#-MIBFILE: cpqwcrm.mib
|
|
|
|
CPQWCRM-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
compaq OBJECT IDENTIFIER ::= { enterprises 232 }
|
|
DisplayString ::=
|
|
OCTET STRING
|
|
|
|
PhysAddress ::=
|
|
OCTET STRING
|
|
|
|
mib-2 OBJECT IDENTIFIER ::= { mgmt 1 }
|
|
system OBJECT IDENTIFIER ::= { mib-2 1 }
|
|
sysName OBJECT IDENTIFIER ::= { system 5 }
|
|
mib-2 OBJECT IDENTIFIER ::= { mgmt 1 }
|
|
sysDescr OBJECT IDENTIFIER ::= { system 1 }
|
|
sysContact OBJECT IDENTIFIER ::= { system 4 }
|
|
sysLocation OBJECT IDENTIFIER ::= { system 6 }
|
|
cpqWcrm OBJECT IDENTIFIER ::= { compaq 167 }
|
|
|
|
cpqWcrmMibRev OBJECT IDENTIFIER ::= { cpqWcrm 1 }
|
|
|
|
cpqWcrmStatus OBJECT IDENTIFIER ::= { cpqWcrm 2 }
|
|
|
|
cpqWcrmStatusSensorInternal OBJECT IDENTIFIER ::= { cpqWcrmStatus 3 }
|
|
|
|
cpqWcrmStatusInternalSensors OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 5 }
|
|
|
|
cpqWcrmStatusInternalOutputs OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 6 }
|
|
|
|
cpqWcrmStatusInternalMsg OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorInternal 7 }
|
|
|
|
cpqWcrmStatusSensorWaterCoolUnit OBJECT IDENTIFIER ::= { cpqWcrmStatus 4 }
|
|
|
|
cpqWcrmStatusWaterCoolUnitSensors OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 5 }
|
|
|
|
cpqWcrmStatusWaterCoolUnitOutputs OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 6 }
|
|
|
|
cpqWcrmStatusWaterCoolUnitMsg OBJECT IDENTIFIER ::= { cpqWcrmStatusSensorWaterCoolUnit 7 }
|
|
|
|
cpqWcrmSetup OBJECT IDENTIFIER ::= { cpqWcrm 3 }
|
|
|
|
cpqWcrmSetupGeneral OBJECT IDENTIFIER ::= { cpqWcrmSetup 1 }
|
|
|
|
cpqWcrmTimerTable1 OBJECT IDENTIFIER ::= { cpqWcrmSetupGeneral 8 }
|
|
|
|
cpqWcrmTrapControl OBJECT IDENTIFIER ::= { cpqWcrm 4 }
|
|
|
|
cpqWcrmTraps OBJECT IDENTIFIER ::= { cpqWcrmTrapControl 7 }
|
|
|
|
cpqWcrmControl OBJECT IDENTIFIER ::= { cpqWcrm 5 }
|
|
|
|
cpqWcrmMibMajRev OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The Major Revision level.
|
|
A change in the major revision level represents a major change
|
|
in the architecture of the MIB. A change in the major revision
|
|
level may indicate a significant change in the information,
|
|
correct interpretation of data may require a MIB document
|
|
with the same major revision level."
|
|
::= { cpqWcrmMibRev 1 }
|
|
|
|
|
|
cpqWcrmMibMinRev OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The Minor Revision level.
|
|
A change in the minor revision level may represent some minor
|
|
additional support, no changes to any pre-existing information
|
|
has occurred."
|
|
::= { cpqWcrmMibRev 2 }
|
|
|
|
|
|
cpqWcrmMibCondition OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
ok(2),
|
|
degraded(3),
|
|
failed(4),
|
|
configChanged(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The overall condition (status) of the system represented by
|
|
this MIB.
