm cleared.
488=489,487,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180488,APC XPDU [$2]: Breaker $3 changed $4.
489=490,488,0,LOG,MAP,NOBELL,PLUS,490,1,X3180489,APC XPDU [$2]: Data mismatch error.
490=491,489,2,LOG,MAP,NOBELL,MINUS,489,1,X3180490,APC XPDU [$2]: Data mismatch error cleared.
491=492,490,1,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180491,APC XPDU [$2]: System state changed to maintenance bypass.
492=493,491,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180492,APC XPDU [$2]: System state changed to UPS operational.
493=494,492,1,LOG,MAP,NOBELL,PLUS,494,NONE,X3180493,APC XGEN [$2]: Generator inner wall rupture alarm.
494=495,493,2,LOG,MAP,NOBELL,MINUS,493,NONE,X3180494,APC XGEN [$2]: Generator inner wall rupture alarm cleared.
495=496,494,0,LOG,MAP,NOBELL,PLUS,496,NONE,X3180495,APC XGEN [$2]: Generator ground fault alarm.
496=497,495,2,LOG,MAP,NOBELL,MINUS,495,NONE,X3180496,APC XGEN [$2]: Generator ground fault alarm cleared.
497=498,496,1,LOG,MAP,NOBELL,PLUS,498,NONE,X3180497,APC XATS [$2]: System load powered by generator alarm.
498=499,497,2,LOG,MAP,NOBELL,MINUS,497,NONE,X3180498,APC XATS [$2]: System load powered by generator alarm cleared.
499=500,498,2,LOG,MAP,NOBELL,PLUS,500,1,X3180499,APC [$2]: Start update transfer.
500=501,499,2,LOG,MAP,NOBELL,MINUS,499,1,X3180500,APC [$2]: update transfer complete.
501=502,500,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180501,APC [$2]: Update transfer failed.
502=503,501,1,LOG,MAP,NOBELL,MINUS,503,NONE,X3180502,APC UPS: The PFC input relay failure exists.
503=504,502,2,LOG,MAP,NOBELL,PLUS,502,NONE,X3180503,APC UPS: The PFC input relay failure cleared.
504=505,503,1,LOG,MAP,NOBELL,MINUS,505,NONE,X3180504,APC UPS: The inverter over temperature condition exists.
505=506,504,2,LOG,MAP,NOBELL,PLUS,504,NONE,X3180505,APC UPS: The inverter over temperature condition cleared.
506=507,505,1,LOG,MAP,NOBELL,MINUS,507,NONE,X3180506,APC UPS: The battery over voltage condition exists.
507=508,506,2,LOG,MAP,NOBELL,PLUS,506,NONE,X3180507,APC UPS: The battery over voltage condition cleared.
508=509,507,1,LOG,MAP,NOBELL,MINUS,507,NONE,X3180508,APC UPS: The EEPROM fault exists.
509=510,508,2,LOG,MAP,NOBELL,PLUS,506,NONE,X3180509,APC UPS: The EEPROM fault cleared.
510=511,509,1,LOG,MAP,NOBELL,PLUS,511,3,X3180510,APC ARU [$4]: Fan [$5] Runhour has Exceeded its Threshold.
511=512,510,2,LOG,MAP,NOBELL,MINUS,510,3,X3180511,APC ARU [$4]: Fan [$5] Runhour Alarm Cleared.
512=513,511,1,LOG,MAP,NOBELL,PLUS,513,3,X3180512,APC ARU [$4]: Fan [$5] Poor Performance Detected.
513=514,512,2,LOG,MAP,NOBELL,MINUS,512,3,X3180513,APC ARU [$4]: Fan [$5] Performance Restored.
514=515,513,1,LOG,MAP,NOBELL,PLUS,515,3,X3180514,APC ARU [$4]: Redundant AC Input has been Lost.
515=516,514,2,LOG,MAP,NOBELL,MINUS,514,3,X3180515,APC ARU [$4]: Redundant AC Input has been Restored.
516=517,515,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180516,APC [$2]: Device configuration change.
517=518,516,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180517,APC ENV [$2]: Sensor $4 Connected.
518=519,517,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180518,APC ENV [$2]: Sensor $4 Disconnected.
519=520,518,0,LOG,MAP,NOBELL,PLUS,520,4,X3180519,APC ENV [$2]: Over max temp on Sensor $5.
520=521,519,2,LOG,MAP,NOBELL,MINUS,519,4,X3180520,APC ENV [$2]: Over max temp on Sensor $4 cleared.
521=522,520,1,LOG,MAP,NOBELL,PLUS,522,4,X3180521,APC ENV [$2]: Overtemp on Sensor $4).
522=523,521,2,LOG,MAP,NOBELL,MINUS,521,4,X3180522,APC ENV [$2]: Overtemp on Sensor $4 cleared.
523=524,522,1,LOG,MAP,NOBELL,PLUS,524,4,X3180523,APC ENV [$2]: Undertemp on Sensor $4.
524=525,523,2,LOG,MAP,NOBELL,MINUS,523,4,X3180524,APC ENV [$2]: Undertemp on Sensor $4 cleared.
525=526,524,0,LOG,MAP,NOBELL,PLUS,526,4,X3180525,APC ENV [$2]: Under min temp on Sensor $4.
526=527,525,2,LOG,MAP,NOBELL,MINUS,525,4,X3180526,APC ENV [$2]: Under min temp on Sensor $4 cleared.
527=528,526,0,LOG,MAP,NOBELL,PLUS,528,4,X3180527,APC ENV [$2]: ST inc. temp rate on Sensor $4.
528=529,527,2,LOG,MAP,NOBELL,MINUS,527,4,X3180528,APC ENV [$2]: ST inc. temp rate on Sensor $4 cleared.
529=530,528,0,LOG,MAP,NOBELL,PLUS,530,4,X3180529,APC ENV [$2]: ST dec. temp rate on Sensor $4.
530=531,529,2,LOG,MAP,NOBELL,MINUS,529,4,X3180530,APC ENV [$2]: ST dec. temp rate on Sensor $4 cleared.
531=532,530,0,LOG,MAP,NOBELL,PLUS,532,4,X3180531,APC ENV [$2]: LT inc. temp rate on Sensor $4.
532=533,531,2,LOG,MAP,NOBELL,MINUS,531,4,X3180532,APC ENV [$2]: LT inc. temp rate on Sensor $4 cleared.
533=534,532,0,LOG,MAP,NOBELL,PLUS,534,4,X3180533,APC ENV [$2]: LT dec. temp rate on Sensor $4.
534=535,533,2,LOG,MAP,NOBELL,MINUS,533,4,X3180534,APC ENV [$2]: LT dec. temp rate on Sensor $4 cleared.
535=536,534,0,LOG,MAP,NOBELL,PLUS,536,4,X3180535,APC ENV [$2]: Over max Humidity on Sensor $4.
536=537,535,2,LOG,MAP,NOBELL,MINUS,535,4,X3180536,APC ENV [$2]: Over max Humidity on Sensor $4 cleared.
537=538,536,1,LOG,MAP,NOBELL,PLUS,538,4,X3180537,APC ENV [$2]: Over Humidity on Sensor $4.
