-- Water Cooled Rack Monitor - (WCRM) MIB
-- Management Information Base for SNMP Network Management
--
-- *********************************************************************
-- Release History
-- Date: August 1, 2005 (Version 1.0)
-- Revised by Charles Cochran - Initial release
-- Date: December 12, 2006 (Version 1.1)
-- Changes: Added MIB-Variable for Waterflow Unit (liter/min or gallon/min),
-- Added Emergency Door Opening (EDO) Thresholds to waterCoolUnitOutputType
-- Added EDO description to MsgStatus
-- Added Condensation Pump Running Time and Cycles Thresholds to waterCoolUnitOutputType
-- Date: July 30, 2007 (Version 1.2)
-- Changes: Added new 'waterCoolUnitSensorType' for MCSS
-- Addes new 'waterCoolUnitOutputType' for MCSS
--
-- Copyright 2005-2008 Hewlett-Packard Development Company, L.P.
--
-- Hewlett-Packard Company shall not be liable for technical or
-- editorial errors or omissions contained herein. The information in
-- this document is provided "as is" without warranty of any kind and
-- is subject to change without notice. The warranties for HP products
-- are set forth in the express limited warranty statements
-- accompanying such products. Nothing herein should be construed as
-- constituting an additional warranty.
--
-- Confidential computer software. Valid license from HP required for
-- possession, use or copying. Consistent with FAR 12.211 and 12.212,
-- Commercial Computer Software, Computer Software Documentation, and
-- Technical Data for Commercial Items are licensed to the U.S.
-- Government under vendor's standard commercial license.
--
-- Refer to the READMIB.RDM file for more information about the
-- organization of the information in the Compaq Enterprise.
--
-- The Compaq Enterprise number is 232.
-- The ASN.1 prefix to, and including the Compaq Enterprise is:
-- 1.3.6.1.4.1.232
--
-- *********************************************************************
-- VARIABLES REQUIRED FOR HP MANAGEMENT
-- ===================================================================================
-- cpqSiProductName (1.3.6.1.4.1.232.2.2.4.2) which is defined in CPQSINFO.MIB.
-- This is the product model name
--
-- cpqSiProductName OBJECT-TYPE
-- SYNTAX DisplayString (SIZE (0..255))
-- ACCESS read-only
-- STATUS mandatory
-- DESCRIPTION
-- "This device product name."
-- ::= { cpqSiSystemBoard 2 }
-- ===================================================================================
--
-- ===================================================================================
-- cpqHoGUID (1.3.6.1.4.1.232.11.2.10.3) which is defined in CPQHOST.MIB
-- This field needs to be filled
-- with the unique serial number (16 bytes)
--
-- cpqHoGUID OBJECT-TYPE
-- SYNTAX OCTET STRING (SIZE (16))
-- ACCESS read-write
-- STATUS mandatory
-- DESCRIPTION
-- "The globally unique identifier of this device."
--
-- ::= { cpqHoSystemStatus 3 }
-- ====================================================================================
--
-- ====================================================================================
-- cpqHoMibStatusArray (1.3.6.1.4.1.232.11.2.10.1) which is defined in CPQHOST.MIB
-- Pretty complicated to decipher if you do not have the guide. We only use the first
-- 4 octets.
--
-- Octet 0 = 00000001 (always)
-- Octet 1 = 00000000 through 00000100 depending on Device H/W Condition below
-- Octet 2 = 00000001 (always)
-- Octet 3 = 00010000 (always decimal 16 see table below)
--
-- For example: With a device with OK status, the values of the 4 octets would be:
--
-- Octet 0 = 0x01 (fixed)
-- Octet 1 = 0x02 (OK overall status)
-- Octet 2 = 0x01 (fixed)
-- Octet 3 = 0x12 (Device type = 18 for Environmental Monitor)
--
-- cpqHoMibStatusArray OBJECT-TYPE
-- SYNTAX OCTET STRING (SIZE (4..256))
-- ACCESS read-only
-- STATUS mandatory
-- DESCRIPTION
-- "The MIB Status Array is an array of MIB status structures. Each
-- structure is made up of 4 octets.
--
-- Array element 0 is the status for all MIBs in the Compaq
-- Enterprise.
--
-- Device H/W Condition (Octet 1)
-- 0 - Not available (e.g. Loss/lack of communication between card and device)
-- 1 - Other (unknown) (mapped to device unknown status)
-- 2 - OK (mapped to device normal status/events)
-- 3 - Degraded (device warning status/events
-- 4 - Failed (device critical status/events
--
-- Detailed Type (octet 3)
-- Bits 0-7 Detailed Type, only used if bit 0 in octect 2 is 1.
--
-- Type Values for Bits 0-4 (maps to CIM7 types)
-- Unknown = 0
-- Server = 1 (yes a duplicate of the server flag)
-- Desktop = 2
-- Workstation = 3
-- Portable = 4
-- Router = 5
-- Cluster = 6
-- Printer = 7
-- Switch = 8 (network switch)
-- Repeater = 9
-- Remote Access Device = 10
-- Other = 11
-- Management Processor = 12 (rib, RILOE, iLo)
-- Rack = 13
-- Enclosure = 14
-- KVM Switch = 15 (IP enabled keyboard video mouse switch).
