-- Water Cooled Rack Monitor - (WCRM) MIB
|
|
-- Management Information Base for SNMP Network Management
|
|
--
|
|
-- *********************************************************************
|
|
-- Release History
|
|
-- Date: August 1, 2005 (Version 1.0)
|
|
-- Revised by Charles Cochran - Initial release
|
|
-- Date: December 12, 2006 (Version 1.1)
|
|
-- Changes: Added MIB-Variable for Waterflow Unit (liter/min or gallon/min),
|
|
-- Added Emergency Door Opening (EDO) Thresholds to waterCoolUnitOutputType
|
|
-- Added EDO description to MsgStatus
|
|
-- Added Condensation Pump Running Time and Cycles Thresholds to waterCoolUnitOutputType
|
|
-- Date: July 30, 2007 (Version 1.2)
|
|
-- Changes: Added new 'waterCoolUnitSensorType' for MCSS
|
|
-- Addes new 'waterCoolUnitOutputType' for MCSS
|
|
--
|
|
-- Copyright 2005-2008 Hewlett-Packard Development Company, L.P.
|
|
--
|
|
-- Hewlett-Packard Company shall not be liable for technical or
|
|
-- editorial errors or omissions contained herein. The information in
|
|
-- this document is provided "as is" without warranty of any kind and
|
|
-- is subject to change without notice. The warranties for HP products
|
|
-- are set forth in the express limited warranty statements
|
|
-- accompanying such products. Nothing herein should be construed as
|
|
-- constituting an additional warranty.
|
|
--
|
|
-- Confidential computer software. Valid license from HP required for
|
|
-- possession, use or copying. Consistent with FAR 12.211 and 12.212,
|
|
-- Commercial Computer Software, Computer Software Documentation, and
|
|
-- Technical Data for Commercial Items are licensed to the U.S.
|
|
-- Government under vendor's standard commercial license.
|
|
--
|
|
-- Refer to the READMIB.RDM file for more information about the
|
|
-- organization of the information in the Compaq Enterprise.
|
|
--
|
|
-- The Compaq Enterprise number is 232.
|
|
-- The ASN.1 prefix to, and including the Compaq Enterprise is:
|
|
-- 1.3.6.1.4.1.232
|
|
--
|
|
-- *********************************************************************
|
|
|
|
-- VARIABLES REQUIRED FOR HP MANAGEMENT
|
|
-- ===================================================================================
|
|
-- cpqSiProductName (1.3.6.1.4.1.232.2.2.4.2) which is defined in CPQSINFO.MIB.
|
|
-- This is the product model name
|
|
--
|
|
-- cpqSiProductName OBJECT-TYPE
|
|
-- SYNTAX DisplayString (SIZE (0..255))
|
|
-- ACCESS read-only
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "This device product name."
|
|
-- ::= { cpqSiSystemBoard 2 }
|
|
-- ===================================================================================
|
|
--
|
|
-- ===================================================================================
|
|
-- cpqHoGUID (1.3.6.1.4.1.232.11.2.10.3) which is defined in CPQHOST.MIB
|
|
-- This field needs to be filled
|
|
-- with the unique serial number (16 bytes)
|
|
--
|
|
-- cpqHoGUID OBJECT-TYPE
|
|
-- SYNTAX OCTET STRING (SIZE (16))
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The globally unique identifier of this device."
|
|
--
|
|
-- ::= { cpqHoSystemStatus 3 }
|
|
-- ====================================================================================
|
|
--
|
|
-- ====================================================================================
|
|
-- cpqHoMibStatusArray (1.3.6.1.4.1.232.11.2.10.1) which is defined in CPQHOST.MIB
|
|
-- Pretty complicated to decipher if you do not have the guide. We only use the first
|
|
-- 4 octets.
|
|
--
|
|
-- Octet 0 = 00000001 (always)
|
|
-- Octet 1 = 00000000 through 00000100 depending on Device H/W Condition below
|
|
-- Octet 2 = 00000001 (always)
|
|
-- Octet 3 = 00010000 (always decimal 16 see table below)
|
|
--
|
|
-- For example: With a device with OK status, the values of the 4 octets would be:
|
|
--
|
|
-- Octet 0 = 0x01 (fixed)
|
|
-- Octet 1 = 0x02 (OK overall status)
|
|
-- Octet 2 = 0x01 (fixed)
|
|
-- Octet 3 = 0x12 (Device type = 18 for Environmental Monitor)
|
|
--
|
|
-- cpqHoMibStatusArray OBJECT-TYPE
|
|
-- SYNTAX OCTET STRING (SIZE (4..256))
|
|
-- ACCESS read-only
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The MIB Status Array is an array of MIB status structures. Each
|
|
-- structure is made up of 4 octets.
|
|
--
|
|
-- Array element 0 is the status for all MIBs in the Compaq
|
|
-- Enterprise.
|
|
--
|
|
-- Device H/W Condition (Octet 1)
|
|
-- 0 - Not available (e.g. Loss/lack of communication between card and device)
|
|
-- 1 - Other (unknown) (mapped to device unknown status)
|
|
-- 2 - OK (mapped to device normal status/events)
|
|
-- 3 - Degraded (device warning status/events
|
|
-- 4 - Failed (device critical status/events
|
|
--
|
|
-- Detailed Type (octet 3)
|
|
-- Bits 0-7 Detailed Type, only used if bit 0 in octect 2 is 1.
|
|
--
|
|
-- Type Values for Bits 0-4 (maps to CIM7 types)
|
|
-- Unknown = 0
|
|
-- Server = 1 (yes a duplicate of the server flag)
|
|
-- Desktop = 2
|
|
-- Workstation = 3
|
|
-- Portable = 4
|
|
-- Router = 5
|
|
-- Cluster = 6
|
|
-- Printer = 7
|
|
-- Switch = 8 (network switch)
|
|
-- Repeater = 9
|
|
-- Remote Access Device = 10
|
|
-- Other = 11
|
|
-- Management Processor = 12 (rib, RILOE, iLo)
|
|
-- Rack = 13
|
|
-- Enclosure = 14
|
|
-- KVM Switch = 15 (IP enabled keyboard video mouse switch).