538=539,537,2,LOG,MAP,NOBELL,MINUS,537,4,X3180538,APC ENV [$2]: Over Humidity on Sensor $4 cleared.
539=540,538,1,LOG,MAP,NOBELL,PLUS,540,4,X3180539,APC ENV [$2]: Under Humidity on Sensor $4.
540=541,539,2,LOG,MAP,NOBELL,MINUS,539,4,X3180540,APC ENV [$2]: Under Humidity on Sensor $4 cleared.
541=542,540,0,LOG,MAP,NOBELL,PLUS,542,4,X3180541,APC ENV [$2]: Under min Humidity on Sensor $4.
542=543,541,2,LOG,MAP,NOBELL,MINUS,541,4,X3180542,APC ENV [$2]: Under min Humidity on Sensor $4 cleared.
543=544,542,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180543,APC [$2]: Beacon Connected.
544=545,543,0,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180544,APC [$2]: Beacon Disconnected.
545=546,544,2,LOG,MAP,NOBELL,PLUS,546,NONE,X3180545,APC [$2]: Beacon On.
546=547,545,2,LOG,MAP,NOBELL,MINUS,545,NONE,X3180546,APC [$2]: Beacon Off.
547=548,546,1,LOG,MAP,NOBELL,PLUS,548,4,X3180547,APC [$2]: Outlet $4 to abnormal state $6.
548=549,547,2,LOG,MAP,NOBELL,MINUS,547,4,X3180548,APC [$2]: Outlet $4 to normal state $6.
549=550,548,1,LOG,MAP,NOBELL,PLUS,550,4,X3180549,APC [$2]: Relay $4 to abnormal state $6.
550=551,549,2,LOG,MAP,NOBELL,MINUS,549,4,X3180550,APC [$2]: Relay $4 to normal state $6.
551=552,550,0,LOG,MAP,NOBELL,PLUS,552,1,X3180551,APC [$2]: Hardware is in an abnormal state.
552=553,551,2,LOG,MAP,NOBELL,MINUS,551,1,X3180552,APC [$2]: Hardware is in its normal state.
553=554,552,0,LOG,MAP,NOBELL,PLUS,554,4,X3180553,APC [$2]: Discrete contact $4 to abnormal state $6.
554=555,553,2,LOG,MAP,NOBELL,MINUS,553,4,X3180554,APC [$2]: Discrete contact $4 to normal state $6.
555=556,554,1,LOG,MAP,NOBELL,PLUS,556,4,X3180555,APC [$2]: Discrete contact $4 to abnormal state $6.
556=557,555,2,LOG,MAP,NOBELL,MINUS,555,4,X3180556,APC [$2]: Discrete contact $4 to normal state $6.
557=558,556,2,LOG,MAP,NOBELL,PLUS,558,4,X3180557,APC [$2]: Discrete contact $4 to abnormal state $6.
558=559,557,2,LOG,MAP,NOBELL,MINUS,557,4,X3180558,APC [$2]: Discrete contact $4 to normal state $6.
559=560,558,0,LOG,MAP,NOBELL,PLUS,560,4,X3180559,APC [$2]: Under max threshold on input $5.
560=561,559,2,LOG,MAP,NOBELL,MINUS,559,4,X3180560,APC [$2]: Over max threshold on input $5 cleared.
561=562,560,1,LOG,MAP,NOBELL,PLUS,562,4,X3180561,APC [$2]: Over high threshold on input $5.
562=563,561,2,LOG,MAP,NOBELL,MINUS,561,4,X3180562,APC [$2]: Over high threshold on input $5 cleared.
563=564,562,1,LOG,MAP,NOBELL,PLUS,564,4,X3180563,APC [$2]: Under low threshold on input $5.
564=565,563,2,LOG,MAP,NOBELL,MINUS,563,4,X3180564,APC [$2]: Under low threshold on input $5 cleared.
565=566,564,0,LOG,MAP,NOBELL,PLUS,566,4,X3180565,APC [$2]: Under min threshold on input $5.
566=567,565,2,LOG,MAP,NOBELL,MINUS,565,4,X3180566,APC [$2]: Under min threshold on input $5 cleared.
567=568,566,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180567,APC: Lost communications reset command has been issued.
568=569,567,2,LOG,MAP,NOBELL,PLUS,569,3,X3180568,APC ENV [$2]: Device $4 Connected.
569=570,568,0,LOG,MAP,NOBELL,MINUS,568,3,X3180569,APC [$2]: Device $4 Disconnected.
570=571,569,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180570,APC Unregistered user's RFID $5.
571=572,570,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180571,APC Access denied, user $5.
572=573,571,2,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180572,APC Registered user configuration change.
573=574,572,2,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180573,APC Door unlocked, door access user $5.
574=575,573,2,LOG,MAP,NOBELL,MINUS,573,NONE,X3180574,APC Door locked, door access user $5.
575=576,574,2,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180575,APC $4 door handle opened.
576=577,575,2,LOG,MAP,NOBELL,MINUS,575,NONE,X3180576,APC $4 door handle closed.
577=578,576,2,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180577,APC $4 door opened.
578=580,577,2,LOG,MAP,NOBELL,MINUS,577,NONE,X3180578,APC $4 door closed.
580=581,578,1,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180580,APC: Key override unlock has occurred on door $4.
581=582,580,2,LOG,MAP,NOBELL,MINUS,580,NONE,X3180581,APC: Key override lock has occurred on door $4.
582=583,581,0,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180582,APC: Forced entry has occurred on door $4.
583=584,582,2,LOG,MAP,NOBELL,MINUS,582,NONE,X3180583,APC: forced entry has has been cleared on door $4.
584=585,583,0,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180584,APC relock timeout on $4.
585=586,584,2,LOG,MAP,NOBELL,MINUS,584,NONE,X3180585,APC relock timout has been cleared on $4.
586=587,585,0,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180586,APC: A door sensor was disconnected on door $4.
587=588,586,2,LOG,MAP,NOBELL,MINUS,586,NONE,X3180587,APC: A door sensor was connected on door $4.
588=589,587,0,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180588,APC: Communication was lost with door $4.
589=590,588,2,LOG,MAP,NOBELL,MINUS,588,NONE,X3180589,APC: Communication has been established with door $4.
590=591,589,2,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180590,APC Registered user access change.
591=592,590,2,LOG,MAP,NOBELL,PLUS,NONE,NONE,X3180591,APC Unregistered user status change.
592=600,591,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180592,APC: User configurations reset command has been issued.
600=601,592,1,LOG,MAP,NOBELL,MINUS,601,NONE,X3180600,APC UPS: The battery temperature sensor fault exists.
601=602,600,2,LOG,MAP,NOBELL,PLUS,600,NONE,X3180601,APC UPS: The battery temperature sensor fault cleared.
602=603,601,1,LOG,MAP,NOBELL,MINUS,603,NONE,X3180602,APC UPS: A battery bus soft start fault exists.
603=604,602,2,LOG,MAP,NOBELL,PLUS,602,NONE,X3180603,APC UPS: A battery bus soft start fault exists cleared.