-- UPS = 16
-- Power Distribution Unit = 17
-- Environmental Monitor = 18 (eg Environmental Controller)"
--
-- ::= { cpqHoSystemStatus 1 }
-- ===============================================================================
CPQWCRM-MIB DEFINITIONS ::= BEGIN
IMPORTS
compaq FROM CPQHOST-MIB
OBJECT-TYPE FROM RFC-1212
DisplayString FROM RFC1213-MIB
sysName FROM RFC1213-MIB
sysDescr FROM RFC1213-MIB
sysContact FROM RFC1213-MIB
sysLocation FROM RFC1213-MIB
TRAP-TYPE FROM RFC-1215;
-- Note: uncomment the following "compaq OBJECT IDENTIFIER" and "enterprises" lines then
-- comment out "compaq FROM CPQHOST-MIB" above to compile without the CPQHOST-MIB
-- enterprises FROM RFC1155-SMI
-- compaq OBJECT IDENTIFIER ::= { enterprises 232 }
cpqWcrm OBJECT IDENTIFIER ::= { compaq 167 }
cpqWcrmMibRev OBJECT IDENTIFIER ::= { cpqWcrm 1 }
cpqWcrmStatus OBJECT IDENTIFIER ::= { cpqWcrm 2 }
cpqWcrmStatusSensorInternal OBJECT IDENTIFIER ::= { cpqWcrmStatus 3 }
cpqWcrmStatusInternalSensors OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 5 }
cpqWcrmStatusInternalOutputs OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 6 }
cpqWcrmStatusInternalMsg OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 7 }
cpqWcrmStatusSensorWaterCoolUnit OBJECT IDENTIFIER ::= { cpqWcrmStatus 4 }
cpqWcrmStatusWaterCoolUnitSensors OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 5 }
cpqWcrmStatusWaterCoolUnitOutputs OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 6 }
cpqWcrmStatusWaterCoolUnitMsg OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 7 }
cpqWcrmSetup OBJECT IDENTIFIER ::= { cpqWcrm 3 }
cpqWcrmSetupGeneral OBJECT IDENTIFIER ::= { cpqWcrmSetup 1 }
cpqWcrmTimerTable1 OBJECT IDENTIFIER ::= { cpqWcrmSetupGeneral 8 }
cpqWcrmTrapControl OBJECT IDENTIFIER ::= { cpqWcrm 4 }
cpqWcrmTraps OBJECT IDENTIFIER ::= { cpqWcrmTrapControl 7 }
cpqWcrmControl OBJECT IDENTIFIER ::= { cpqWcrm 5 }
--*****************************************************************************
-- HP Modular Control System Environmental Controller
--*****************************************************************************
--cpqWcrmMibRev-group
cpqWcrmMibMajRev OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Major Revision level.
A change in the major revision level represents a major change
in the architecture of the MIB. A change in the major revision
level may indicate a significant change in the information,
correct interpretation of data may require a MIB document
with the same major revision level."
::= { cpqWcrmMibRev 1 }
cpqWcrmMibMinRev OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Minor Revision level.
A change in the minor revision level may represent some minor
additional support, no changes to any pre-existing information
has occurred."
::= { cpqWcrmMibRev 2 }
cpqWcrmMibCondition OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
degraded (3),
failed (4),
configChanged (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The overall condition (status) of the system represented by
this MIB.
(2) OK
(3) a minor problem, warning condition (yellow LED on Environmental Controller)
(4) a major problem (red LED on Environmental Controller)
(5) configuration of sensor units changed or
unit detected (red/yellow/green LED on Environmental Controller)"
::= { cpqWcrmMibRev 3 }
--status-group
cpqWcrmStatusDeviceEnvironmentalController OBJECT-TYPE
SYNTAX INTEGER {
failed(1),
ok(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status of Environmental Controller unit itself
(1) failed
(2) OK"
::= { cpqWcrmStatus 1 }
cpqWcrmUnitsConnected OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensor units connected to the Environmental Controller, Port 1 to 2"
::= { cpqWcrmStatus 2 }
cpqWcrmURL OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..80))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"URL of the management interface in the format http[s]://ipaddr[:port#][/page]"
::= { cpqWcrmStatus 7 }
--status sensor units-group
--unit 1
cpqWcrmInternalTypeOfDevice OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
unitWcrm (2),
unitIO (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor unit connected to port 1"
::= { cpqWcrmStatusSensorInternal 1 }
cpqWcrmInternalText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for sensor unit connected to port 1"
::= { cpqWcrmStatusSensorInternal 2 }
cpqWcrmInternalSerial OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Serialnumber of sensor unit connected to port 1"
::= { cpqWcrmStatusSensorInternal 3 }
cpqWcrmInternalStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
error(2),
changed(3),
reset(4),
timeout(5),
detected(6),
notAvail(7),
lowPower(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status sensor unit connected to port 1
(1) OK
(2) error, e. g. value overflow
(3) configuration of sensor unit has changed, confirmation required
(4) reset from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required to unload this unit
(6) sensor unit detected, needs to be confirmed
(7) unit is not available
(8) supply voltage is too low"
::= { cpqWcrmStatusSensorInternal 4 }
-- Sensors
cpqWcrmInternalNumberOfSensors OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors connected to sensor unit 1"
::= { cpqWcrmStatusInternalSensors 1 }
-- table with entry for each sensor available on this unit
cpqWcrmInternalSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmInternalSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of sensor table"
::= { cpqWcrmStatusInternalSensors 2 }
cpqWcrmInternalSensorEntry OBJECT-TYPE
SYNTAX CpqWcrmInternalSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of sensor table"
INDEX { internalSensorIndex }
::= { cpqWcrmInternalSensorTable 1 }
CpqWcrmInternalSensorEntry ::=
SEQUENCE {
internalSensorIndex
INTEGER,
internalSensorType
INTEGER,
internalSensorText
DisplayString (SIZE (0..20)),
internalSensorStatus
INTEGER,
internalSensorValue
INTEGER,
internalSensorSetHigh
INTEGER,
internalSensorSetLow
INTEGER,
internalSensorSetWarn
INTEGER
}
internalSensorIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of value entries. Its value ranges
between 1 and the value of cpqWcrmInternalNumberOfSensors."