|
|
(2) OK
|
|
(3) a minor problem, warning condition (yellow LED on Environmental Controller)
|
|
(4) a major problem (red LED on Environmental Controller)
|
|
(5) configuration of sensor units changed or
|
|
unit detected (red/yellow/green LED on Environmental Controller)"
|
|
::= { cpqWcrmMibRev 3 }
|
|
|
|
|
|
cpqWcrmStatusDeviceEnvironmentalController OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
failed(1),
|
|
ok(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "General Status of Environmental Controller unit itself
|
|
(1) failed
|
|
(2) OK"
|
|
::= { cpqWcrmStatus 1 }
|
|
|
|
|
|
cpqWcrmUnitsConnected OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of sensor units connected to the Environmental Controller, Port 1 to 2"
|
|
::= { cpqWcrmStatus 2 }
|
|
|
|
|
|
cpqWcrmURL OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..80))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "URL of the management interface in the format http[s]://ipaddr[:port#][/page]"
|
|
::= { cpqWcrmStatus 7 }
|
|
|
|
|
|
cpqWcrmInternalTypeOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
unitWcrm(2),
|
|
unitIO(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of sensor unit connected to port 1"
|
|
::= { cpqWcrmStatusSensorInternal 1 }
|
|
|
|
|
|
cpqWcrmInternalText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..10))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for sensor unit connected to port 1"
|
|
::= { cpqWcrmStatusSensorInternal 2 }
|
|
|
|
|
|
cpqWcrmInternalSerial OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Serialnumber of sensor unit connected to port 1"
|
|
::= { cpqWcrmStatusSensorInternal 3 }
|
|
|
|
|
|
cpqWcrmInternalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
error(2),
|
|
changed(3),
|
|
reset(4),
|
|
timeout(5),
|
|
detected(6),
|
|
notAvail(7),
|
|
lowPower(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "General Status sensor unit connected to port 1
|
|
(1) OK
|
|
(2) error, e. g. value overflow
|
|
(3) configuration of sensor unit has changed, confirmation required
|
|
(4) reset from sensor unit to confirm configuration changes
|
|
(5) timeout of sensor unit, confirmation required to unload this unit
|
|
(6) sensor unit detected, needs to be confirmed
|
|
(7) unit is not available
|
|
(8) supply voltage is too low"
|
|
::= { cpqWcrmStatusSensorInternal 4 }
|
|
|
|
|
|
cpqWcrmInternalNumberOfSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of sensors connected to sensor unit 1"
|
|
::= { cpqWcrmStatusInternalSensors 1 }
|
|
|
|
|
|
cpqWcrmInternalSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmInternalSensorEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Headline of sensor table"
|
|
::= { cpqWcrmStatusInternalSensors 2 }
|
|
|
|
|
|
cpqWcrmInternalSensorEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmInternalSensorEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of sensor table"
|
|
INDEX { internalSensorIndex }
|
|
|
|
::= { cpqWcrmInternalSensorTable 1 }
|
|
|
|
cpqWcrmInternalSensorEntry ::=
|
|
SEQUENCE {
|
|
internalSensorIndex INTEGER,
|
|
internalSensorType INTEGER,
|
|
internalSensorText DisplayString,
|
|
internalSensorStatus INTEGER,
|
|
internalSensorValue INTEGER,
|
|
internalSensorSetHigh INTEGER,
|
|
internalSensorSetLow INTEGER,
|
|
internalSensorSetWarn INTEGER
|
|
}
|
|
|
|
internalSensorIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the list of value entries. Its value ranges
|
|
between 1 and the value of cpqWcrmInternalNumberOfSensors."
|
|
::= { cpqWcrmInternalSensorEntry 1 }
|
|
|
|
|
|
internalSensorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
failure(2),
|
|
overflow(3),
|
|
access(4),
|
|
vibration(5),
|
|
motion(6),
|
|
smoke(7),
|
|
airFlow(8),
|
|
type6(9),
|
|
temperature(10),
|
|
current4to20(11),
|
|
humidity(12),
|
|
userNO(13),
|
|
userNC(14),
|
|
voltOK(17),
|
|
voltage(18),
|
|
fanOK(19),
|
|
leakage(20)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
|
|
1: no sensor connected
|
|
2: sensor failure
|
|
3: value overflow
|
|
4: sensor type 1, access sensor
|
|
5: sensor type 2, vibration sensor
|
|
6: sensor type 3, motion sensor
|
|
7: sensor type 4, smoke sensor
|
|
8: sensor type 5, air flow sensor
|
|
9: sensor type 6, reserved
|
|
10: sensor type 7, temperature sensor
|
|
11: sensor type 8, 4..20mA sensor
|
|
12: sensor type 9, humidity sensor
|
|
13: user sensor with normally opened contact
|
|
14: user sensor with normally closed contact
|
|
15: door locked sensor from locking device
|
|
16: remote unlock sensor (e.g. external keypad)
|
|
17: voltage sensor, indicates status of main voltage (OK, NOK)
|
|
18: voltage value
|
|
19: fan status, from Environmental Controller-FAS-Unit
|
|
20: leakage sensor"
|
|
::= { cpqWcrmInternalSensorEntry 2 }
|
|
|
|
|
|
internalSensorText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for each sensor (entry in the table)"
|
|
::= { cpqWcrmInternalSensorEntry 3 }
|
|
|
|
|
|
internalSensorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
warning(7),
|
|
tooLow(8),
|
|
tooHigh(9)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Actual status of the sensor"
|
|