|
|
-- UPS = 16
|
|
-- Power Distribution Unit = 17
|
|
-- Environmental Monitor = 18 (eg Environmental Controller)"
|
|
--
|
|
-- ::= { cpqHoSystemStatus 1 }
|
|
-- ===============================================================================
|
|
|
|
CPQWCRM-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
compaq FROM CPQHOST-MIB
|
|
OBJECT-TYPE FROM RFC-1212
|
|
DisplayString FROM RFC1213-MIB
|
|
sysName FROM RFC1213-MIB
|
|
sysDescr FROM RFC1213-MIB
|
|
sysContact FROM RFC1213-MIB
|
|
sysLocation FROM RFC1213-MIB
|
|
TRAP-TYPE FROM RFC-1215;
|
|
|
|
-- Note: uncomment the following "compaq OBJECT IDENTIFIER" and "enterprises" lines then
|
|
-- comment out "compaq FROM CPQHOST-MIB" above to compile without the CPQHOST-MIB
|
|
-- enterprises FROM RFC1155-SMI
|
|
-- compaq OBJECT IDENTIFIER ::= { enterprises 232 }
|
|
|
|
cpqWcrm OBJECT IDENTIFIER ::= { compaq 167 }
|
|
cpqWcrmMibRev OBJECT IDENTIFIER ::= { cpqWcrm 1 }
|
|
cpqWcrmStatus OBJECT IDENTIFIER ::= { cpqWcrm 2 }
|
|
cpqWcrmStatusSensorInternal OBJECT IDENTIFIER ::= { cpqWcrmStatus 3 }
|
|
cpqWcrmStatusInternalSensors OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 5 }
|
|
cpqWcrmStatusInternalOutputs OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 6 }
|
|
cpqWcrmStatusInternalMsg OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 7 }
|
|
cpqWcrmStatusSensorWaterCoolUnit OBJECT IDENTIFIER ::= { cpqWcrmStatus 4 }
|
|
cpqWcrmStatusWaterCoolUnitSensors OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 5 }
|
|
cpqWcrmStatusWaterCoolUnitOutputs OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 6 }
|
|
cpqWcrmStatusWaterCoolUnitMsg OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 7 }
|
|
cpqWcrmSetup OBJECT IDENTIFIER ::= { cpqWcrm 3 }
|
|
cpqWcrmSetupGeneral OBJECT IDENTIFIER ::= { cpqWcrmSetup 1 }
|
|
cpqWcrmTimerTable1 OBJECT IDENTIFIER ::= { cpqWcrmSetupGeneral 8 }
|
|
cpqWcrmTrapControl OBJECT IDENTIFIER ::= { cpqWcrm 4 }
|
|
cpqWcrmTraps OBJECT IDENTIFIER ::= { cpqWcrmTrapControl 7 }
|
|
cpqWcrmControl OBJECT IDENTIFIER ::= { cpqWcrm 5 }
|
|
|
|
|
|
--*****************************************************************************
|
|
-- HP Modular Control System Environmental Controller
|
|
--*****************************************************************************
|
|
--cpqWcrmMibRev-group
|
|
|
|
cpqWcrmMibMajRev OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Major Revision level.
|
|
A change in the major revision level represents a major change
|
|
in the architecture of the MIB. A change in the major revision
|
|
level may indicate a significant change in the information,
|
|
correct interpretation of data may require a MIB document
|
|
with the same major revision level."
|
|
::= { cpqWcrmMibRev 1 }
|
|
|
|
cpqWcrmMibMinRev OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Minor Revision level.
|
|
A change in the minor revision level may represent some minor
|
|
additional support, no changes to any pre-existing information
|
|
has occurred."
|
|
::= { cpqWcrmMibRev 2 }
|
|
|
|
cpqWcrmMibCondition OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other (1),
|
|
ok (2),
|
|
degraded (3),
|
|
failed (4),
|
|
configChanged (5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The overall condition (status) of the system represented by
|
|
this MIB.
|
|
(2) OK
|
|
(3) a minor problem, warning condition (yellow LED on Environmental Controller)
|
|
(4) a major problem (red LED on Environmental Controller)
|
|
(5) configuration of sensor units changed or
|
|
unit detected (red/yellow/green LED on Environmental Controller)"
|
|
::= { cpqWcrmMibRev 3 }
|
|
|
|
|
|
|
|
--status-group
|
|
cpqWcrmStatusDeviceEnvironmentalController OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
failed(1),
|
|
ok(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"General Status of Environmental Controller unit itself
|
|
(1) failed
|
|
(2) OK"
|
|
::= { cpqWcrmStatus 1 }
|
|
|
|
cpqWcrmUnitsConnected OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of sensor units connected to the Environmental Controller, Port 1 to 2"
|
|
::= { cpqWcrmStatus 2 }
|
|
|
|
cpqWcrmURL OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..80))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"URL of the management interface in the format http[s]://ipaddr[:port#][/page]"
|
|
::= { cpqWcrmStatus 7 }
|
|
|
|
|
|
--status sensor units-group
|
|
|
|
--unit 1
|
|
cpqWcrmInternalTypeOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail (1),
|
|
unitWcrm (2),
|
|
unitIO (3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of sensor unit connected to port 1"
|
|
::= { cpqWcrmStatusSensorInternal 1 }
|
|
|
|
cpqWcrmInternalText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for sensor unit connected to port 1"
|
|
::= { cpqWcrmStatusSensorInternal 2 }
|
|
|
|
cpqWcrmInternalSerial OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Serialnumber of sensor unit connected to port 1"
|
|
::= { cpqWcrmStatusSensorInternal 3 }
|
|
|
|
cpqWcrmInternalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
error(2),
|
|
changed(3),
|
|
reset(4),
|
|
timeout(5),
|
|
detected(6),
|
|
notAvail(7),
|
|
lowPower(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"General Status sensor unit connected to port 1
|
|
(1) OK
|
|
(2) error, e. g. value overflow
|
|
(3) configuration of sensor unit has changed, confirmation required
|
|
(4) reset from sensor unit to confirm configuration changes
|
|
(5) timeout of sensor unit, confirmation required to unload this unit
|
|
(6) sensor unit detected, needs to be confirmed
|
|
(7) unit is not available
|
|
(8) supply voltage is too low"
|
|
::= { cpqWcrmStatusSensorInternal 4 }
|
|
|
|
-- Sensors
|
|
cpqWcrmInternalNumberOfSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of sensors connected to sensor unit 1"
|
|
::= { cpqWcrmStatusInternalSensors 1 }
|
|
|
|
-- table with entry for each sensor available on this unit
|
|
cpqWcrmInternalSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmInternalSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Headline of sensor table"
|
|
::= { cpqWcrmStatusInternalSensors 2 }
|
|
|
|
cpqWcrmInternalSensorEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmInternalSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of sensor table"
|
|
INDEX { internalSensorIndex }
|
|
::= { cpqWcrmInternalSensorTable 1 }
|
|
|
|
CpqWcrmInternalSensorEntry ::=
|
|
SEQUENCE {
|
|
internalSensorIndex
|
|
INTEGER,
|
|
internalSensorType
|
|
INTEGER,
|
|
internalSensorText
|
|
DisplayString (SIZE (0..20)),
|
|
internalSensorStatus
|
|
INTEGER,
|
|
internalSensorValue
|
|
INTEGER,
|
|
internalSensorSetHigh
|
|
INTEGER,
|
|
internalSensorSetLow
|
|
INTEGER,
|
|
internalSensorSetWarn
|
|
INTEGER
|
|
}
|
|
|
|
internalSensorIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the list of value entries. Its value ranges
|
|
between 1 and the value of cpqWcrmInternalNumberOfSensors."