::= { cpqWcrmInternalSensorEntry 1 }
internalSensorType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
access (4),
vibration (5),
motion (6),
smoke (7),
airFlow (8),
type6 (9),
temperature(10),
current4to20(11),
humidity(12),
userNO (13),
userNC (14),
voltOK (17),
voltage (18),
fanOK (19),
leakage (20)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage (OK, NOK)
18: voltage value
19: fan status, from Environmental Controller-FAS-Unit
20: leakage sensor"
::= { cpqWcrmInternalSensorEntry 2 }
internalSensorText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each sensor (entry in the table)"
::= { cpqWcrmInternalSensorEntry 3 }
internalSensorStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
warning(7),
tooLow(8),
tooHigh(9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the sensor"
::= { cpqWcrmInternalSensorEntry 4 }
internalSensorValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value of sensor"
::= { cpqWcrmInternalSensorEntry 5 }
internalSensorSetHigh OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for high setpoint of sensor"
::= { cpqWcrmInternalSensorEntry 6 }
internalSensorSetLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for low setpoint of sensor,
also used as alarm delay"
::= { cpqWcrmInternalSensorEntry 7 }
internalSensorSetWarn OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for warning setpoint of sensor,
also used as fan threshold"
::= { cpqWcrmInternalSensorEntry 8 }
-- table END
-- Outputs
cpqWcrmInternalNumberOfOutputs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of outputs available on internal sensor"
::= { cpqWcrmStatusInternalOutputs 1 }
-- table with entry for each output available on this unit
cpqWcrmInternalOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmInternalOutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of output table"
::= { cpqWcrmStatusInternalOutputs 2 }
cpqWcrmInternalOutputEntry OBJECT-TYPE
SYNTAX CpqWcrmInternalOutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of output table"
INDEX { internalOutputIndex }
::= { cpqWcrmInternalOutputTable 1 }
CpqWcrmInternalOutputEntry ::=
SEQUENCE {
internalOutputIndex
INTEGER,
internalOutputType
INTEGER,
internalOutputText
DisplayString (SIZE (0..20)),
internalOutputStatus
INTEGER,
internalOutputValue
INTEGER,
internalOutputSet
INTEGER,
internalOutputConfig
INTEGER,
internalOutputDelay
INTEGER,
internalOutputTimeoutAction
INTEGER
}
internalOutputIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of output entries. Its value ranges
between 1 and the value of cpqWcrmInternalNumberOfOutputs."
::= { cpqWcrmInternalOutputEntry 1 }
internalOutputType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
universalOut (4),
powerOut(5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of output which is connected to internal sensor to output[internalOutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 6, universal relay output
5: output type 8, power output"
::= { cpqWcrmInternalOutputEntry 2 }
internalOutputText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each output (entry in the table)"
::= { cpqWcrmInternalOutputEntry 3 }
internalOutputStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
setOff(7),
setOn(8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Actual status of the output"
::= { cpqWcrmInternalOutputEntry 4 }
internalOutputValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for output"
::= { cpqWcrmInternalOutputEntry 5 }
internalOutputSet OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
lock (3),
unlock (4),
unlockDelay (5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command for output"
::= { cpqWcrmInternalOutputEntry 6 }
internalOutputConfig OBJECT-TYPE
SYNTAX INTEGER {
disRemote (1),
enRemote (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control "
::= { cpqWcrmInternalOutputEntry 7 }
internalOutputDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unsigned Value for delay,
after this time the output will fall into the previous state"
::= { cpqWcrmInternalOutputEntry 8 }
internalOutputTimeoutAction OBJECT-TYPE
SYNTAX INTEGER {
stay (1),
off (2),
on (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"State for output if timeout (RS422) occurs"
::= { cpqWcrmInternalOutputEntry 9 }
-- Messages
cpqWcrmInternalNumberOfMsgs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of messages that can be created with internal sensor"
::= { cpqWcrmStatusInternalMsg 1 }
-- table with entry for each alarm available on this unit
cpqWcrmInternalMsgTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmInternalMsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of message table"
::= { cpqWcrmStatusInternalMsg 2 }
cpqWcrmInternalMsgEntry OBJECT-TYPE
SYNTAX CpqWcrmInternalMsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of message table"
INDEX { internalMsgIndex }
::= { cpqWcrmInternalMsgTable 1 }
CpqWcrmInternalMsgEntry ::=
SEQUENCE {
internalMsgIndex
INTEGER,
internalMsgText
DisplayString (SIZE (0..20)),
internalMsgStatus
INTEGER,
internalMsgRelay
INTEGER,
internalMsgBeeper
INTEGER,
internalMsgTrap1
INTEGER,
internalMsgTrap2
INTEGER,
internalMsgTrap3
INTEGER,
internalMsgTrap4
INTEGER,
internalMsgReset
INTEGER
}
internalMsgIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of message entries. Its value ranges
between 1 and the value of cpqWcrmInternalNumberOfMsgs."