::= { cpqWcrmInternalSensorEntry 4 }
|
|
|
|
|
|
internalSensorValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value of sensor"
|
|
::= { cpqWcrmInternalSensorEntry 5 }
|
|
|
|
|
|
internalSensorSetHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value for high setpoint of sensor"
|
|
::= { cpqWcrmInternalSensorEntry 6 }
|
|
|
|
|
|
internalSensorSetLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value for low setpoint of sensor,
|
|
also used as alarm delay"
|
|
::= { cpqWcrmInternalSensorEntry 7 }
|
|
|
|
|
|
internalSensorSetWarn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value for warning setpoint of sensor,
|
|
also used as fan threshold"
|
|
::= { cpqWcrmInternalSensorEntry 8 }
|
|
|
|
|
|
cpqWcrmInternalNumberOfOutputs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of outputs available on internal sensor"
|
|
::= { cpqWcrmStatusInternalOutputs 1 }
|
|
|
|
|
|
cpqWcrmInternalOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmInternalOutputEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Headline of output table"
|
|
::= { cpqWcrmStatusInternalOutputs 2 }
|
|
|
|
|
|
cpqWcrmInternalOutputEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmInternalOutputEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of output table"
|
|
INDEX { internalOutputIndex }
|
|
|
|
::= { cpqWcrmInternalOutputTable 1 }
|
|
|
|
cpqWcrmInternalOutputEntry ::=
|
|
SEQUENCE {
|
|
internalOutputIndex INTEGER,
|
|
internalOutputType INTEGER,
|
|
internalOutputText DisplayString,
|
|
internalOutputStatus INTEGER,
|
|
internalOutputValue INTEGER,
|
|
internalOutputSet INTEGER,
|
|
internalOutputConfig INTEGER,
|
|
internalOutputDelay INTEGER,
|
|
internalOutputTimeoutAction INTEGER
|
|
}
|
|
|
|
internalOutputIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the list of output entries. Its value ranges
|
|
between 1 and the value of cpqWcrmInternalNumberOfOutputs."
|
|
::= { cpqWcrmInternalOutputEntry 1 }
|
|
|
|
|
|
internalOutputType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
failure(2),
|
|
overflow(3),
|
|
universalOut(4),
|
|
powerOut(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of output which is connected to internal sensor to output[internalOutputIndex]
|
|
1: no output connected
|
|
2: output failure
|
|
3: value overflow
|
|
4: output type 6, universal relay output
|
|
5: output type 8, power output"
|
|
::= { cpqWcrmInternalOutputEntry 2 }
|
|
|
|
|
|
internalOutputText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for each output (entry in the table)"
|
|
::= { cpqWcrmInternalOutputEntry 3 }
|
|
|
|
|
|
internalOutputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
setOff(7),
|
|
setOn(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Actual status of the output"
|
|
::= { cpqWcrmInternalOutputEntry 4 }
|
|
|
|
|
|
internalOutputValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value for output"
|
|
::= { cpqWcrmInternalOutputEntry 5 }
|
|
|
|
|
|
internalOutputSet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2),
|
|
lock(3),
|
|
unlock(4),
|
|
unlockDelay(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Command for output"
|
|
::= { cpqWcrmInternalOutputEntry 6 }
|
|
|
|
|
|
internalOutputConfig OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disRemote(1),
|
|
enRemote(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Configuration for output
|
|
1: disable remote control (e.g. keypad)
|
|
2: enable remote control "
|
|
::= { cpqWcrmInternalOutputEntry 7 }
|
|
|
|
|
|
internalOutputDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Unsigned Value for delay,
|
|
after this time the output will fall into the previous state"
|
|
::= { cpqWcrmInternalOutputEntry 8 }
|
|
|
|
|
|
internalOutputTimeoutAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
stay(1),
|
|
off(2),
|
|
on(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "State for output if timeout (RS422) occurs"
|
|
::= { cpqWcrmInternalOutputEntry 9 }
|
|
|
|
|
|
cpqWcrmInternalNumberOfMsgs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of messages that can be created with internal sensor"
|
|
::= { cpqWcrmStatusInternalMsg 1 }
|
|
|
|
|
|
cpqWcrmInternalMsgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmInternalMsgEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Headline of message table"
|
|
::= { cpqWcrmStatusInternalMsg 2 }
|
|
|
|
|
|
cpqWcrmInternalMsgEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmInternalMsgEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of message table"
|
|
INDEX { internalMsgIndex }
|
|
|
|
::= { cpqWcrmInternalMsgTable 1 }
|
|
|
|
cpqWcrmInternalMsgEntry ::=
|
|
SEQUENCE {
|
|
internalMsgIndex INTEGER,
|
|
internalMsgText DisplayString,
|
|
internalMsgStatus INTEGER,
|
|
internalMsgRelay INTEGER,
|
|
internalMsgBeeper INTEGER,
|
|
internalMsgTrap1 INTEGER,
|
|
internalMsgTrap2 INTEGER,
|
|
internalMsgTrap3 INTEGER,
|
|
internalMsgTrap4 INTEGER,
|
|
internalMsgReset INTEGER
|
|
}
|
|
|
|
internalMsgIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the list of message entries. Its value ranges
|
|
between 1 and the value of cpqWcrmInternalNumberOfMsgs."