|
|
::= { cpqWcrmInternalSensorEntry 1 }
|
|
|
|
internalSensorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail (1),
|
|
failure (2),
|
|
overflow (3),
|
|
access (4),
|
|
vibration (5),
|
|
motion (6),
|
|
smoke (7),
|
|
airFlow (8),
|
|
type6 (9),
|
|
temperature(10),
|
|
current4to20(11),
|
|
humidity(12),
|
|
userNO (13),
|
|
userNC (14),
|
|
voltOK (17),
|
|
voltage (18),
|
|
fanOK (19),
|
|
leakage (20)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
|
|
1: no sensor connected
|
|
2: sensor failure
|
|
3: value overflow
|
|
4: sensor type 1, access sensor
|
|
5: sensor type 2, vibration sensor
|
|
6: sensor type 3, motion sensor
|
|
7: sensor type 4, smoke sensor
|
|
8: sensor type 5, air flow sensor
|
|
9: sensor type 6, reserved
|
|
10: sensor type 7, temperature sensor
|
|
11: sensor type 8, 4..20mA sensor
|
|
12: sensor type 9, humidity sensor
|
|
13: user sensor with normally opened contact
|
|
14: user sensor with normally closed contact
|
|
15: door locked sensor from locking device
|
|
16: remote unlock sensor (e.g. external keypad)
|
|
17: voltage sensor, indicates status of main voltage (OK, NOK)
|
|
18: voltage value
|
|
19: fan status, from Environmental Controller-FAS-Unit
|
|
20: leakage sensor"
|
|
::= { cpqWcrmInternalSensorEntry 2 }
|
|
|
|
|
|
internalSensorText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for each sensor (entry in the table)"
|
|
::= { cpqWcrmInternalSensorEntry 3 }
|
|
|
|
internalSensorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
warning(7),
|
|
tooLow(8),
|
|
tooHigh(9)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Actual status of the sensor"
|
|
::= { cpqWcrmInternalSensorEntry 4 }
|
|
|
|
internalSensorValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value of sensor"
|
|
::= { cpqWcrmInternalSensorEntry 5 }
|
|
|
|
internalSensorSetHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value for high setpoint of sensor"
|
|
::= { cpqWcrmInternalSensorEntry 6 }
|
|
|
|
internalSensorSetLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value for low setpoint of sensor,
|
|
also used as alarm delay"
|
|
::= { cpqWcrmInternalSensorEntry 7 }
|
|
|
|
internalSensorSetWarn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value for warning setpoint of sensor,
|
|
also used as fan threshold"
|
|
::= { cpqWcrmInternalSensorEntry 8 }
|
|
|
|
|
|
-- table END
|
|
|
|
-- Outputs
|
|
cpqWcrmInternalNumberOfOutputs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outputs available on internal sensor"
|
|
::= { cpqWcrmStatusInternalOutputs 1 }
|
|
|
|
-- table with entry for each output available on this unit
|
|
|
|
cpqWcrmInternalOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmInternalOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Headline of output table"
|
|
::= { cpqWcrmStatusInternalOutputs 2 }
|
|
|
|
cpqWcrmInternalOutputEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmInternalOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of output table"
|
|
INDEX { internalOutputIndex }
|
|
::= { cpqWcrmInternalOutputTable 1 }
|
|
|
|
CpqWcrmInternalOutputEntry ::=
|
|
SEQUENCE {
|
|
internalOutputIndex
|
|
INTEGER,
|
|
internalOutputType
|
|
INTEGER,
|
|
internalOutputText
|
|
DisplayString (SIZE (0..20)),
|
|
internalOutputStatus
|
|
INTEGER,
|
|
internalOutputValue
|
|
INTEGER,
|
|
internalOutputSet
|
|
INTEGER,
|
|
internalOutputConfig
|
|
INTEGER,
|
|
internalOutputDelay
|
|
INTEGER,
|
|
internalOutputTimeoutAction
|
|
INTEGER
|
|
}
|
|
|
|
internalOutputIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the list of output entries. Its value ranges
|
|
between 1 and the value of cpqWcrmInternalNumberOfOutputs."