604=605,603,1,LOG,MAP,NOBELL,MINUS,605,NONE,X3180604,APC Device: An output short circuit condition exists.
605=606,604,2,LOG,MAP,NOBELL,PLUS,604,NONE,X3180605,APC Device: An output short circuit condition cleared.
606=607,605,1,LOG,MAP,NOBELL,MINUS,607,NONE,X3180606,APC Device: An output relay (or its driver) fault exists.
607=608,606,2,LOG,MAP,NOBELL,PLUS,606,NONE,X3180607,APC Device: An output relay (or its driver) fault cleared.
608=609,607,1,LOG,MAP,NOBELL,MINUS,609,NONE,X3180608,APC UPS: A PFC fault exists.
609=610,608,2,LOG,MAP,NOBELL,PLUS,608,NONE,X3180609,APC UPS: The PFC fault cleared.
610=611,609,1,LOG,MAP,NOBELL,MINUS,611,NONE,X3180610,APC Devcie: DC bus voltage is too high.
611=612,610,2,LOG,MAP,NOBELL,PLUS,610,NONE,X3180611,APC Device: The DC bus voltage is too high cleared.
612=613,611,1,LOG,MAP,NOBELL,MINUS,613,NONE,X3180612,APC UPS: The inverter fault exists.
613=614,612,2,LOG,MAP,NOBELL,PLUS,612,NONE,X3180613,APC UPS: The inverter fault cleared.
614=615,613,1,LOG,MAP,NOBELL,MINUS,615,NONE,X3180614,APC Device: The A/D converter fault exists.
615=616,614,2,LOG,MAP,NOBELL,PLUS,614,NONE,X3180615,APC Device: The A/D converter fault cleared.
616=617,615,1,LOG,MAP,NOBELL,MINUS,617,NONE,X3180616,APC Device: A logic power supply fault exists.
617=618,616,2,LOG,MAP,NOBELL,PLUS,616,NONE,X3180617,APC Device: A logic power supply fault cleared.
618=619,617,1,LOG,MAP,NOBELL,MINUS,619,NONE,X3180618,APC Device: The DC component of the tformer's curr is too high.
619=620,618,2,LOG,MAP,NOBELL,PLUS,618,NONE,X3180619,APC Device: The DC component of the tformer's curr is normal.
620=621,619,1,LOG,MAP,NOBELL,MINUS,621,NONE,X3180620,UPS Device: The backfeed relay (or its driver) has a fault.
621=622,620,2,LOG,MAP,NOBELL,PLUS,620,NONE,X3180621,UPS Device: The bfeed rly (or its drver) has a flt cleared.
622=623,621,1,LOG,MAP,NOBELL,MINUS,623,NONE,X3180622,APC Device: A bypass relay (or its driver) has a fault.
623=624,622,2,LOG,MAP,NOBELL,PLUS,622,NONE,X3180623,APC Device: A bypass relay (or its driver) has a fault cleared.
624=625,623,0,LOG,MAP,NOBELL,MINUS,625,NONE,X3180624,APC Device: A main relay (or its driver) has a fault.
625=626,624,2,LOG,MAP,NOBELL,PLUS,624,NONE,X3180625,APC Device: A main relay (or its driver) has a fault cleared.
626=627,625,0,LOG,MAP,NOBELL,PLUS,627,3,X3180626,APC XPDU [$2]: Branch circuit current $4 below threshold $5.
627=628,626,2,LOG,MAP,NOBELL,MINUS,626,3,X3180627,APC XPDU [$2]: Branch circuit low current $3 alarm cleared.
628=629,627,0,LOG,MAP,NOBELL,PLUS,629,3,X3180628,APC XPDU [$2]: Branch circuit current $4 above threshold $5.
629=630,628,2,LOG,MAP,NOBELL,MINUS,628,3,X3180629,APC XPDU [$2]: Branch circuit current $4 alarm cleared.
630=631,629,1,LOG,MAP,NOBELL,PLUS,631,1,X3180630,APC Rack PDU: Violation of outlet low load threshold.
631=632,630,2,LOG,MAP,NOBELL,MINUS,630,1,X3180631,APC Rack PDU: Low load condition cleared.
632=633,631,1,LOG,MAP,NOBELL,PLUS,633,1,X3180632,APC Rack PDU: Near an overload condition.
633=634,632,2,LOG,MAP,NOBELL,MINUS,632,1,X3180633,APC Rack PDU: Outlet Near overload condition has cleared.
634=635,633,0,LOG,MAP,NOBELL,PLUS,635,1,X3180634,APC Rack PDU: Outlet Overload condition.
635=636,634,2,LOG,MAP,NOBELL,MINUS,634,1,X3180635,APC Rack PDU: Overload condition has cleared.
636=637,635,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180636,APC: Test trap.
637=999,636,2,LOG,MAP,NOBELL,MINUS,25,NONE,X3180637,APC UPS: Base module fan has been repaired
999=1000,637,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X3180999,APC X.
1000=LastEntry,999,2,LOG,MAP,NOBELL,NONE,NONE,NONE,X31801000,APC X.