|
|
::= { cpqWcrmInternalMsgEntry 1 }
|
|
|
|
|
|
internalMsgText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for each message (entry in the table)"
|
|
::= { cpqWcrmInternalMsgEntry 2 }
|
|
|
|
|
|
internalMsgStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
configChanged(2),
|
|
error(3),
|
|
ok(4),
|
|
alarm(5),
|
|
warning(6),
|
|
tooLow(7),
|
|
tooHigh(8),
|
|
setOff(9),
|
|
setOn(10)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Actual message status
|
|
1: not available
|
|
2: configuration has changed (sensor new, changed, lost)
|
|
3: error
|
|
4: OK
|
|
5: alarm, e.g. smoke, vibration...
|
|
6: warning of analog value, value reached warning threshold
|
|
7: analog value too low, value reached low threshold
|
|
8: analog value too high, value reached high threshold
|
|
9: output is set to ON
|
|
10: output is set to OFF"
|
|
::= { cpqWcrmInternalMsgEntry 3 }
|
|
|
|
|
|
internalMsgRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Setup of Alarm relay for this message/alarm
|
|
1: no switching of alarm relay
|
|
2: switching of alarm relay"
|
|
::= { cpqWcrmInternalMsgEntry 4 }
|
|
|
|
|
|
internalMsgBeeper OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Setup of Alarm beeper for this alarm
|
|
1: no audible alarm
|
|
2: audible alarm"
|
|
::= { cpqWcrmInternalMsgEntry 5 }
|
|
|
|
|
|
internalMsgTrap1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 1 activated"
|
|
::= { cpqWcrmInternalMsgEntry 6 }
|
|
|
|
|
|
internalMsgTrap2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 2 activated"
|
|
::= { cpqWcrmInternalMsgEntry 7 }
|
|
|
|
|
|
internalMsgTrap3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 3 activated"
|
|
::= { cpqWcrmInternalMsgEntry 8 }
|
|
|
|
|
|
internalMsgTrap4 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 4 and Event Logging activated"
|
|
::= { cpqWcrmInternalMsgEntry 9 }
|
|
|
|
|
|
internalMsgReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(1),
|
|
manual(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Reset of this alarm
|
|
1: auto
|
|
2: manual, alarm needs confirmation, e. g. with 'C' key"
|
|
::= { cpqWcrmInternalMsgEntry 10 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitTypeOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
unitWcrm(2),
|
|
unitIO(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of sensor unit connected to port 2"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 1 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..10))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for sensor unit connected to port 2"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 2 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitSerial OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Serialnumber of sensor unit connected to port 2"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 3 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
error(2),
|
|
changed(3),
|
|
reset(4),
|
|
timeout(5),
|
|
detected(6),
|
|
notAvail(7),
|
|
lowPower(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "General Status sensor unit connected to port 2
|
|
(1) OK
|
|
(2) error
|
|
(3) configuration of sensor unit has changed, confirmation required
|
|
(4) reset from sensor unit to confirm configuration changes
|
|
(5) timeout of sensor unit, confirmation required
|
|
(6) sensor unit detected, needs to be confirmed
|
|
(8) supply voltage is too low"
|
|
::= { cpqWcrmStatusSensorWaterCoolUnit 4 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitNumberOfSensors OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of sensors connected to water cool unit"
|
|
::= { cpqWcrmStatusWaterCoolUnitSensors 1 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitSensorEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Headline of sensor table"
|
|
::= { cpqWcrmStatusWaterCoolUnitSensors 2 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitSensorEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmWaterCoolUnitSensorEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of sensor table"
|
|
INDEX { waterCoolUnitSensorIndex }
|
|
|
|
::= { cpqWcrmWaterCoolUnitSensorTable 1 }
|
|
|
|
cpqWcrmWaterCoolUnitSensorEntry ::=
|
|
SEQUENCE {
|
|
waterCoolUnitSensorIndex INTEGER,
|
|
waterCoolUnitSensorType INTEGER,
|
|
waterCoolUnitSensorText DisplayString,
|
|
waterCoolUnitSensorStatus INTEGER,
|
|
waterCoolUnitSensorValue INTEGER,
|
|
waterCoolUnitSensorSetHigh INTEGER,
|
|
waterCoolUnitSensorSetLow INTEGER,
|
|
waterCoolUnitSensorSetWarn INTEGER
|
|
}
|
|
|
|
waterCoolUnitSensorIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the list of value entries. Its value ranges
|
|
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors."