|
|
::= { cpqWcrmInternalOutputEntry 1 }
|
|
|
|
internalOutputType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail (1),
|
|
failure (2),
|
|
overflow (3),
|
|
universalOut (4),
|
|
powerOut(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of output which is connected to internal sensor to output[internalOutputIndex]
|
|
1: no output connected
|
|
2: output failure
|
|
3: value overflow
|
|
4: output type 6, universal relay output
|
|
5: output type 8, power output"
|
|
::= { cpqWcrmInternalOutputEntry 2 }
|
|
|
|
|
|
internalOutputText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for each output (entry in the table)"
|
|
::= { cpqWcrmInternalOutputEntry 3 }
|
|
|
|
internalOutputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
setOff(7),
|
|
setOn(8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Actual status of the output"
|
|
::= { cpqWcrmInternalOutputEntry 4 }
|
|
|
|
internalOutputValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value for output"
|
|
::= { cpqWcrmInternalOutputEntry 5 }
|
|
|
|
internalOutputSet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (1),
|
|
on (2),
|
|
lock (3),
|
|
unlock (4),
|
|
unlockDelay (5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Command for output"
|
|
::= { cpqWcrmInternalOutputEntry 6 }
|
|
|
|
internalOutputConfig OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disRemote (1),
|
|
enRemote (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Configuration for output
|
|
1: disable remote control (e.g. keypad)
|
|
2: enable remote control "
|
|
::= { cpqWcrmInternalOutputEntry 7 }
|
|
|
|
internalOutputDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Unsigned Value for delay,
|
|
after this time the output will fall into the previous state"
|
|
::= { cpqWcrmInternalOutputEntry 8 }
|
|
|
|
internalOutputTimeoutAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
stay (1),
|
|
off (2),
|
|
on (3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"State for output if timeout (RS422) occurs"
|
|
::= { cpqWcrmInternalOutputEntry 9 }
|
|
|
|
|
|
-- Messages
|
|
|
|
cpqWcrmInternalNumberOfMsgs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of messages that can be created with internal sensor"
|
|
::= { cpqWcrmStatusInternalMsg 1 }
|
|
|
|
-- table with entry for each alarm available on this unit
|
|
|
|
cpqWcrmInternalMsgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmInternalMsgEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Headline of message table"
|
|
::= { cpqWcrmStatusInternalMsg 2 }
|
|
|
|
cpqWcrmInternalMsgEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmInternalMsgEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of message table"
|
|
INDEX { internalMsgIndex }
|
|
::= { cpqWcrmInternalMsgTable 1 }
|
|
|
|
CpqWcrmInternalMsgEntry ::=
|
|
SEQUENCE {
|
|
internalMsgIndex
|
|
INTEGER,
|
|
internalMsgText
|
|
DisplayString (SIZE (0..20)),
|
|
internalMsgStatus
|
|
INTEGER,
|
|
internalMsgRelay
|
|
INTEGER,
|
|
internalMsgBeeper
|
|
INTEGER,
|
|
internalMsgTrap1
|
|
INTEGER,
|
|
internalMsgTrap2
|
|
INTEGER,
|
|
internalMsgTrap3
|
|
INTEGER,
|
|
internalMsgTrap4
|
|
INTEGER,
|
|
internalMsgReset
|
|
INTEGER
|
|
}
|
|
|
|
internalMsgIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the list of message entries. Its value ranges
|
|
between 1 and the value of cpqWcrmInternalNumberOfMsgs."
|
|
::= { cpqWcrmInternalMsgEntry 1 }
|
|
|
|
internalMsgText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for each message (entry in the table)"
|
|
::= { cpqWcrmInternalMsgEntry 2 }
|
|
|
|
internalMsgStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
configChanged(2),
|
|
error(3),
|
|
ok(4),
|
|
alarm(5),
|
|
warning(6),
|
|
tooLow(7),
|
|
tooHigh(8),
|
|
setOff(9),
|
|
setOn(10)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Actual message status
|
|
1: not available
|
|
2: configuration has changed (sensor new, changed, lost)
|
|
3: error
|
|
4: OK
|
|
5: alarm, e.g. smoke, vibration...
|
|
6: warning of analog value, value reached warning threshold
|
|
7: analog value too low, value reached low threshold
|
|
8: analog value too high, value reached high threshold
|
|
9: output is set to ON
|
|
10: output is set to OFF"
|
|
::= { cpqWcrmInternalMsgEntry 3 }
|
|
|
|
internalMsgRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup of Alarm relay for this message/alarm
|
|
1: no switching of alarm relay
|
|
2: switching of alarm relay"
|
|
::= { cpqWcrmInternalMsgEntry 4 }
|
|
|
|
internalMsgBeeper OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup of Alarm beeper for this alarm
|
|
1: no audible alarm
|
|
2: audible alarm"
|
|
::= { cpqWcrmInternalMsgEntry 5 }
|
|
|
|
internalMsgTrap1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 1 activated"
|
|
::= { cpqWcrmInternalMsgEntry 6 }
|
|
|
|
internalMsgTrap2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 2 activated"
|
|
::= { cpqWcrmInternalMsgEntry 7 }
|
|
|
|
internalMsgTrap3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 3 activated"
|
|
::= { cpqWcrmInternalMsgEntry 8 }
|
|
|
|
internalMsgTrap4 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 4 and Event Logging activated"
|
|
::= { cpqWcrmInternalMsgEntry 9 }
|
|
|
|
internalMsgReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto (1),
|
|
manual (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reset of this alarm
|
|
1: auto
|
|
2: manual, alarm needs confirmation, e. g. with 'C' key"
|
|
::= { cpqWcrmInternalMsgEntry 10 }
|
|
-- table internal sensors unit END
|
|
-- waterCoolUnit
|
|
cpqWcrmWaterCoolUnitTypeOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail (1),
|
|
unitWcrm (2),
|
|
unitIO (3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of sensor unit connected to port 2"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 1 }
|
|
|
|
cpqWcrmWaterCoolUnitText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for sensor unit connected to port 2"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 2 }
|
|
|
|
cpqWcrmWaterCoolUnitSerial OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Serialnumber of sensor unit connected to port 2"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 3 }
|
|
|
|
cpqWcrmWaterCoolUnitStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
error(2),
|
|
changed(3),
|
|
reset(4),
|
|
timeout(5),
|
|
detected(6),
|
|
notAvail(7),
|
|
lowPower(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"General Status sensor unit connected to port 2
|
|
(1) OK
|
|
(2) error
|
|
(3) configuration of sensor unit has changed, confirmation required
|
|
(4) reset from sensor unit to confirm configuration changes
|
|
(5) timeout of sensor unit, confirmation required
|
|
(6) sensor unit detected, needs to be confirmed
|
|
(8) supply voltage is too low"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 4 }
|
|
|
|
-- Water Cool Unit table
|
|
|
|
-- Sensors
|
|
cpqWcrmWaterCoolUnitNumberOfSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of sensors connected to water cool unit"
|
|
::= { cpqWcrmStatusWaterCoolUnitSensors 1 }
|
|
|
|
-- table with entry for each sensor available on this unit
|
|
cpqWcrmWaterCoolUnitSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Headline of sensor table"
|
|
::= { cpqWcrmStatusWaterCoolUnitSensors 2 }
|
|
|
|
cpqWcrmWaterCoolUnitSensorEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmWaterCoolUnitSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of sensor table"
|
|
INDEX { waterCoolUnitSensorIndex }
|
|
::= { cpqWcrmWaterCoolUnitSensorTable 1 }
|
|
|
|
CpqWcrmWaterCoolUnitSensorEntry ::=
|
|
SEQUENCE {
|
|
waterCoolUnitSensorIndex
|
|
INTEGER,
|
|
waterCoolUnitSensorType
|
|
INTEGER,
|
|
waterCoolUnitSensorText
|
|
DisplayString (SIZE (0..20)),
|
|
waterCoolUnitSensorStatus
|
|
INTEGER,
|
|
waterCoolUnitSensorValue
|
|
INTEGER,
|
|
waterCoolUnitSensorSetHigh
|
|
INTEGER,
|
|
waterCoolUnitSensorSetLow
|
|
INTEGER,
|
|
waterCoolUnitSensorSetWarn
|
|
INTEGER
|
|
}
|
|
|
|
waterCoolUnitSensorIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the list of value entries. Its value ranges
|
|
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors."