::= { cpqWcrmInternalMsgEntry 1 }
internalMsgText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each message (entry in the table)"
::= { cpqWcrmInternalMsgEntry 2 }
internalMsgStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
configChanged(2),
error(3),
ok(4),
alarm(5),
warning(6),
tooLow(7),
tooHigh(8),
setOff(9),
setOn(10)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to ON
10: output is set to OFF"
::= { cpqWcrmInternalMsgEntry 3 }
internalMsgRelay OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm relay for this message/alarm
1: no switching of alarm relay
2: switching of alarm relay"
::= { cpqWcrmInternalMsgEntry 4 }
internalMsgBeeper OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm"
::= { cpqWcrmInternalMsgEntry 5 }
internalMsgTrap1 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 1 activated"
::= { cpqWcrmInternalMsgEntry 6 }
internalMsgTrap2 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 2 activated"
::= { cpqWcrmInternalMsgEntry 7 }
internalMsgTrap3 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 3 activated"
::= { cpqWcrmInternalMsgEntry 8 }
internalMsgTrap4 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 4 and Event Logging activated"
::= { cpqWcrmInternalMsgEntry 9 }
internalMsgReset OBJECT-TYPE
SYNTAX INTEGER {
auto (1),
manual (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key"
::= { cpqWcrmInternalMsgEntry 10 }
-- table internal sensors unit END
-- waterCoolUnit
cpqWcrmWaterCoolUnitTypeOfDevice OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
unitWcrm (2),
unitIO (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor unit connected to port 2"
::= { cpqWcrmStatusSensorWaterCoolUnit 1 }
cpqWcrmWaterCoolUnitText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for sensor unit connected to port 2"
::= { cpqWcrmStatusSensorWaterCoolUnit 2 }
cpqWcrmWaterCoolUnitSerial OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Serialnumber of sensor unit connected to port 2"
::= { cpqWcrmStatusSensorWaterCoolUnit 3 }
cpqWcrmWaterCoolUnitStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
error(2),
changed(3),
reset(4),
timeout(5),
detected(6),
notAvail(7),
lowPower(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status sensor unit connected to port 2
(1) OK
(2) error
(3) configuration of sensor unit has changed, confirmation required
(4) reset from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required
(6) sensor unit detected, needs to be confirmed
(8) supply voltage is too low"
::= { cpqWcrmStatusSensorWaterCoolUnit 4 }
-- Water Cool Unit table
-- Sensors
cpqWcrmWaterCoolUnitNumberOfSensors OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors connected to water cool unit"
::= { cpqWcrmStatusWaterCoolUnitSensors 1 }
-- table with entry for each sensor available on this unit
cpqWcrmWaterCoolUnitSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of sensor table"
::= { cpqWcrmStatusWaterCoolUnitSensors 2 }
cpqWcrmWaterCoolUnitSensorEntry OBJECT-TYPE
SYNTAX CpqWcrmWaterCoolUnitSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of sensor table"
INDEX { waterCoolUnitSensorIndex }
::= { cpqWcrmWaterCoolUnitSensorTable 1 }
CpqWcrmWaterCoolUnitSensorEntry ::=
SEQUENCE {
waterCoolUnitSensorIndex
INTEGER,
waterCoolUnitSensorType
INTEGER,
waterCoolUnitSensorText
DisplayString (SIZE (0..20)),
waterCoolUnitSensorStatus
INTEGER,
waterCoolUnitSensorValue
INTEGER,
waterCoolUnitSensorSetHigh
INTEGER,
waterCoolUnitSensorSetLow
INTEGER,
waterCoolUnitSensorSetWarn
INTEGER
}
waterCoolUnitSensorIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of value entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors."