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 1 }
|
|
|
|
|
|
waterCoolUnitSensorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
failure(2),
|
|
overflow(3),
|
|
tempIn(4),
|
|
tempOut(5),
|
|
heatFlow(6),
|
|
alarm(7),
|
|
warning(8),
|
|
rpmFan1(9),
|
|
rpmFan2(10),
|
|
rpmFan3(11),
|
|
fanSpeed(12),
|
|
tempIn1(13),
|
|
tempOut1(14),
|
|
tempIn2(15),
|
|
tempOut2(16),
|
|
tempIn3(17),
|
|
tempOut3(18),
|
|
tempWaterIn(19),
|
|
tempWaterOut(20),
|
|
waterFlow(21),
|
|
valve(22),
|
|
status(23),
|
|
condensateDuration(24),
|
|
condensateCycles(25),
|
|
rpmFan4(26),
|
|
rpmFan5(27),
|
|
rpmFan6(28),
|
|
transfSwitch(29),
|
|
valveActValue(30)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
|
|
1: no sensor connected
|
|
2: sensor failure
|
|
3: value overflow
|
|
4: average temperature of air inlet to rack, average or max/min from each HEX
|
|
5: average temperature of air outlet from rack, average or max/min from each HEX
|
|
6: heatflow sensor
|
|
7: alarm:
|
|
Bit 0: Leakage
|
|
Bit 1: IIC Failure
|
|
8: warning:
|
|
Bit 0..2: Fan Tach 1..3
|
|
Bit 3,4: Temp. sensor HEX1 In,Out
|
|
Bit 5,6: Temp. sensor HEX2 In,Out
|
|
Bit 7,8: Temp. sensor HEX3 In,Out
|
|
Bit 9: Air temp. sensor
|
|
Bit 10..12: IIC failure, HEX1..3
|
|
Bit 13: Waterflow low
|
|
Bit 14,15: Watertemp. In,Out
|
|
Bit 16: Waterflow sensor fail.
|
|
Bit 17: Magnetic valve fail.
|
|
Bit 18: Leakdetector fail.
|
|
Bit 19: Uneven heat load
|
|
Bit 20: Condensation Pump Cycles > Max
|
|
Bit 21: Condensation Pump Running Time > Max
|
|
9: rpm speed of Fan1
|
|
10: rpm speed of Fan2
|
|
11: rpm speed of Fan3
|
|
12: fanSpeed setpoint, calculated from average temperatures
|
|
13: temperature air inlet to rack, HEX 1
|
|
14: temperature air outlet from rack, HEX 1
|
|
15: temperature air inlet to rack, HEX 1
|
|
16: temperature air outlet from rack, HEX 1
|
|
17: temperature air inlet to rack, HEX 1
|
|
18: temperature air outlet from rack, HEX 1
|
|
19: water temperature In
|
|
20: water temperature Out
|
|
21: water Flow
|
|
22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%)
|
|
23: status: Bit 0..Bit 2: fan module 1..3 available
|
|
Bit 3: water module available
|
|
24: condensation pump number of seconds on counter (last operating time)
|
|
25: condensation pump on/off cycle counter
|
|
26: rpm speed of Fan4
|
|
27: rpm speed of Fan5
|
|
28: rpm speed of Fan6
|
|
29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2
|
|
30: water valve actual value (%)"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 2 }
|
|
|
|
|
|
waterCoolUnitSensorText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for each sensor (entry in the table)"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 3 }
|
|
|
|
|
|
waterCoolUnitSensorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
warning(7),
|
|
tooLow(8),
|
|
tooHigh(9)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Actual status of the sensor"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 4 }
|
|
|
|
|
|
waterCoolUnitSensorValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)
|
|
|
|
If msg index = 1, 5 or 6
|
|
This value represents the actual Server Intake Temperature.