X3180001=SEVERE: Communication lost between the agent and the UPS.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180002=SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180003=SEVERE: The UPS has failed its internal self-test.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180004=SEVERE: The UPS batteries are discharged.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180005=WARNING: The UPS has switched to battery backup power.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180006=WARNING: The UPS has enabled SmartBoost(TM); low incoming line voltage.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180007=SEVERE: The UPS system's batteries are low and will soon be exhausted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180008=INFORMATIONAL: UPS communication has been established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180009=INFORMATIONAL: Returned from battery backup power; utility power restored.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180010=INFORMATIONAL: The UPS passed internal self-test.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180011=INFORMATIONAL: The UPS has returned from a Low-Battery condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180012=WARNING: The UPS has been switched off by a management station.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180013=WARNING: The UPS entered sleep mode. Power to the load will be cut off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180014=INFORMATIONAL: The UPS has returned from sleep mode. Power to the load has been restored.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180015=WARNING: The UPS has started its reboot sequence.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180016=WARNING: The DIP switch settings on the UPS have been changed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180017=SEVERE: The UPS batteries require immediate replacement.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180018=SEVERE: An Environment contact $1 closure has faulted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180019=INFORMATIONAL: A Environment contact $1 closure has returned to it's default state.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180020=SEVERE: The UPS is on bypass due to an internal fault.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180021=WARNING: UPS put on bypass by user via software or front UPS panel.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180022=WARNING: UPS put on bypass by user.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180023=INFORMATIONAL: The UPS has returned from bypass mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180024=SEVERE: The base module bypass power supply needs repair.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180025=SEVERE: The base module fan needs repair.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180026=SEVERE: Communication lost with external battery packs, check battery signal cable.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180027=INFORMATIONAL: Communication established with external battery packs.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180028=INFORMATIONAL: A battery run time calibration test has been initiated.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180029=INFORMATIONAL: Agent restarting as commanded by manager.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180030=INFORMATIONAL: A UPS is turned on.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180031=WARNING: The UPS has enabled SmartTrim(TM) voltage reduction.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180032=INFORMATIONAL: Authentication on agent code image is done.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180033=INFORMATIONAL: The overload condition has been cleared. .\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180034=INFORMATIONAL: The UPS has returned from SmartBoost(TM).\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180035=INFORMATIONAL: The UPS has returned from SmartTrim(TM) voltage reduction.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180036=INFORMATIONAL: The UPS has returned from a bad battery fault.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180037=INFORMATIONAL: The UPS has finished calibrating\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180038=INFORMATIONAL: The UPS discharge condition has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180039=INFORMATIONAL: A graceful shutdown has been initiated.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180041=WARNING: Outlet $1 has been turned on\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180042=WARNING: Outlet $1 has turned off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180043=WARNING: Outlet $1 has rebooted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180044=WARNING: The SNMP configuration has been changed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180045=WARNING: Outlet $1 configuration has been changed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180046=WARNING: Three unsuccessful logins have been attempted via the console.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180047=WARNING: An unsuccessful attempt to login via HTTP.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180048=WARNING: Someone has changed the password on the device.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180049=WARNING: The output voltage is not within acceptable range.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180050=INFORMATIONAL: The output voltage has returned to an acceptable level.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180051=WARNING: The battery charger has failed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180052=INFORMATIONAL: The battery charger failure condition has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180053=WARNING: The battery temperature threshold has been violated.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180054=INFORMATIONAL: The battery over temperature has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180055=WARNING: SmartBoost(TM) or SmartTrim(TM) relay fault.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180056=INFORMATIONAL: SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180057=SEVERE: A humidity threshold has been violated on probe 1. Humidity is $1 percent.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180058=INFORMATIONAL: A humidity threshold violation has been cleared on probe 1.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180059=SEVERE: A temperature threshold has been violated on probe 1. Temperature is $1.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180060=INFORMATIONAL: A temperature threshold violation has been cleared on probe 1.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180061=SEVERE: A humidity threshold has been violated on probe 2. Humidity is $1 percent.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180062=INFORMATIONAL: A humidity threshold violation has been cleared on probe 2.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180063=SEVERE: A temperature threshold has been violated on probe 2. Temperature is $1.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180064=INFORMATIONAL: A temperature threshold violation has been cleared on probe 2.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180065=INFORMATIONAL: Communication established between the agent and the Environmental Monitor.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180066=SEVERE: Communication lost between the agent and the Environmental Monitor.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180067=INFORMATIONAL: The number of batteries has increased.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180068=INFORMATIONAL: The number of batteries has decreased.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180069=INFORMATIONAL: The number of power modules has increased.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180070=INFORMATIONAL: The number of power modules has decreased.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180071=INFORMATIONAL: An intelligence module has been inserted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180072=INFORMATIONAL: An intelligence module has been removed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180073=INFORMATIONAL: A redundant intelligence module has been inserted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180074=INFORMATIONAL: A redundant intelligence module has been removed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180075=INFORMATIONAL: An external battery frame has been added.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180076=INFORMATIONAL: An external battery frame has been removed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180077=SEVERE: APC $2\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180078=INFORMATIONAL: APC $2\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180079=INFORMATIONAL: The status of the device being monitored has changed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180080=WARNING: The UPS has no batteries attached.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180081=INFORMATIONAL: The UPS's batteries have been attached.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180082=INFORMATIONAL: A new user has been added.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180083=INFORMATIONAL: A user has been deleted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180084=INFORMATIONAL: A user has been modified.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180085=INFORMATIONAL: Communications with the MasterSwitch VM has been established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180086=SEVERE: Communications with the MasterSwitch VM has been lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180087=SEVERE: The MasterSwitch VM is near or at an overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180088=INFORMATIONAL: The overload condition on the MasterSwitch VM has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180089=INFORMATIONAL: An outlet on the MasterSwitch VM has turned on.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180090=INFORMATIONAL: An outlet on the MasterSwitch VM has turned off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180091=INFORMATIONAL: A device configuration change has been made on a MasterSwitch VM.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180092=INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch VM.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180093=INFORMATIONAL: The MasterSwitch VM has violated the low load threshold.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180094=INFORMATIONAL: The low load condition on the MasterSwitch VM has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180095=SEVERE: The MasterSwitch VM is near or at an overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180096=INFORMATIONAL: The overload condition on the MasterSwitch VM has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180097=WARNING: The power supply status of the MasterSwitch VM has changed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180098=INFORMATIONAL: Communications with the MasterSwitch plus has been established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180099=SEVERE: Communications with the MasterSwitch plus has been lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180100=INFORMATIONAL: An outlet on the MasterSwitch plus has turned on.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180101=INFORMATIONAL: An outlet on the MasterSwitch plus has turned off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180102=INFORMATIONAL: A device configuration change has been made on a MasterSwitch plus.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180103=INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch plus.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180104=INFORMATIONAL: The Redundant Switch has switched source.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180105=SEVERE: The Redundant Switch has lost redundancy.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180106=INFORMATIONAL: Redundancy has been restored to the Redundant Switch .\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180107=INFORMATIONAL: A configuration change has been made on a Redundant Switch.