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 1 }
|
|
|
|
waterCoolUnitSensorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail (1),
|
|
failure (2),
|
|
overflow (3),
|
|
tempIn (4),
|
|
tempOut (5), -- ()
|
|
heatFlow (6),
|
|
alarm (7),
|
|
warning (8),
|
|
rpmFan1 (9),
|
|
rpmFan2 (10),
|
|
rpmFan3 (11),
|
|
fanSpeed (12),
|
|
tempIn1 (13),
|
|
tempOut1 (14),
|
|
tempIn2 (15),
|
|
tempOut2 (16),
|
|
tempIn3 (17),
|
|
tempOut3 (18),
|
|
tempWaterIn (19),
|
|
tempWaterOut (20),
|
|
waterFlow (21),
|
|
valve (22), -- (MCS:status of valve: open, closed; MCSS: setpoint valve (%)..)
|
|
status (23),
|
|
condensateDuration (24),
|
|
condensateCycles (25),
|
|
rpmFan4 (26),
|
|
rpmFan5 (27),
|
|
rpmFan6 (28),
|
|
transfSwitch(29),
|
|
valveActValue(30)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
|
|
1: no sensor connected
|
|
2: sensor failure
|
|
3: value overflow
|
|
4: average temperature of air inlet to rack, average or max/min from each HEX
|
|
5: average temperature of air outlet from rack, average or max/min from each HEX
|
|
6: heatflow sensor
|
|
7: alarm:
|
|
Bit 0: Leakage
|
|
Bit 1: IIC Failure
|
|
8: warning:
|
|
Bit 0..2: Fan Tach 1..3
|
|
Bit 3,4: Temp. sensor HEX1 In,Out
|
|
Bit 5,6: Temp. sensor HEX2 In,Out
|
|
Bit 7,8: Temp. sensor HEX3 In,Out
|
|
Bit 9: Air temp. sensor
|
|
Bit 10..12: IIC failure, HEX1..3
|
|
Bit 13: Waterflow low
|
|
Bit 14,15: Watertemp. In,Out
|
|
Bit 16: Waterflow sensor fail.
|
|
Bit 17: Magnetic valve fail.
|
|
Bit 18: Leakdetector fail.
|
|
Bit 19: Uneven heat load
|
|
Bit 20: Condensation Pump Cycles > Max
|
|
Bit 21: Condensation Pump Running Time > Max
|
|
9: rpm speed of Fan1
|
|
10: rpm speed of Fan2
|
|
11: rpm speed of Fan3
|
|
12: fanSpeed setpoint, calculated from average temperatures
|
|
13: temperature air inlet to rack, HEX 1
|
|
14: temperature air outlet from rack, HEX 1
|
|
15: temperature air inlet to rack, HEX 1
|
|
16: temperature air outlet from rack, HEX 1
|
|
17: temperature air inlet to rack, HEX 1
|
|
18: temperature air outlet from rack, HEX 1
|
|
19: water temperature In
|
|
20: water temperature Out
|
|
21: water Flow
|
|
22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%)
|
|
23: status: Bit 0..Bit 2: fan module 1..3 available
|
|
Bit 3: water module available
|
|
24: condensation pump number of seconds on counter (last operating time)
|
|
25: condensation pump on/off cycle counter
|
|
26: rpm speed of Fan4
|
|
27: rpm speed of Fan5
|
|
28: rpm speed of Fan6
|
|
29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2
|
|
30: water valve actual value (%)"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 2 }
|
|
|
|
|
|
waterCoolUnitSensorText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for each sensor (entry in the table)"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 3 }
|
|
|
|
waterCoolUnitSensorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
warning(7),
|
|
tooLow(8),
|
|
tooHigh(9)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Actual status of the sensor"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 4 }
|
|
|
|
waterCoolUnitSensorValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)
|
|
|
|
If msg index = 1, 5 or 6
|
|
This value represents the actual Server Intake Temperature.