|
|
|
|
If msg index = 2:
|
|
This value represents the bit coded warning condition
|
|
Bit 0: Top Fan Module Failed
|
|
Bit 1: Middle Fan Module Failed
|
|
Bit 2: Bottom Fan Module Failed
|
|
Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed
|
|
Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed
|
|
Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed
|
|
Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed
|
|
Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed
|
|
Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed
|
|
Bit 9: Air Temperature Sensor Failed
|
|
Bit 10: Top Fan not installed
|
|
Bit 11: Middle Fan not installed
|
|
Bit 12: Bottom Fan not installed
|
|
Bit 13: Waterflow low
|
|
Bit 14: Water Unit Temperature Input Out of Range
|
|
Bit 15: Water Unit Temperature Output Out of Range
|
|
Bit 16: Waterflow Sensor Value Out of Range
|
|
Bit 17: Water Valve Failed
|
|
Bit 18: Leakdetector Failed
|
|
Bit 19: Heat Load Warning
|
|
Bit 20: The Condensation Pump has exceeded the max. number of cycles
|
|
Bit 21: The Condensation Pump has exceeded the max. Running Time
|
|
|
|
If msg index = 3:
|
|
This value represents the bit coded alarm condition
|
|
Bit 0: Leakage Detected
|
|
Bit 1: Comm. Failure IIC"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 5 }
|
|
|
|
|
|
waterCoolUnitSensorSetHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value for high setpoint of sensor"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 6 }
|
|
|
|
|
|
waterCoolUnitSensorSetLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value for low setpoint of sensor,
|
|
also used as alarm delay"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 7 }
|
|
|
|
|
|
waterCoolUnitSensorSetWarn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Value for warning setpoint of sensor,
|
|
also used as fan threshold"
|
|
::= { cpqWcrmWaterCoolUnitSensorEntry 8 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitNumberOfOutputs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of outputs available on sensor water cool unit"
|
|
::= { cpqWcrmStatusWaterCoolUnitOutputs 1 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitOutputEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Headline of output table"
|
|
::= { cpqWcrmStatusWaterCoolUnitOutputs 2 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitOutputEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmWaterCoolUnitOutputEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of output table"
|
|
INDEX { waterCoolUnitOutputIndex }
|
|
|
|
::= { cpqWcrmWaterCoolUnitOutputTable 1 }
|
|
|
|
cpqWcrmWaterCoolUnitOutputEntry ::=
|
|
SEQUENCE {
|
|
waterCoolUnitOutputIndex INTEGER,
|
|
waterCoolUnitOutputType INTEGER,
|
|
waterCoolUnitOutputText DisplayString,
|
|
waterCoolUnitOutputStatus INTEGER,
|
|
waterCoolUnitOutputValue INTEGER,
|
|
waterCoolUnitOutputSet INTEGER,
|
|
waterCoolUnitOutputConfig INTEGER,
|
|
waterCoolUnitOutputDelay INTEGER,
|
|
waterCoolUnitOutputTimeoutAction INTEGER
|
|
}
|
|
|
|
waterCoolUnitOutputIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the list of output entries. Its value ranges
|
|
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs."
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 1 }
|
|
|
|
|
|
waterCoolUnitOutputType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
failure(2),
|
|
overflow(3),
|
|
setpoint(4),
|
|
hysteresis(5),
|
|
command(6),
|
|
controlMode(7),
|
|
fanSpeedMin(8),
|
|
dTmin(9),
|
|
dTmax(10),
|
|
cpWatert(11),
|
|
setHeatload(12),
|
|
setEdoFlow(13),
|
|
setEdoHeat(14),
|
|
setCondCycles(15),
|
|
setCondRun(16),
|
|
doorControl(17),
|
|
pidContrKP(18),
|
|
pidContrKI(19),
|
|
pidContrKD(20),
|
|
pidSampleTime(21)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex]
|
|
1: no output connected
|
|
2: output failure
|
|
3: value overflow
|
|
4: water valve setpoint
|
|
5: water valve hysteresis
|
|
6: command for manual control
|
|
7: Flow Meter Model, 0=SIKA, 1=Chemline
|
|
8: minimum fan speed
|
|
9: min delta T, used for fan control
|
|
10: max delta T, used for fan control
|
|
11: specific heat capacity
|
|
12: setpoint heatload warning
|
|
13: setpoint Water Flow Loss Emergency Door Opening
|
|
14: setpoint High Temperature Emergency Door Opening
|
|
15: setpoint Condensation Pump Cycles (Warning)
|
|
16: setpoint Condensation Pump Running Time (Warning)
|
|
17: command for door opening, 0=lock door, 1=unlock door
|
|
18: KP parameter for PID controller
|
|
19: KI parameter for PID controller
|
|
20: KD parameter for PID controller
|
|
21: sampling time PID controller"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 2 }
|
|
|
|
|
|
waterCoolUnitOutputText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for each output (entry in the table)"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 3 }
|
|
|
|
|
|
waterCoolUnitOutputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
lost(2),
|
|
changed(3),
|
|
ok(4),
|
|
off(5),
|
|
on(6),
|
|
setOff(7),
|
|
setOn(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Actual status of the output"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 4 }
|
|
|
|
|
|
waterCoolUnitOutputValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Signed value for output"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 5 }
|
|
|
|