::= { cpqWcrmWaterCoolUnitSensorEntry 1 }
waterCoolUnitSensorType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
tempIn (4),
tempOut (5), -- ()
heatFlow (6),
alarm (7),
warning (8),
rpmFan1 (9),
rpmFan2 (10),
rpmFan3 (11),
fanSpeed (12),
tempIn1 (13),
tempOut1 (14),
tempIn2 (15),
tempOut2 (16),
tempIn3 (17),
tempOut3 (18),
tempWaterIn (19),
tempWaterOut (20),
waterFlow (21),
valve (22), -- (MCS:status of valve: open, closed; MCSS: setpoint valve (%)..)
status (23),
condensateDuration (24),
condensateCycles (25),
rpmFan4 (26),
rpmFan5 (27),
rpmFan6 (28),
transfSwitch(29),
valveActValue(30)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: average temperature of air inlet to rack, average or max/min from each HEX
5: average temperature of air outlet from rack, average or max/min from each HEX
6: heatflow sensor
7: alarm:
Bit 0: Leakage
Bit 1: IIC Failure
8: warning:
Bit 0..2: Fan Tach 1..3
Bit 3,4: Temp. sensor HEX1 In,Out
Bit 5,6: Temp. sensor HEX2 In,Out
Bit 7,8: Temp. sensor HEX3 In,Out
Bit 9: Air temp. sensor
Bit 10..12: IIC failure, HEX1..3
Bit 13: Waterflow low
Bit 14,15: Watertemp. In,Out
Bit 16: Waterflow sensor fail.
Bit 17: Magnetic valve fail.
Bit 18: Leakdetector fail.
Bit 19: Uneven heat load
Bit 20: Condensation Pump Cycles > Max
Bit 21: Condensation Pump Running Time > Max
9: rpm speed of Fan1
10: rpm speed of Fan2
11: rpm speed of Fan3
12: fanSpeed setpoint, calculated from average temperatures
13: temperature air inlet to rack, HEX 1
14: temperature air outlet from rack, HEX 1
15: temperature air inlet to rack, HEX 1
16: temperature air outlet from rack, HEX 1
17: temperature air inlet to rack, HEX 1
18: temperature air outlet from rack, HEX 1
19: water temperature In
20: water temperature Out
21: water Flow
22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%)
23: status: Bit 0..Bit 2: fan module 1..3 available
Bit 3: water module available
24: condensation pump number of seconds on counter (last operating time)
25: condensation pump on/off cycle counter
26: rpm speed of Fan4
27: rpm speed of Fan5
28: rpm speed of Fan6
29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2
30: water valve actual value (%)"
::= { cpqWcrmWaterCoolUnitSensorEntry 2 }
waterCoolUnitSensorText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each sensor (entry in the table)"
::= { cpqWcrmWaterCoolUnitSensorEntry 3 }
waterCoolUnitSensorStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
warning(7),
tooLow(8),
tooHigh(9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the sensor"
::= { cpqWcrmWaterCoolUnitSensorEntry 4 }
waterCoolUnitSensorValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)
If msg index = 1, 5 or 6
This value represents the actual Server Intake Temperature.
If msg index = 2:
This value represents the bit coded warning condition
Bit 0: Top Fan Module Failed
Bit 1: Middle Fan Module Failed
Bit 2: Bottom Fan Module Failed
Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed
Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed
Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed
Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed
Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed
Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed
Bit 9: Air Temperature Sensor Failed
Bit 10: Top Fan not installed
Bit 11: Middle Fan not installed
Bit 12: Bottom Fan not installed
Bit 13: Waterflow low
Bit 14: Water Unit Temperature Input Out of Range
Bit 15: Water Unit Temperature Output Out of Range
Bit 16: Waterflow Sensor Value Out of Range
Bit 17: Water Valve Failed
Bit 18: Leakdetector Failed
Bit 19: Heat Load Warning
Bit 20: The Condensation Pump has exceeded the max. number of cycles
Bit 21: The Condensation Pump has exceeded the max. Running Time
If msg index = 3:
This value represents the bit coded alarm condition
Bit 0: Leakage Detected
Bit 1: Comm. Failure IIC"
::= { cpqWcrmWaterCoolUnitSensorEntry 5 }
waterCoolUnitSensorSetHigh OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for high setpoint of sensor"
::= { cpqWcrmWaterCoolUnitSensorEntry 6 }
waterCoolUnitSensorSetLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for low setpoint of sensor,
also used as alarm delay"
::= { cpqWcrmWaterCoolUnitSensorEntry 7 }
waterCoolUnitSensorSetWarn OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for warning setpoint of sensor,
also used as fan threshold"
::= { cpqWcrmWaterCoolUnitSensorEntry 8 }
-- table END
-- Outputs
cpqWcrmWaterCoolUnitNumberOfOutputs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of outputs available on sensor water cool unit"
::= { cpqWcrmStatusWaterCoolUnitOutputs 1 }
-- table with entry for each output available on this unit
cpqWcrmWaterCoolUnitOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitOutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of output table"
::= { cpqWcrmStatusWaterCoolUnitOutputs 2 }
cpqWcrmWaterCoolUnitOutputEntry OBJECT-TYPE
SYNTAX CpqWcrmWaterCoolUnitOutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of output table"
INDEX { waterCoolUnitOutputIndex }
::= { cpqWcrmWaterCoolUnitOutputTable 1 }
CpqWcrmWaterCoolUnitOutputEntry ::=
SEQUENCE {
waterCoolUnitOutputIndex
INTEGER,
waterCoolUnitOutputType
INTEGER,
waterCoolUnitOutputText
DisplayString (SIZE (0..20)),
waterCoolUnitOutputStatus
INTEGER,
waterCoolUnitOutputValue
INTEGER,
waterCoolUnitOutputSet
INTEGER,
waterCoolUnitOutputConfig
INTEGER,
waterCoolUnitOutputDelay
INTEGER,
waterCoolUnitOutputTimeoutAction
INTEGER
}
waterCoolUnitOutputIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of output entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs."