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180108=INFORMATIONAL: Communications with the Redundant Switch has been established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180109=SEVERE: Communications with the Redundant Switch has been lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180110=INFORMATIONAL: Communications with the DC power plant has been established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180111=SEVERE: Communications with the DC power plant has been lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180112=INFORMATIONAL: The active PIN on the DC controller has been changed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180113=SEVERE: A Major alarm is active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180114=INFORMATIONAL: A Major alarm is no longer active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180115=WARNING: A Minor alarm is active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180116=INFORMATIONAL: A Minor alarm is no longer active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180117=WARNING: An output relay has gone on in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180118=INFORMATIONAL: An output relay has gone off in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180119=WARNING: An input relay has gone on in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180120=INFORMATIONAL: An input relay has gone off in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180121=INFORMATIONAL: The number of system power supplies has increased.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180122=INFORMATIONAL: The number of system power supplies has decreased.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180123=INFORMATIONAL: External Switch Gear $1 closed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180124=INFORMATIONAL: External Switch Gear $1 opened.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180125=INFORMATIONAL: $1 APC Device event.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180126=INFORMATIONAL: The Automatic Transfer Switch has switched source.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180127=SEVERE: The Automatic Transfer Switch has lost redundancy.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180128=INFORMATIONAL: Redundancy has been restored to the Automatic Transfer Switch .\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180129=INFORMATIONAL: A configuration change has been made on a Automatic Transfer Switch.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180130=INFORMATIONAL: Communications with the Automatic Transfer Switch has been established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180131=SEVERE: Communications with the Automatic Transfer Switch has been lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180132=SEVERE: Output Current has exceeded Threshold. \n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180133=INFORMATIONAL: Output Current has returned below threshold.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180134=SEVERE: The Automatic Transfer Switch Power Supply has failed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180135=INFORMATIONAL: The Automatic Transfer Switch Power Supply Failure Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180136=WARNING: A Mains Fail alarm is active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180137=INFORMATIONAL: Mains Fail alarm is no longer active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180138=WARNING: A Fan Fail alarm is active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180139=INFORMATIONAL: A Fan Fail alarm is no longer active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180140=WARNING: Rect. Overtemp alarm is active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180141=INFORMATIONAL: Rect. Overtemp alarm is no longer active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180142=WARNING: A Current Limit alarm is active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180143=INFORMATIONAL: Current Limit alarm is no longer active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180144=WARNING: A Rect. Fail alarm is active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180145=INFORMATIONAL: Rect. Fail alarm is no longer active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180146=WARNING: Multiple Rect. Fail alarm is active in the powerplant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180147=INFORMATIONAL: Multiple Rect Fail alarm is no longer active in the powerplant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180148=WARNING: Batt. Breaker alarm is active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180149=INFORMATIONAL: Batt. Breaker alarm is no longer active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180150=WARNING: A Rect. OVP alarm is active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180151=INFORMATIONAL: A Rect. OVP alarm is no longer active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180152=WARNING: A LVD Imminent alarm is active in the powerplant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180153=INFORMATIONAL: A LVD Imminent alarm is no longer active in the powerplant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180154=WARNING: A Fuse/CB alarm is active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180155=INFORMATIONAL: A Fuse/CB alarm is no longer active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180156=WARNING: A Battery Test failed in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180157=WARNING: A Temperature alarm is active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180158=INFORMATIONAL: A Temperature alarm is no longer active in the power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180159=WARNING: A Humidity alarm is active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180160=INFORMATIONAL: A Humidity alarm is no longer active in the DC power plant.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180161=INFORMATIONAL: Power plant bridging board communications established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180162=SEVERE: Power plant bridging board communications lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180163=SEVERE: High temperature threshold of violation of $1 $2 on probe $3, $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180164=INFORMATIONAL: High temperature threshold violation has been cleared on probe $1, $2.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180165=SEVERE: Low temperature threshold of violation of $1 $2 on probe $3, $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180166=INFORMATIONAL: Low temperature threshold violation has been cleared on probe $1, $2.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180167=SEVERE: High humidity threshold of violation of $1 percent relative humidity on probe $2, $3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180168=INFORMATIONAL: High humidity threshold violation on probe $1, $2, has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180169=SEVERE: High humidity threshold of violation of $1 percent relative humidity on probe $2, $3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180170=INFORMATIONAL: Low humidity threshold violation on probe $1, $2, has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180171=WARNING: Probe has been disconnected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180172=INFORMATIONAL: Probe has been connected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180173=SEVERE: There is a fault on contact $1, $2.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180174=INFORMATIONAL: There is a fault on contact $1, $2.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180175=SEVERE: Output relay $1, $2, has faulted because $3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180176=INFORMATIONAL: Output relay $1, $2 fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180177=INFORMATIONAL: Unit $1 Communications Established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180178=SEVERE: Unit $1 Communications Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180179=SEVERE: Unit $1 Knee Alarm Detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180180=INFORMATIONAL: Unit $1 Knee Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180181=WARNING: Unit $1 Charger Alarm Detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180182=INFORMATIONAL: Unit $1 Charger Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180183=WARNING: Unit $1 Battery Alarm Detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180184=INFORMATIONAL: Unit $1 Battery Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180185=WARNING: Unit $1 Environment Alarm Detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180186=INFORMATIONAL: Unit $1 Environment Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180187=INFORMATIONAL: Unit $1 Maintenance Due Alarm Detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180188=INFORMATIONAL: Unit $1 Maintenance Due Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180189=INFORMATIONAL: Communication Established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180190=SEVERE: Communication Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180191=SEVERE: Utility Line Undervoltage L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180192=INFORMATIONAL: Utility Line Undervoltage Cleared L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180193=SEVERE: Utility Line Overvoltage L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180194=INFORMATIONAL: Utility Line Overvoltage Cleared L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180195=SEVERE: Ground Overcurrent.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180196=INFORMATIONAL: Ground Overcurrent Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180197=SEVERE: Circuit Panel Input Undervoltage L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180198=INFORMATIONAL: Circuit Panel Input Undervoltage Cleared L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180199=SEVERE: Circuit Panel Input Overvoltage L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180200=INFORMATIONAL: Circuit Panel Input Overvoltage Cleared L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180201=SEVERE: Circuit Panel Input Undercurrent L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180202=INFORMATIONAL: Circuit Panel Input Undercurrent Cleared L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180203=SEVERE: Circuit Panel Input Overcurrent L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180204=INFORMATIONAL: Circuit Panel Input Overcurrent Cleared L$3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180205=SEVERE: Circuit Panel Input Frequency Out Of Range.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180206=INFORMATIONAL: Circuit Panel Input Frequency No Longer Out Of Range.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180207=SEVERE: Circuit Panel Input Neutral Overcurrent.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180208=INFORMATIONAL: Circuit Panel Input Neutral Overcurrent Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180209=SEVERE: PDU System Off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180210=SEVERE: PDU is in On Battery Mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180211=INFORMATIONAL: PDU is in Maintenance Bypass Mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180212=WARNING: PDU is in Atypical Bypass Mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180213=SEVERE: PDU is in No Panel Feed Mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180214=INFORMATIONAL: PDU is in Ups Operation Mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180215=WARNING: PDU is in Forced Bypass Mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180216=SEVERE: Input Transformer Over Temperature.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180217=INFORMATIONAL: Input Transformer Over Temperature Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180218=SEVERE: UPS Input Voltage L$3-N Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180219=INFORMATIONAL: UPS Input Voltage L$3-N Restored.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180220=SEVERE: Contact $3 Abnormal.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180221=INFORMATIONAL: Contact $3 Normal.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180222=WARNING: A bank or phase on the Rack PDU has violated the low load threshold.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180223=INFORMATIONAL: The bank or phase low load condition on a Rack PDU has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180224=WARNING: A bank or phase of the Rack PDU is near an overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180225=INFORMATIONAL: Rack PDU bank or phase near overload condition has cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180226=SEVERE: A bank or phase of the Rack PDU is in an overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180227=INFORMATIONAL: The bank or phase overload condition on a Rack PDU has cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180228=INFORMATIONAL: ARU device configuration change.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180229=SEVERE: Communication Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180230=INFORMATIONAL: Communication Established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180231=SEVERE: Communication Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180232=INFORMATIONAL: Probe $3 Connected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180233=SEVERE: Probe $3 Disconnected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180234=INFORMATIONAL: Sensor $3 Connected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180235=SEVERE: Sensor $3 Disconnected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180236=SEVERE: Sensor $3 Fault.