|
|
|
|
If msg index = 2:
|
|
This value represents the bit coded warning condition
|
|
Bit 0: Top Fan Module Failed
|
|
Bit 1: Middle Fan Module Failed
|
|
Bit 2: Bottom Fan Module Failed
|
|
Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed
|
|
Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed
|
|
Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed
|
|
Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed
|
|
Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed
|
|
Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed
|
|
Bit 9: Air Temperature Sensor Failed
|
|
Bit 10: Top Fan not installed
|
|
Bit 11: Middle Fan not installed
|
|
Bit 12: Bottom Fan not installed
|
|
Bit 13: Waterflow low
|
|
Bit 14: Water Unit Temperature Input Out of Range
|
|
Bit 15: Water Unit Temperature Output Out of Range
|
|
Bit 16: Waterflow Sensor Value Out of Range
|
|
Bit 17: Water Valve Failed
|
|
Bit 18: Leakdetector Failed
|
|
Bit 19: Heat Load Warning
|
|
Bit 20: The Condensation Pump has exceeded the max. number of cycles
|
|
Bit 21: The Condensation Pump has exceeded the max. Running Time
|
|
|
|
If msg index = 3:
|
|
This value represents the bit coded alarm condition
|
|
Bit 0: Leakage Detected
|
|
Bit 1: Comm. Failure IIC"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 5 }
|
|
|
|
waterCoolUnitSensorSetHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value for high setpoint of sensor"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 6 }
|
|
|
|
waterCoolUnitSensorSetLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value for low setpoint of sensor,
|
|
also used as alarm delay"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 7 }
|
|
|
|
waterCoolUnitSensorSetWarn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Value for warning setpoint of sensor,
|
|
also used as fan threshold"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 8 }
|
|
|
|
-- table END
|
|
|
|
-- Outputs
|
|
cpqWcrmWaterCoolUnitNumberOfOutputs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outputs available on sensor water cool unit"
|
|
::= { cpqWcrmStatusWaterCoolUnitOutputs 1 }
|
|
|
|
-- table with entry for each output available on this unit
|
|
|
|
cpqWcrmWaterCoolUnitOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Headline of output table"
|
|
::= { cpqWcrmStatusWaterCoolUnitOutputs 2 }
|
|
|
|
cpqWcrmWaterCoolUnitOutputEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmWaterCoolUnitOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of output table"
|
|
INDEX { waterCoolUnitOutputIndex }
|
|
::= { cpqWcrmWaterCoolUnitOutputTable 1 }
|
|
|
|
CpqWcrmWaterCoolUnitOutputEntry ::=
|
|
SEQUENCE {
|
|
waterCoolUnitOutputIndex
|
|
INTEGER,
|
|
waterCoolUnitOutputType
|
|
INTEGER,
|
|
waterCoolUnitOutputText
|
|
DisplayString (SIZE (0..20)),
|
|
waterCoolUnitOutputStatus
|
|
INTEGER,
|
|
waterCoolUnitOutputValue
|
|
INTEGER,
|
|
waterCoolUnitOutputSet
|
|
INTEGER,
|
|
waterCoolUnitOutputConfig
|
|
INTEGER,
|
|
waterCoolUnitOutputDelay
|
|
INTEGER,
|
|
waterCoolUnitOutputTimeoutAction
|
|
INTEGER
|
|
}
|
|
|
|
waterCoolUnitOutputIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the list of output entries. Its value ranges
|
|
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs."
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 1 }
|
|
|
|
waterCoolUnitOutputType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail (1),
|
|
failure (2),
|
|
overflow (3),
|
|
setpoint (4),
|
|
hysteresis (5),
|
|
command (6),
|
|
controlMode (7),
|
|
fanSpeedMin (8),
|
|
dTmin (9),
|
|
dTmax(10),
|
|
cpWatert(11),
|
|
setHeatload(12),
|
|
setEdoFlow(13),
|
|
setEdoHeat(14),
|
|
setCondCycles(15),
|
|
setCondRun(16),
|
|
doorControl(17),
|
|
pidContrKP(18),
|
|
pidContrKI(19),
|
|
pidContrKD(20),
|
|
pidSampleTime(21)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex]
|
|
1: no output connected
|
|
2: output failure
|
|
3: value overflow
|
|
4: water valve setpoint
|
|
5: water valve hysteresis
|
|
6: command for manual control
|
|
7: Flow Meter Model, 0=SIKA, 1=Chemline
|
|
8: minimum fan speed
|
|
9: min delta T, used for fan control
|
|
10: max delta T, used for fan control
|
|
11: specific heat capacity
|
|
12: setpoint heatload warning
|
|
13: setpoint Water Flow Loss Emergency Door Opening
|
|
14: setpoint High Temperature Emergency Door Opening
|
|
15: setpoint Condensation Pump Cycles (Warning)
|
|
16: setpoint Condensation Pump Running Time (Warning)
|
|
17: command for door opening, 0=lock door, 1=unlock door
|
|
18: KP parameter for PID controller
|
|
19: KI parameter for PID controller
|
|
20: KD parameter for PID controller
|
|
21: sampling time PID controller"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 2 }
|
|
|
|
|
|
waterCoolUnitOutputText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for each output (entry in the table)"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 3 }
|
|
|
|
waterCoolUnitOutputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
setOff(7),
|
|
setOn(8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Actual status of the output"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 4 }
|
|
|
|
waterCoolUnitOutputValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Signed value for output"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 5 }
|
|
|
|
waterCoolUnitOutputSet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (1),
|
|
on (2),
|
|
lock (3),
|
|
unlock (4),
|
|
unlockDelay (5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Command for output"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 6 }
|
|
|
|
waterCoolUnitOutputConfig OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disRemote (1),
|
|
enRemote (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Configuration for output
|
|
1: disable remote control (e.g. keypad)
|
|
2: enable remote control "
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 7 }
|
|
|
|
waterCoolUnitOutputDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Unsigned Value for delay,
|
|
after this time the output will fall into the previous state"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 8 }
|
|
|
|
waterCoolUnitOutputTimeoutAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
stay (1),
|
|
off (2),
|
|
on (3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"State for output if timeout (RS422) occurs"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 9 }
|
|
|
|
-- Alarms
|
|
|
|
cpqWcrmWaterCoolUnitNumberOfMsgs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of alarms that can be created with water cool unit"
|
|
::= { cpqWcrmStatusWaterCoolUnitMsg 1 }
|
|
|
|
-- table with entry for each alarm available on this unit
|
|
|
|
cpqWcrmWaterCoolUnitMsgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitMsgEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Headline of message table"
|
|
::= { cpqWcrmStatusWaterCoolUnitMsg 2 }
|
|
|
|
cpqWcrmWaterCoolUnitMsgEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmWaterCoolUnitMsgEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of message table"
|
|
INDEX { waterCoolUnitMsgIndex }
|
|
::= { cpqWcrmWaterCoolUnitMsgTable 1 }
|
|
|
|
CpqWcrmWaterCoolUnitMsgEntry ::=
|
|
SEQUENCE {
|
|
waterCoolUnitMsgIndex
|
|
INTEGER,
|
|
waterCoolUnitMsgText
|
|
DisplayString (SIZE (0..20)),
|
|
waterCoolUnitMsgStatus
|
|
INTEGER,
|
|
waterCoolUnitMsgRelay
|
|
INTEGER,
|
|
waterCoolUnitMsgBeeper
|
|
INTEGER,
|
|
waterCoolUnitMsgTrap1
|
|
INTEGER,
|
|
waterCoolUnitMsgTrap2
|
|
INTEGER,
|
|
waterCoolUnitMsgTrap3
|
|
INTEGER,
|
|
waterCoolUnitMsgTrap4
|
|
INTEGER,
|
|
waterCoolUnitMsgReset
|
|
INTEGER
|
|
}
|
|
|
|
waterCoolUnitMsgIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the list of alarm entries. Its value ranges
|
|
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs."