::= { cpqWcrmWaterCoolUnitOutputEntry 1 }
waterCoolUnitOutputType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
setpoint (4),
hysteresis (5),
command (6),
controlMode (7),
fanSpeedMin (8),
dTmin (9),
dTmax(10),
cpWatert(11),
setHeatload(12),
setEdoFlow(13),
setEdoHeat(14),
setCondCycles(15),
setCondRun(16),
doorControl(17),
pidContrKP(18),
pidContrKI(19),
pidContrKD(20),
pidSampleTime(21)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex]
1: no output connected
2: output failure
3: value overflow
4: water valve setpoint
5: water valve hysteresis
6: command for manual control
7: Flow Meter Model, 0=SIKA, 1=Chemline
8: minimum fan speed
9: min delta T, used for fan control
10: max delta T, used for fan control
11: specific heat capacity
12: setpoint heatload warning
13: setpoint Water Flow Loss Emergency Door Opening
14: setpoint High Temperature Emergency Door Opening
15: setpoint Condensation Pump Cycles (Warning)
16: setpoint Condensation Pump Running Time (Warning)
17: command for door opening, 0=lock door, 1=unlock door
18: KP parameter for PID controller
19: KI parameter for PID controller
20: KD parameter for PID controller
21: sampling time PID controller"
::= { cpqWcrmWaterCoolUnitOutputEntry 2 }
waterCoolUnitOutputText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each output (entry in the table)"
::= { cpqWcrmWaterCoolUnitOutputEntry 3 }
waterCoolUnitOutputStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
setOff(7),
setOn(8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Actual status of the output"
::= { cpqWcrmWaterCoolUnitOutputEntry 4 }
waterCoolUnitOutputValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Signed value for output"
::= { cpqWcrmWaterCoolUnitOutputEntry 5 }
waterCoolUnitOutputSet OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
lock (3),
unlock (4),
unlockDelay (5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command for output"
::= { cpqWcrmWaterCoolUnitOutputEntry 6 }
waterCoolUnitOutputConfig OBJECT-TYPE
SYNTAX INTEGER {
disRemote (1),
enRemote (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control "
::= { cpqWcrmWaterCoolUnitOutputEntry 7 }
waterCoolUnitOutputDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unsigned Value for delay,
after this time the output will fall into the previous state"
::= { cpqWcrmWaterCoolUnitOutputEntry 8 }
waterCoolUnitOutputTimeoutAction OBJECT-TYPE
SYNTAX INTEGER {
stay (1),
off (2),
on (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"State for output if timeout (RS422) occurs"
::= { cpqWcrmWaterCoolUnitOutputEntry 9 }
-- Alarms
cpqWcrmWaterCoolUnitNumberOfMsgs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of alarms that can be created with water cool unit"
::= { cpqWcrmStatusWaterCoolUnitMsg 1 }
-- table with entry for each alarm available on this unit
cpqWcrmWaterCoolUnitMsgTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitMsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of message table"
::= { cpqWcrmStatusWaterCoolUnitMsg 2 }
cpqWcrmWaterCoolUnitMsgEntry OBJECT-TYPE
SYNTAX CpqWcrmWaterCoolUnitMsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of message table"
INDEX { waterCoolUnitMsgIndex }
::= { cpqWcrmWaterCoolUnitMsgTable 1 }
CpqWcrmWaterCoolUnitMsgEntry ::=
SEQUENCE {
waterCoolUnitMsgIndex
INTEGER,
waterCoolUnitMsgText
DisplayString (SIZE (0..20)),
waterCoolUnitMsgStatus
INTEGER,
waterCoolUnitMsgRelay
INTEGER,
waterCoolUnitMsgBeeper
INTEGER,
waterCoolUnitMsgTrap1
INTEGER,
waterCoolUnitMsgTrap2
INTEGER,
waterCoolUnitMsgTrap3
INTEGER,
waterCoolUnitMsgTrap4
INTEGER,
waterCoolUnitMsgReset
INTEGER
}
waterCoolUnitMsgIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of alarm entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs."