|
|
waterCoolUnitOutputSet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2),
|
|
lock(3),
|
|
unlock(4),
|
|
unlockDelay(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Command for output"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 6 }
|
|
|
|
|
|
waterCoolUnitOutputConfig OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disRemote(1),
|
|
enRemote(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Configuration for output
|
|
1: disable remote control (e.g. keypad)
|
|
2: enable remote control "
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 7 }
|
|
|
|
|
|
waterCoolUnitOutputDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Unsigned Value for delay,
|
|
after this time the output will fall into the previous state"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 8 }
|
|
|
|
|
|
waterCoolUnitOutputTimeoutAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
stay(1),
|
|
off(2),
|
|
on(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "State for output if timeout (RS422) occurs"
|
|
::= { cpqWcrmWaterCoolUnitOutputEntry 9 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitNumberOfMsgs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of alarms that can be created with water cool unit"
|
|
::= { cpqWcrmStatusWaterCoolUnitMsg 1 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitMsgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmWaterCoolUnitMsgEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Headline of message table"
|
|
::= { cpqWcrmStatusWaterCoolUnitMsg 2 }
|
|
|
|
|
|
cpqWcrmWaterCoolUnitMsgEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmWaterCoolUnitMsgEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of message table"
|
|
INDEX { waterCoolUnitMsgIndex }
|
|
|
|
::= { cpqWcrmWaterCoolUnitMsgTable 1 }
|
|
|
|
cpqWcrmWaterCoolUnitMsgEntry ::=
|
|
SEQUENCE {
|
|
waterCoolUnitMsgIndex INTEGER,
|
|
waterCoolUnitMsgText DisplayString,
|
|
waterCoolUnitMsgStatus INTEGER,
|
|
waterCoolUnitMsgRelay INTEGER,
|
|
waterCoolUnitMsgBeeper INTEGER,
|
|
waterCoolUnitMsgTrap1 INTEGER,
|
|
waterCoolUnitMsgTrap2 INTEGER,
|
|
waterCoolUnitMsgTrap3 INTEGER,
|
|
waterCoolUnitMsgTrap4 INTEGER,
|
|
waterCoolUnitMsgReset INTEGER
|
|
}
|
|
|
|
waterCoolUnitMsgIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the list of alarm entries. Its value ranges
|
|
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs."
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 1 }
|
|
|
|
|
|
waterCoolUnitMsgText OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Descriptional text for each message (entry in the table)"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 2 }
|
|
|
|
|
|
waterCoolUnitMsgStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notAvail(1),
|
|
configChanged(2),
|
|
error(3),
|
|
ok(4),
|
|
alarm(5),
|
|
warning(6),
|
|
tooLow(7),
|
|
tooHigh(8),
|
|
setOff(9),
|
|
setOn(10)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Actual message status
|
|
4: OK
|
|
5: alarm
|
|
6: warning
|
|
7: analog value too low, value reached low threshold
|
|
8: analog value too high, value reached high threshold"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 3 }
|
|
|
|
|
|
waterCoolUnitMsgRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Setup of Alarm relay for this alarm
|
|
2: no switching of alarm relay
|
|
1: switching of alarm relay"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 4 }
|
|
|
|
|
|
waterCoolUnitMsgBeeper OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Setup of Alarm beeper for this alarm
|
|
2: no audible alarm
|
|
1: audible alarm"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 5 }
|
|
|
|
|
|
waterCoolUnitMsgTrap1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 1 activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 6 }
|
|
|
|
|
|
waterCoolUnitMsgTrap2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 2 activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 7 }
|
|
|
|
|
|
waterCoolUnitMsgTrap3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 3 activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 8 }
|
|
|
|
|
|
waterCoolUnitMsgTrap4 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(1),
|
|
enable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Trap receiver 4 and Event Logging activated"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 9 }
|
|
|
|
|
|
waterCoolUnitMsgReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(1),
|
|
manual(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Reset of this alarm
|
|
1: auto
|
|
2: manual, alarm needs confirmation, e. g. with 'C' key"
|
|
::= { cpqWcrmWaterCoolUnitMsgEntry 10 }
|
|
|
|
|
|
cpqWcrmSetTempUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
celsius(1),
|
|
fahrenheit(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Unit of all temperature values and setpoints, Celsius or Fahrenheit"
|
|
::= { cpqWcrmSetupGeneral 1 }
|
|
|
|
|
|
cpqWcrmSetBeeper OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Audible alarm in Environmental Controller unit:
|
|
(2): beeper is on
|
|
(1): beeper is off (general)"
|
|
::= { cpqWcrmSetupGeneral 2 }
|
|
|
|
|
|
cpqWcrmResetRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Enable or disable acknowledging currently active alarm relay
|
|
(with 'C' on Environmental Controller)."