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 1 }
|
|
|
|
waterCoolUnitMsgText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Descriptional text for each message (entry in the table)"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 2 }
|
|
|
|
waterCoolUnitMsgStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
configChanged(2),
|
|
error(3),
|
|
ok(4),
|
|
alarm(5),
|
|
warning(6),
|
|
tooLow(7),
|
|
tooHigh(8),
|
|
setOff(9),
|
|
setOn(10)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Actual message status
|
|
4: OK
|
|
5: alarm
|
|
6: warning
|
|
7: analog value too low, value reached low threshold
|
|
8: analog value too high, value reached high threshold"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 3 }
|
|
|
|
waterCoolUnitMsgRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup of Alarm relay for this alarm
|
|
2: no switching of alarm relay
|
|
1: switching of alarm relay"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 4 }
|
|
|
|
waterCoolUnitMsgBeeper OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup of Alarm beeper for this alarm
|
|
2: no audible alarm
|
|
1: audible alarm"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 5 }
|
|
|
|
waterCoolUnitMsgTrap1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 1 activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 6 }
|
|
|
|
waterCoolUnitMsgTrap2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 2 activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 7 }
|
|
|
|
waterCoolUnitMsgTrap3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 3 activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 8 }
|
|
|
|
waterCoolUnitMsgTrap4 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable (1),
|
|
enable (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Trap receiver 4 and Event Logging activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 9 }
|
|
|
|
waterCoolUnitMsgReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto (1),
|
|
manual (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reset of this alarm
|
|
1: auto
|
|
2: manual, alarm needs confirmation, e. g. with 'C' key"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 10 }
|
|
-- table END
|
|
|
|
--setupGeneral-group
|
|
cpqWcrmSetTempUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
celsius(1),
|
|
fahrenheit(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Unit of all temperature values and setpoints, Celsius or Fahrenheit"
|
|
::= { cpqWcrmSetupGeneral 1 }
|
|
|
|
cpqWcrmSetBeeper OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Audible alarm in Environmental Controller unit:
|
|
(2): beeper is on
|
|
(1): beeper is off (general)"
|
|
::= { cpqWcrmSetupGeneral 2 }
|
|
|
|
|
|
cpqWcrmResetRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable acknowledging currently active alarm relay
|
|
(with 'C' on Environmental Controller)."
|
|
::= { cpqWcrmSetupGeneral 3 }
|
|
|
|
|
|
cpqWcrmLogicRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
closeAtAlarm(1),
|
|
openAtAlarm(2),
|
|
off(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Logic of alarm relay:
|
|
(1) Relay will pick up in case of an alarm
|
|
(2) Relay will release in case of an alarm
|
|
(3) Relay off (general)"
|
|
::= { cpqWcrmSetupGeneral 4 }
|
|
|
|
cpqWcrmWebAccess OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
viewOnly(1),
|
|
fullAccess(2),
|
|
off(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Web access via HTTP:
|
|
(1) view only
|
|
(2) full Access, read and set
|
|
(3) Web disabled (general)"
|
|
::= { cpqWcrmSetupGeneral 5 }
|
|
|
|
|
|
-- SetupClock
|
|
cpqWcrmSetupDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"actual Date in format DD.MM.YYYY"
|
|
::= { cpqWcrmSetupGeneral 6 }
|
|
|
|
cpqWcrmSetupTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..8))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)"
|
|
::= { cpqWcrmSetupGeneral 7 }
|
|
|
|
-- table for timer function
|
|
|
|
cpqWcrmTimerNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of value-table entries=number of outlets available on this unit"
|
|
::= { cpqWcrmTimerTable1 1 }
|
|
|
|
cpqWcrmTimerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmTimerEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Headline of status-table"
|
|
::= { cpqWcrmTimerTable1 2 }
|
|
|
|
cpqWcrmTimerEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmTimerEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of timer-table"
|
|
INDEX { cpqWcrmTimerIndex }
|
|
::= { cpqWcrmTimerTable 1 }
|
|
|
|
CpqWcrmTimerEntry ::=
|
|
SEQUENCE {
|
|
cpqWcrmTimerIndex
|
|
INTEGER,
|
|
cpqWcrmTimerStatus
|
|
INTEGER,
|
|
cpqWcrmTimerDayOfWeek
|
|
INTEGER,
|
|
cpqWcrmTimeOn
|
|
DisplayString (SIZE (0..5)),
|
|
cpqWcrmTimeOff
|
|
DisplayString (SIZE (0..5)),
|
|
cpqWcrmTimeControl
|
|
INTEGER,
|
|
cpqWcrmTimerFunction
|
|
INTEGER
|
|
}
|
|
|
|
cpqWcrmTimerIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the list of timer entries. Its value ranges
|
|
between 1 and the value of cpqWcrmTimerNumber."