::= { cpqWcrmWaterCoolUnitMsgEntry 1 }
waterCoolUnitMsgText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each message (entry in the table)"
::= { cpqWcrmWaterCoolUnitMsgEntry 2 }
waterCoolUnitMsgStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
configChanged(2),
error(3),
ok(4),
alarm(5),
warning(6),
tooLow(7),
tooHigh(8),
setOff(9),
setOn(10)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual message status
4: OK
5: alarm
6: warning
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold"
::= { cpqWcrmWaterCoolUnitMsgEntry 3 }
waterCoolUnitMsgRelay OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm relay for this alarm
2: no switching of alarm relay
1: switching of alarm relay"
::= { cpqWcrmWaterCoolUnitMsgEntry 4 }
waterCoolUnitMsgBeeper OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm beeper for this alarm
2: no audible alarm
1: audible alarm"
::= { cpqWcrmWaterCoolUnitMsgEntry 5 }
waterCoolUnitMsgTrap1 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 1 activated"
::= { cpqWcrmWaterCoolUnitMsgEntry 6 }
waterCoolUnitMsgTrap2 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 2 activated"
::= { cpqWcrmWaterCoolUnitMsgEntry 7 }
waterCoolUnitMsgTrap3 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 3 activated"
::= { cpqWcrmWaterCoolUnitMsgEntry 8 }
waterCoolUnitMsgTrap4 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 4 and Event Logging activated"
::= { cpqWcrmWaterCoolUnitMsgEntry 9 }
waterCoolUnitMsgReset OBJECT-TYPE
SYNTAX INTEGER {
auto (1),
manual (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key"
::= { cpqWcrmWaterCoolUnitMsgEntry 10 }
-- table END
--setupGeneral-group
cpqWcrmSetTempUnit OBJECT-TYPE
SYNTAX INTEGER {
celsius(1),
fahrenheit(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unit of all temperature values and setpoints, Celsius or Fahrenheit"
::= { cpqWcrmSetupGeneral 1 }
cpqWcrmSetBeeper OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Audible alarm in Environmental Controller unit:
(2): beeper is on
(1): beeper is off (general)"
::= { cpqWcrmSetupGeneral 2 }
cpqWcrmResetRelay OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable acknowledging currently active alarm relay
(with 'C' on Environmental Controller)."
::= { cpqWcrmSetupGeneral 3 }
cpqWcrmLogicRelay OBJECT-TYPE
SYNTAX INTEGER {
closeAtAlarm(1),
openAtAlarm(2),
off(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Logic of alarm relay:
(1) Relay will pick up in case of an alarm
(2) Relay will release in case of an alarm
(3) Relay off (general)"
::= { cpqWcrmSetupGeneral 4 }
cpqWcrmWebAccess OBJECT-TYPE
SYNTAX INTEGER {
viewOnly(1),
fullAccess(2),
off(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Web access via HTTP:
(1) view only
(2) full Access, read and set
(3) Web disabled (general)"
::= { cpqWcrmSetupGeneral 5 }
-- SetupClock
cpqWcrmSetupDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"actual Date in format DD.MM.YYYY"
::= { cpqWcrmSetupGeneral 6 }
cpqWcrmSetupTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)"
::= { cpqWcrmSetupGeneral 7 }
-- table for timer function
cpqWcrmTimerNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of value-table entries=number of outlets available on this unit"
::= { cpqWcrmTimerTable1 1 }
cpqWcrmTimerTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmTimerEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of status-table"
::= { cpqWcrmTimerTable1 2 }
cpqWcrmTimerEntry OBJECT-TYPE
SYNTAX CpqWcrmTimerEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of timer-table"
INDEX { cpqWcrmTimerIndex }
::= { cpqWcrmTimerTable 1 }
CpqWcrmTimerEntry ::=
SEQUENCE {
cpqWcrmTimerIndex
INTEGER,
cpqWcrmTimerStatus
INTEGER,
cpqWcrmTimerDayOfWeek
INTEGER,
cpqWcrmTimeOn
DisplayString (SIZE (0..5)),
cpqWcrmTimeOff
DisplayString (SIZE (0..5)),
cpqWcrmTimeControl
INTEGER,
cpqWcrmTimerFunction
INTEGER
}
cpqWcrmTimerIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of timer entries. Its value ranges
between 1 and the value of cpqWcrmTimerNumber."