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180237=INFORMATIONAL: Sensor $3 Fault Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180238=INFORMATIONAL: Beacon Connected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180239=SEVERE: Beacon Disconnected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180240=INFORMATIONAL: Beacon On.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180241=INFORMATIONAL: Beacon Off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180242=SEVERE: Major Alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180243=INFORMATIONAL: Major Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180244=SEVERE: Minor Alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180245=INFORMATIONAL: Minor Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180246=WARNING: Outlet $3 to abnormal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180247=INFORMATIONAL: Outlet $3 to normal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180248=WARNING: Contact $3 to abnormal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180249=INFORMATIONAL: Contact $3 to normal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180250=WARNING: Relay $3 to abnormal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180251=INFORMATIONAL: Relay $3 to normal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180252=INFORMATIONAL: A device configuration change has been made on a EMS.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180253=SEVERE: Overtemp ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180254=INFORMATIONAL: Overtemp ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180255=SEVERE: Undertemp ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180256=INFORMATIONAL: Undertemp ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180257=SEVERE: Over Humidity ($3) on Probe $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180258=INFORMATIONAL: Over Humidity ($3) on Probe $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180259=SEVERE: Under Humidity ($3) on Probe $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180260=INFORMATIONAL: Under Humidity ($3) on Probe $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180261=INFORMATIONAL: Communication Established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180266=INFORMATIONAL: Communication with Rack PDU [$2] established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180267=SEVERE: Communication with Rack PDU [$2] has been lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180268=INFORMATIONAL: Outlet $3 [$4] on Switched Rack PDU [$2] has turned on.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180269=INFORMATIONAL: Outlet $3 [$4] on Switched Rack PDU [$2] has turned off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180270=INFORMATIONAL: Device configuration change made on Rack PDU [$2].\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180271=INFORMATIONAL: Outlet $3 [$4] configuration change made on Switched Rack PDU [$2].\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180272=WARNING: Rack PDU [$2], phase $3 has violated the low load threshold.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180273=INFORMATIONAL: Rack PDU [$2], phase $3 low load condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180274=WARNING: Rack PDU [$2], phase $3 is near an overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180275=INFORMATIONAL: Rack PDU [$2], phase $3 near overload condition has cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180276=SEVERE: Rack PDU [$2], phase $3 is in an overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180277=INFORMATIONAL: Rack PDU [$2], phase $3 overload condition has cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180278=SEVERE: Power Supply 1 on Rack PDU [$2] is in FAIL state.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180279=INFORMATIONAL: Power Supply 1 on Rack PDU [$2] is operating normally.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180280=SEVERE: Power Supply 2 on Rack PDU [$2] is in FAIL state.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180281=INFORMATIONAL: Power Supply 2 on Rack PDU [$2] is operating normally.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180282=INFORMATIONAL: Phase $3 configuration change made on Rack PDU [$2].\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180283=INFORMATIONAL: Cancel Pending Command made for outlet $3 [$4], on Switched Rack PDU $2.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180284=INFORMATIONAL: Communication Established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180285=SEVERE: Communication Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180286=SEVERE: Fan Fail.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180287=INFORMATIONAL: Fan Fail Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180288=SEVERE: Smoke Alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180289=INFORMATIONAL: Smoke Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180290=WARNING: High Temperature Alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180291=INFORMATIONAL: High Temperature Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180292=SEVERE: Exhaust Temperature Alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180293=INFORMATIONAL: Exhaust Temperature Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180294=INFORMATIONAL: Communication Established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180295=SEVERE: Communication Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180296=SEVERE: Alink Power Overload.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180297=INFORMATIONAL: Alink Power Overload Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180298=INFORMATIONAL: Outlet Group $1 turned on\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180299=WARNING: Outlet Group $1 turned off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180300=SEVERE: A critical condition has been detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180301=INFORMATIONAL: A critical condition has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180302=WARNING: A warning condition has been detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180303=INFORMATIONAL: A warning condition has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180304=INFORMATIONAL: An informational condition has been detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180305=INFORMATIONAL: An informational condition has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180306=SEVERE: Critical condition: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180307=INFORMATIONAL: Critical condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180308=WARNING: Warning condition set: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180309=INFORMATIONAL: Warning condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180310=INFORMATIONAL: Informational condition set: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180311=INFORMATIONAL: Informational condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180312=SEVERE: Input voltage $4 is below threshold$5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180313=INFORMATIONAL: Main input voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180314=SEVERE: Input voltage $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180315=INFORMATIONAL: Main input high voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180316=SEVERE: Bypass input voltage $4 is below threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180317=INFORMATIONAL: Bypass input low voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180318=SEVERE: Bypass input voltage $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180319=INFORMATIONAL: Bypass input high voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180320=SEVERE: Output voltage $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180321=INFORMATIONAL: Output low voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180322=SEVERE: Output voltage $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180323=INFORMATIONAL: Output high voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180324=SEVERE: Output current $4 is below threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180325=INFORMATIONAL: Output low current $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180326=SEVERE: Output current $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180327=INFORMATIONAL: Output high current $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180328=SEVERE: Output frequency alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180329=INFORMATIONAL: Output frequency in range.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180330=SEVERE: Earth ground current $3 is above threshold $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180331=INFORMATIONAL: Earth ground high current $3 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180332=SEVERE: Input contact $3 to abnormal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180333=INFORMATIONAL: Input contact $3 to normal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180334=WARNING: Output neutral current $3 is above threshold $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180335=INFORMATIONAL: Output neutral high current $3 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180336=SEVERE: Cooling fan failure.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180337=INFORMATIONAL: Cooling fan alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180338=SEVERE: Transformer temp alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180339=INFORMATIONAL: Transformer temp alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180340=WARNING: Branch circuit current $4 is below threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180341=INFORMATIONAL: Branch circuit low current $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180342=WARNING: Branch circuit current $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180343=INFORMATIONAL: Branch circuit high current $3 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180344=SEVERE: Internal communication error.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180345=SEVERE: Hardware is in an abnormal state.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180346=INFORMATIONAL: Hardware is in its normal state.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180347=SEVERE: Severe condition set: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180348=INFORMATIONAL: Severe condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180349=WARNING: Warning condition set: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180350=INFORMATIONAL: Warning condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180351=INFORMATIONAL: Informational condition set: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180352=INFORMATIONAL: Informational condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180353=WARNING: The internal over temperature condition exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180354=INFORMATIONAL: The internal over temperature condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180355=INFORMATIONAL: The MPU has been reset.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180356=INFORMATIONAL: The Output Switch is closed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180357=INFORMATIONAL: The Output Switch is open.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180358=INFORMATIONAL: A calibration value in the stack was changed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180359=SEVERE: Over max temp ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180360=INFORMATIONAL: Over max temp ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180361=SEVERE: Under min temp ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180362=INFORMATIONAL: Under min temp ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180363=SEVERE: Over max Humidity ($3) on Probe $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180364=INFORMATIONAL: Over max Humidity ($3) on Probe $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180365=SEVERE: Under min Humidity ($3) on Probe $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180366=INFORMATIONAL: Under min Humidity ($3) on Probe $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180367=SEVERE: Short-term inc. temp rate violation. ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180368=INFORMATIONAL: Short-term inc. temp rate violation ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180369=SEVERE: Short-term dec. temp rate violation. ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180370=INFORMATIONAL: Short-term dec. temp rate violation ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180371=SEVERE: Long-term inc. temp rate violation. ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180372=INFORMATIONAL: Long-term inc. temp rate violation ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180373=SEVERE: Long-term dec. temp rate violation. ($3,$4) on Probe $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180374=INFORMATIONAL: Long-term dec. temp rate violation ($3,$4) on Probe $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180375=SEVERE: Critical condition: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180376=INFORMATIONAL: Critical condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180377=WARNING: Warning condition set: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180378=INFORMATIONAL: Warning condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180379=INFORMATIONAL: Informational condition set: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180380=INFORMATIONAL: Informational condition cleared: $1\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180381=SEVERE: Output voltage $4 is below threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180382=INFORMATIONAL: Output low voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180383=SEVERE: Output voltage $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180384=INFORMATIONAL: Output high voltage $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180385=SEVERE: Output current $4 is below threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180386=INFORMATIONAL: Output low current $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180387=SEVERE: Output current $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180388=INFORMATIONAL: Output high current $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180389=SEVERE: Output frequency is out-of-range.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180390=INFORMATIONAL: Output frequency in range.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180391=SEVERE: Internal communication error.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180392=INFORMATIONAL: ATS Communication error cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180393=SEVERE: ATS data mismatch error.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180394=INFORMATIONAL: ATS data mismatch error cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180395=WARNING: ATS/Generator communication lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180396=INFORMATIONAL: ATS/generator communication established.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180397=WARNING: Transferred to neutral.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180398=INFORMATIONAL: Source-to-Source transfer.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180399=SEVERE: ATS internal fault detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180400=INFORMATIONAL: ATS internal fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180401=INFORMATIONAL: Engine Start asserted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180402=INFORMATIONAL: Engine Stop asserted.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180403=SEVERE: Generator failed to start.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180404=WARNING: Generator failed to stop.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180405=SEVERE: ATS not in auto.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180406=INFORMATIONAL: ATS in auto mode.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180407=SEVERE: EPO tripped.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180408=INFORMATIONAL: EPO armed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180409=WARNING: EPO disabled.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180410=INFORMATIONAL: EPO armed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180411=INFORMATIONAL: Test initiated.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180412=INFORMATIONAL: Test canceled.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180413=SEVERE: Initiated test failed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180414=INFORMATIONAL: Initiated test passed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180415=SEVERE: Input contact $3 has changed to its abnormal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180416=INFORMATIONAL: Input contact $3 has changed to its normal state $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180417=SEVERE: Generator/ATS start contact mismatch.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180418=INFORMATIONAL: Generator/ATS start contact mismatch cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180419=WARNING: Panel door open alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180420=INFORMATIONAL: Panel door open alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180421=WARNING: ATS DC backup failure.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180422=INFORMATIONAL: DC backup alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180423=SEVERE: Generator low coolant level alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180424=INFORMATIONAL: Generator low coolant level alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180425=SEVERE: Generator very low coolant level alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180426=INFORMATIONAL: Generator very low coolant level alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180427=SEVERE: Generator high coolant temperature alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180428=INFORMATIONAL: Generator high coolant temperature alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180429=SEVERE: Generator very high coolant temperature alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180430=INFORMATIONAL: Generator very high coolant temperature alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180431=WARNING: Generator low coolant temperature alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180432=INFORMATIONAL: Generator low coolant temperature alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180433=SEVERE: Generator low oil level alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180434=INFORMATIONAL: Generator low oil level alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180435=SEVERE: Generator low battery volts while cranking alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180436=INFORMATIONAL: Generator low battery volts while cranking alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180437=SEVERE: Generator v.low battery volts while cranking alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180438=INFORMATIONAL: Generator v.low battery volts while cranking alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180439=SEVERE: Generator emergency stop engaged.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180440=INFORMATIONAL: Generator emergency stop condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180441=WARNING: Generator high battery volts.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180442=INFORMATIONAL: Generator high battery volts condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180443=SEVERE: Generator low battery volts.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180444=INFORMATIONAL: Generator low battery volts condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180445=SEVERE: Generator not-in-auto.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180446=INFORMATIONAL: Generator not-in-auto cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180447=SEVERE: Generator low oil pressure.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180448=INFORMATIONAL: Generator low oil pressure condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180449=SEVERE: Generator v.low oil pressure.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180450=INFORMATIONAL: Generator v.low oil pressure condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180451=SEVERE: Generator on overload event.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180452=INFORMATIONAL: Generator on overload event cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180453=SEVERE: State of the Generator AC voltage.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180454=INFORMATIONAL: State of the Generator AC voltage cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180455=SEVERE: State of the Generator AC voltage.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180456=INFORMATIONAL: State of the Generator AC voltage cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180457=SEVERE: Generator overspeed condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180458=INFORMATIONAL: Generator overspeed condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180459=SEVERE: Generator engine is cold.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180460=INFORMATIONAL: Engine is cold to start condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180461=SEVERE: Generator output breaker open.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180462=INFORMATIONAL: Generator output breaker open cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180463=WARNING: Generator low fuel level alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180464=INFORMATIONAL: Generator low fuel level alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180465=SEVERE: Generator very low fuel level alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180466=INFORMATIONAL: Generator very low fuel level alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180467=WARNING: Generator low run time alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180468=INFORMATIONAL: Generator low run time alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180469=SEVERE: Generator very low run time alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180470=INFORMATIONAL: Generator very low run time alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180471=WARNING: Generator maintenance due.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180472=INFORMATIONAL: Generator service alarm is cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180473=SEVERE: Generator shutdown\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180474=INFORMATIONAL: Generator shutdown is cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180475=SEVERE: Generator battery charger is nonfunctional\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180476=INFORMATIONAL: Fault in the generator battery charger is cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180477=WARNING: Generator generic event.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180478=INFORMATIONAL: Generic generator event is cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180479=INFORMATIONAL: PDU Communication error cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180480=SEVERE: PDU state change alarm $3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180481=INFORMATIONAL: PDU normal state change $3.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180482=WARNING: EPO disabled.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180483=INFORMATIONAL: EPO armed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180484=SEVERE: Fuse $3 detected opened.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180485=INFORMATIONAL: Fuse $3 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180486=SEVERE: Breaker $3 position alarm $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180487=INFORMATIONAL: Breaker $3 alarm cleared $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180488=INFORMATIONAL: Breaker/switch event.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180489=SEVERE: XPDU data mismatch error.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180490=INFORMATIONAL: XPDU data mismatch error cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180491=WARNING: PDU state changed to maintenance bypass.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180492=INFORMATIONAL: PDU state changed to UPS operational.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180493=WARNING: Generator inner wall rupture alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180494=INFORMATIONAL: Generator inner wall rupture alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180495=SEVERE: Generator ground fault alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180496=INFORMATIONAL: Generator ground fault alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180497=WARNING: System load powered by generator.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180498=INFORMATIONAL: System load powered by generator alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180499=INFORMATIONAL: Start update transfer.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180500=INFORMATIONAL: Update transfer complete.