|
|
::= { cpqWcrmTimerEntry 1 }
|
|
|
|
cpqWcrmTimerStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
switchedOff(1),
|
|
switchedOn(2),
|
|
noTime(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Actual status of the timer"
|
|
::= { cpqWcrmTimerEntry 2 }
|
|
|
|
cpqWcrmTimerDayOfWeek OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sun(1),
|
|
mon(2),
|
|
tue(3) ,
|
|
wed(4),
|
|
thu(5),
|
|
fri(6),
|
|
sat(7),
|
|
sat-sun(8),
|
|
mon-fri(9),
|
|
mon-sun(10)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Selection of day of week for timer to switch"
|
|
::= { cpqWcrmTimerEntry 3 }
|
|
|
|
cpqWcrmTimeOn OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..5))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Time to switch on current function,
|
|
Format: HH:MM"
|
|
::= { cpqWcrmTimerEntry 4 }
|
|
|
|
cpqWcrmTimeOff OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..5))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Time to switch off current function,
|
|
Format: HH:MM"
|
|
::= { cpqWcrmTimerEntry 5 }
|
|
|
|
cpqWcrmTimeControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Control via RTC"
|
|
::= { cpqWcrmTimerEntry 6 }
|
|
|
|
cpqWcrmTimerFunction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disTrapRec1 (1),
|
|
disTrapRec2 (2),
|
|
disTrapRec3 (3),
|
|
disTrapRec4 (4),
|
|
schedule1 (5),
|
|
schedule2 (6),
|
|
schedule3 (7),
|
|
schedule4 (8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Function which is controlled via timer
|
|
1-4: sending Traps to this Trap receiver will be disabled
|
|
5 - 8: scheduled alarm off"
|
|
::= { cpqWcrmTimerEntry 7 }
|
|
|
|
-- added Oct 27, 2006
|
|
cpqWcrmSetFlowUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
literMin(1),
|
|
gallonMin(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Unit of Water Flow, Liter/min or Gallon/min"
|
|
::= { cpqWcrmSetupGeneral 9 }
|
|
-- added
|
|
|
|
--cpqWcrmTrapTable-group
|
|
|
|
cpqWcrmTraptableNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of trapTable entries. The number of trap-receiver"
|
|
::= { cpqWcrmTraps 1 }
|
|
|
|
cpqWcrmTrapTableTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmTrapTableEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of trap-receiver entries"
|
|
::= { cpqWcrmTraps 2 }
|
|
|
|
cpqWcrmTrapTableEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmTrapTableEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Entries of trapTable"
|
|
INDEX { trapIndex }
|
|
::= { cpqWcrmTrapTableTable 1 }
|
|
|
|
CpqWcrmTrapTableEntry ::=
|
|
SEQUENCE {
|
|
trapIndex
|
|
INTEGER,
|
|
trapStatus
|
|
INTEGER,
|
|
trapIPaddress
|
|
DisplayString
|
|
}
|
|
|
|
trapIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Index for the trap-receiver-table. Its value ranges between
|
|
1 and the value of traptableNumber "
|
|
::= { cpqWcrmTrapTableEntry 1 }
|
|
|
|
trapStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable trap receiver"
|
|
::= { cpqWcrmTrapTableEntry 2 }
|
|
|
|
trapIPaddress OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-address of trap-receiver"
|
|
::= { cpqWcrmTrapTableEntry 3 }
|
|
|
|
--cpqWcrmControl-group (Added in Version 1.1)
|
|
cpqWcrmResetUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noReset(1),
|
|
reset(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Command to reset (acknowledge) alarms of Environmental Controller unit.
|
|
Setting to 'reset' (2) will have same result as pressing 'C' on Units.
|
|
Variable is automatically set back to 'noReset' (1)."
|
|
::= { cpqWcrmControl 1 }
|
|
|
|
|
|
--Traps
|
|
|
|
alarmSensorInternal TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation,
|
|
internalMsgIndex, internalMsgText, internalMsgStatus, internalSensorValue, cpqWcrmURL }
|
|
DESCRIPTION
|
|
"Internal Sensor Alarm"
|
|
--
|
|
--#TYPE "Internal sensor alarm"
|
|
--#SUMMARY "Location: %s, Alarm[%d]: %s, Status: %d, Actual Value: %d, from: %s, contact %s, URL %s"
|
|
--#ARGUMENTS { 2, 3, 4, 5, 6, 1, 0, 7}
|
|
--#SEVERITY MAJOR
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
--#TIMEINDEX 99
|
|
--
|
|
::= 1
|
|
|
|
alarmSensorWaterCoolUnit TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation,
|
|
waterCoolUnitMsgIndex, waterCoolUnitMsgText, waterCoolUnitMsgStatus, waterCoolUnitSensorValue, cpqWcrmURL }
|
|
DESCRIPTION
|
|
"Water Cool Unit Sensor Alarm"
|
|
--
|
|
--#TYPE "Water cool unit sensor alarm"
|
|
--#SUMMARY "Location: %s, Alarm[%d]: %s, Status: %d, Actual Value: %d, from: %s, contact %s, URL %s"
|
|
--#ARGUMENTS { 2, 3, 4, 5, 6, 1, 0, 7}
|
|
--#SEVERITY MAJOR
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
--#TIMEINDEX 99
|
|
--
|
|
::= 2
|
|
|
|
alarmInternal TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation,
|
|
cpqWcrmInternalText, cpqWcrmInternalStatus, cpqWcrmURL }
|
|
DESCRIPTION
|
|
"Internal Unit Alarm"
|
|
--
|
|
--#TYPE "Internal unit alarm"
|
|
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s, URL %s"
|
|
--#ARGUMENTS { 2, 3, 1, 0, 5}
|
|
--#SEVERITY MAJOR
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
--#TIMEINDEX 99
|
|
|
|
--
|
|
::= 5
|
|
|
|
alarmWaterCoolUnit TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation,
|
|
cpqWcrmWaterCoolUnitText, cpqWcrmWaterCoolUnitStatus, cpqWcrmURL }
|
|
DESCRIPTION
|
|
"Water Cool Unit System Alarm"
|
|
--
|
|
--#TYPE "Water cool unit alarm"
|
|
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s, URL %s"
|
|
--#ARGUMENTS { 2, 3, 1, 0, 5}
|
|
--#SEVERITY MAJOR
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
--#TIMEINDEX 99
|
|
--
|
|
::= 6
|
|
|
|
testTrap TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation, cpqWcrmURL }
|
|
DESCRIPTION
|
|
"Test trap sent to a trap receiver to check proper reception of traps"
|
|
--
|
|
--#TYPE "Test Trap"
|
|
--#SUMMARY "Location: %s, Test Trap from unit %s was sent, contact %s, URL %s"
|
|
--#ARGUMENTS { 2, 1, 0, 3}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
--#TIMEINDEX 99
|
|
--
|
|
::= 10
|
|
|
|
|
|
END
|
|
|