::= { cpqWcrmTimerEntry 1 }
cpqWcrmTimerStatus OBJECT-TYPE
SYNTAX INTEGER {
switchedOff(1),
switchedOn(2),
noTime(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the timer"
::= { cpqWcrmTimerEntry 2 }
cpqWcrmTimerDayOfWeek OBJECT-TYPE
SYNTAX INTEGER {
sun(1),
mon(2),
tue(3) ,
wed(4),
thu(5),
fri(6),
sat(7),
sat-sun(8),
mon-fri(9),
mon-sun(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of day of week for timer to switch"
::= { cpqWcrmTimerEntry 3 }
cpqWcrmTimeOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..5))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time to switch on current function,
Format: HH:MM"
::= { cpqWcrmTimerEntry 4 }
cpqWcrmTimeOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..5))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time to switch off current function,
Format: HH:MM"
::= { cpqWcrmTimerEntry 5 }
cpqWcrmTimeControl OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Control via RTC"
::= { cpqWcrmTimerEntry 6 }
cpqWcrmTimerFunction OBJECT-TYPE
SYNTAX INTEGER {
disTrapRec1 (1),
disTrapRec2 (2),
disTrapRec3 (3),
disTrapRec4 (4),
schedule1 (5),
schedule2 (6),
schedule3 (7),
schedule4 (8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Function which is controlled via timer
1-4: sending Traps to this Trap receiver will be disabled
5 - 8: scheduled alarm off"
::= { cpqWcrmTimerEntry 7 }
-- added Oct 27, 2006
cpqWcrmSetFlowUnit OBJECT-TYPE
SYNTAX INTEGER {
literMin(1),
gallonMin(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unit of Water Flow, Liter/min or Gallon/min"
::= { cpqWcrmSetupGeneral 9 }
-- added
--cpqWcrmTrapTable-group
cpqWcrmTraptableNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of trapTable entries. The number of trap-receiver"
::= { cpqWcrmTraps 1 }
cpqWcrmTrapTableTable OBJECT-TYPE
SYNTAX SEQUENCE OF CpqWcrmTrapTableEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of trap-receiver entries"
::= { cpqWcrmTraps 2 }
cpqWcrmTrapTableEntry OBJECT-TYPE
SYNTAX CpqWcrmTrapTableEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of trapTable"
INDEX { trapIndex }
::= { cpqWcrmTrapTableTable 1 }
CpqWcrmTrapTableEntry ::=
SEQUENCE {
trapIndex
INTEGER,
trapStatus
INTEGER,
trapIPaddress
DisplayString
}
trapIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the trap-receiver-table. Its value ranges between
1 and the value of traptableNumber "
::= { cpqWcrmTrapTableEntry 1 }
trapStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable trap receiver"
::= { cpqWcrmTrapTableEntry 2 }
trapIPaddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-address of trap-receiver"
::= { cpqWcrmTrapTableEntry 3 }
--cpqWcrmControl-group (Added in Version 1.1)
cpqWcrmResetUnit OBJECT-TYPE
SYNTAX INTEGER {
noReset(1),
reset(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command to reset (acknowledge) alarms of Environmental Controller unit.
Setting to 'reset' (2) will have same result as pressing 'C' on Units.
Variable is automatically set back to 'noReset' (1)."
::= { cpqWcrmControl 1 }
--Traps
alarmSensorInternal TRAP-TYPE
ENTERPRISE cpqWcrm
VARIABLES { sysContact, sysName, sysLocation,
internalMsgIndex, internalMsgText, internalMsgStatus, internalSensorValue, cpqWcrmURL }
DESCRIPTION
"Internal Sensor Alarm"
--
--#TYPE "Internal sensor alarm"
--#SUMMARY "Location: %s, Alarm[%d]: %s, Status: %d, Actual Value: %d, from: %s, contact %s, URL %s"
--#ARGUMENTS { 2, 3, 4, 5, 6, 1, 0, 7}
--#SEVERITY MAJOR
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
--#TIMEINDEX 99
--
::= 1
alarmSensorWaterCoolUnit TRAP-TYPE
ENTERPRISE cpqWcrm
VARIABLES { sysContact, sysName, sysLocation,
waterCoolUnitMsgIndex, waterCoolUnitMsgText, waterCoolUnitMsgStatus, waterCoolUnitSensorValue, cpqWcrmURL }
DESCRIPTION
"Water Cool Unit Sensor Alarm"
--
--#TYPE "Water cool unit sensor alarm"
--#SUMMARY "Location: %s, Alarm[%d]: %s, Status: %d, Actual Value: %d, from: %s, contact %s, URL %s"
--#ARGUMENTS { 2, 3, 4, 5, 6, 1, 0, 7}
--#SEVERITY MAJOR
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
--#TIMEINDEX 99
--
::= 2
alarmInternal TRAP-TYPE
ENTERPRISE cpqWcrm
VARIABLES { sysContact, sysName, sysLocation,
cpqWcrmInternalText, cpqWcrmInternalStatus, cpqWcrmURL }
DESCRIPTION
"Internal Unit Alarm"
--
--#TYPE "Internal unit alarm"
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s, URL %s"
--#ARGUMENTS { 2, 3, 1, 0, 5}
--#SEVERITY MAJOR
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
--#TIMEINDEX 99
--
::= 5
alarmWaterCoolUnit TRAP-TYPE
ENTERPRISE cpqWcrm
VARIABLES { sysContact, sysName, sysLocation,
cpqWcrmWaterCoolUnitText, cpqWcrmWaterCoolUnitStatus, cpqWcrmURL }
DESCRIPTION
"Water Cool Unit System Alarm"
--
--#TYPE "Water cool unit alarm"
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s, URL %s"
--#ARGUMENTS { 2, 3, 1, 0, 5}
--#SEVERITY MAJOR
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
--#TIMEINDEX 99
--
::= 6
testTrap TRAP-TYPE
ENTERPRISE cpqWcrm
VARIABLES { sysContact, sysName, sysLocation, cpqWcrmURL }
DESCRIPTION
"Test trap sent to a trap receiver to check proper reception of traps"
--
--#TYPE "Test Trap"
--#SUMMARY "Location: %s, Test Trap from unit %s was sent, contact %s, URL %s"
--#ARGUMENTS { 2, 1, 0, 3}
--#SEVERITY INFORMATIONAL
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
--#TIMEINDEX 99
--
::= 10
END