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180501=SEVERE: Update transfer failed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180502=WARNING: The PFC (Power Factor Correction) input relay failure exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180503=INFORMATIONAL: The PFC (Power Factor Correction) input relay failure cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180504=WARNING: The inverter over temperature condition exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180505=INFORMATIONAL: The inverter over temperature condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180506=WARNING: The battery over voltage condition exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180507=INFORMATIONAL: The battery over voltage condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180508=WARNING: The EEPROM fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180509=INFORMATIONAL: The EEPROM fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180510=WARNING: Fan Runhour Alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180511=INFORMATIONAL: Fan Runhour Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180512=WARNING: Fan Health Alarm.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180513=INFORMATIONAL: Fan Health Alarm Cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180514=WARNING: AC Redundancy Lost.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180515=INFORMATIONAL: AC Redundancy Restored.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180516=INFORMATIONAL: A device configuration change has been made on a device.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180517=INFORMATIONAL: Sensor $4 Connected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180518=SEVERE: Sensor $4 Disconnected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180519=SEVERE: Over max temp on Sensor $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180520=INFORMATIONAL: Over max temp on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180521=WARNING: Overtemp on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180522=INFORMATIONAL: Overtemp on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180523=WARNING: Undertemp on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180524=INFORMATIONAL: Undertemp on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180525=SEVERE: Under min temp on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180526=INFORMATIONAL: Under min temp on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180527=SEVERE: Short-term inc. temp rate violation. on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180528=INFORMATIONAL: Short-term inc. temp rate violation on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180529=SEVERE: Short-term dec. temp rate violation. on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180530=INFORMATIONAL: Short-term dec. temp rate violation on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180531=SEVERE: Long-term inc. temp rate violation. on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180532=INFORMATIONAL: Long-term inc. temp rate violation on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180533=SEVERE: Long-term dec. temp rate violation. on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180534=INFORMATIONAL: Long-term dec. temp rate violation on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180535=SEVERE: Over max Humidity on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180536=INFORMATIONAL: Over max Humidity on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180537=WARNING: Over Humidity on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180538=INFORMATIONAL: Over Humidity on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180539=WARNING: Under Humidity on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180540=INFORMATIONAL: Under Humidity on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180541=SEVERE: Under min Humidity on Sensor $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180542=INFORMATIONAL: Under min Humidity on Sensor $4 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180543=INFORMATIONAL: Beacon Connected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180544=SEVERE: Beacon Disconnected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180545=INFORMATIONAL: Beacon On.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180546=INFORMATIONAL: Beacon Off.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180547=WARNING: Outlet $4 to abnormal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180548=INFORMATIONAL: Outlet $4 to normal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180549=WARNING: Relay $4 to abnormal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180550=INFORMATIONAL: Relay $4 to normal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180551=SEVERE: Hardware is in an abnormal state.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180552=INFORMATIONAL: Hardware is in its normal state.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180553=SEVERE: Discrete contact $4 to abnormal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180554=INFORMATIONAL: Discrete contact $4 to normal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180555=WARNING: Discrete contact $4 to abnormal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180556=INFORMATIONAL: Discrete contact $4 to normal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180557=INFORMATIONAL: Discrete contact $4 to abnormal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180558=INFORMATIONAL: Discrete contact $4 to normal state $6.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180559=SEVERE: Over max threshold on input $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180560=INFORMATIONAL: Over max threshold on input $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180561=WARNING: Over high threshold on input $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180562=INFORMATIONAL: Over high threshold on input $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180563=WARNING: Under low threshold on input $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180564=INFORMATIONAL: Under low threshold on input $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180565=SEVERE: Under min threshold on input $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180566=INFORMATIONAL: Under min threshold on input $5 cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180567=INFORMATIONAL: Lost communications reset command has been issued.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180568=INFORMATIONAL: Device $4 Connected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180569=SEVERE: Device $4 Disconnected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180570=INFORMATIONAL: Unregistered user's RFID $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180571=INFORMATIONAL: Access denied, user $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180572=INFORMATIONAL: Registered user configuration change.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180573=INFORMATIONAL: Door unlocked, door access user $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180574=INFORMATIONAL: Door locked, door access user $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180575=INFORMATIONAL: $4 door handle opened.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180576=INFORMATIONAL: $4 door handle closed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180577=INFORMATIONAL: $4 door opened.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180578=INFORMATIONAL: $4 door closed.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180580=WARNING: Key override unlock has occurred on door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180581=INFORMATIONAL: Key override lock has occurred on door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180582=SEVERE: Forced entry has occurred on door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180583=INFORMATIONAL: Forced entry has been cleared on door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180584=SEVERE: Relock timeout on $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180585=INFORMATIONAL: Relock timout has been cleared on $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180586=SEVERE: A door sensor was disconnected on door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180587=INFORMATIONAL: A door sensor was connected on door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180588=SEVERE: Communication was lost with door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180589=INFORMATIONAL: Communication has been established with door $4.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180590=INFORMATIONAL: Registered user access change.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180591=INFORMATIONAL: Unregistered user status change.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180592=INFORMATIONAL: User configurations reset command has been issued.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180600=WARNING: The battery temperature sensor fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180601=INFORMATIONAL: The battery temperature sensor fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180602=WARNING: A battery bus soft start fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180603=INFORMATIONAL: A battery bus soft start fault exists cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180604=WARNING: An output short circuit condition exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180605=INFORMATIONAL: An output short circuit condition cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180606=WARNING: An output relay (or its driver) fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180607=INFORMATIONAL: An output relay (or its driver) fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180608=WARNING: A PFC fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180609=INFORMATIONAL: The PFC fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180610=WARNING: The DC bus voltage is too high.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180611=INFORMATIONAL: The DC bus voltage is too high cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180612=WARNING: The inverter fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180613=INFORMATIONAL: The inverter fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180614=WARNING: The A/D converter fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180615=INFORMATIONAL: The A/D converter fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180616=WARNING: A logic power supply fault exists.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180617=INFORMATIONAL: A logic power supply fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180618=WARNING: The DC component of the transformer's current is too high.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180619=INFORMATIONAL: The DC component of the transformer's current is normal.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180620=WARNING: The backfeed relay (or its driver) has a fault.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180621=INFORMATIONAL: The backfeed relay (or its driver) has a fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180622=WARNING: A bypass relay (or its driver) has a fault.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180623=INFORMATIONAL: A bypass relay (or its driver) has a fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180624=SEVERE: A main relay (or its driver) has a fault.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180625=INFORMATIONAL: A main relay (or its driver) has a fault cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180626=SEVERE: Branch circuit current $4 is below threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180627=INFORMATIONAL: Branch circuit low current $4 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180628=SEVERE: Branch circuit current $4 is above threshold $5.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180629=INFORMATIONAL: Branch circuit high current $3 alarm cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180630=WARNING: A Rack PDU has violated the outlet low load threshold.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180631=INFORMATIONAL: The low load condition on a Rack PDU has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180632=WARNING: A Rack PDU is near an outlet overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180633=INFORMATIONAL: Rack PDU outlet near overload condition has cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180634=SEVERE: A Rack PDU is in an outlet overload condition.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180635=INFORMATIONAL: The outlet overload condition on a Rack PDU has cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180636=INFORMATIONAL: Test Trap.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180637=INFORMATIONAL: The base module fan has been repaired.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3180999=INFORMATIONAL: .\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X31801000=INFORMATIONAL: .\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3181000=SEVERE: Undefined condition has been detected.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*
X3181001=INFORMATIONAL: Undefined condition has been cleared.\n\nAPC PowerNet Agent\n\nTrap Arguments:\n$*