|
|
::= { cpqWcrmSetupGeneral 3 }
|
|
|
|
|
|
cpqWcrmLogicRelay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
closeAtAlarm(1),
|
|
openAtAlarm(2),
|
|
off(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Logic of alarm relay:
|
|
(1) Relay will pick up in case of an alarm
|
|
(2) Relay will release in case of an alarm
|
|
(3) Relay off (general)"
|
|
::= { cpqWcrmSetupGeneral 4 }
|
|
|
|
|
|
cpqWcrmWebAccess OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
viewOnly(1),
|
|
fullAccess(2),
|
|
off(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Web access via HTTP:
|
|
(1) view only
|
|
(2) full Access, read and set
|
|
(3) Web disabled (general)"
|
|
::= { cpqWcrmSetupGeneral 5 }
|
|
|
|
|
|
cpqWcrmSetupDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..10))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "actual Date in format DD.MM.YYYY"
|
|
::= { cpqWcrmSetupGeneral 6 }
|
|
|
|
|
|
cpqWcrmSetupTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)"
|
|
::= { cpqWcrmSetupGeneral 7 }
|
|
|
|
|
|
cpqWcrmTimerNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of value-table entries=number of outlets available on this unit"
|
|
::= { cpqWcrmTimerTable1 1 }
|
|
|
|
|
|
cpqWcrmTimerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmTimerEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Headline of status-table"
|
|
::= { cpqWcrmTimerTable1 2 }
|
|
|
|
|
|
cpqWcrmTimerEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmTimerEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of timer-table"
|
|
INDEX { cpqWcrmTimerIndex }
|
|
|
|
::= { cpqWcrmTimerTable 1 }
|
|
|
|
cpqWcrmTimerEntry ::=
|
|
SEQUENCE {
|
|
cpqWcrmTimerIndex INTEGER,
|
|
cpqWcrmTimerStatus INTEGER,
|
|
cpqWcrmTimerDayOfWeek INTEGER,
|
|
cpqWcrmTimeOn DisplayString,
|
|
cpqWcrmTimeOff DisplayString,
|
|
cpqWcrmTimeControl INTEGER,
|
|
cpqWcrmTimerFunction INTEGER
|
|
}
|
|
|
|
cpqWcrmTimerIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the list of timer entries. Its value ranges
|
|
between 1 and the value of cpqWcrmTimerNumber."
|
|
::= { cpqWcrmTimerEntry 1 }
|
|
|
|
|
|
cpqWcrmTimerStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
switchedOff(1),
|
|
switchedOn(2),
|
|
noTime(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Actual status of the timer"
|
|
::= { cpqWcrmTimerEntry 2 }
|
|
|
|
|
|
cpqWcrmTimerDayOfWeek OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sun(1),
|
|
mon(2),
|
|
tue(3),
|
|
wed(4),
|
|
thu(5),
|
|
fri(6),
|
|
sat(7),
|
|
sat-sun(8),
|
|
mon-fri(9),
|
|
mon-sun(10)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Selection of day of week for timer to switch"
|
|
::= { cpqWcrmTimerEntry 3 }
|
|
|
|
|
|
cpqWcrmTimeOn OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..5))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Time to switch on current function,
|
|
Format: HH:MM"
|
|
::= { cpqWcrmTimerEntry 4 }
|
|
|
|
|
|
cpqWcrmTimeOff OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..5))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Time to switch off current function,
|
|
Format: HH:MM"
|
|
::= { cpqWcrmTimerEntry 5 }
|
|
|
|
|
|
cpqWcrmTimeControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Control via RTC"
|
|
::= { cpqWcrmTimerEntry 6 }
|
|
|
|
|
|
cpqWcrmTimerFunction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disTrapRec1(1),
|
|
disTrapRec2(2),
|
|
disTrapRec3(3),
|
|
disTrapRec4(4),
|
|
schedule1(5),
|
|
schedule2(6),
|
|
schedule3(7),
|
|
schedule4(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Function which is controlled via timer
|
|
1-4: sending Traps to this Trap receiver will be disabled
|
|
5 - 8: scheduled alarm off"
|
|
::= { cpqWcrmTimerEntry 7 }
|
|
|
|
|
|
cpqWcrmSetFlowUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
literMin(1),
|
|
gallonMin(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Unit of Water Flow, Liter/min or Gallon/min"
|
|
::= { cpqWcrmSetupGeneral 9 }
|
|
|
|
|
|
cpqWcrmTraptableNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of trapTable entries. The number of trap-receiver"
|
|
::= { cpqWcrmTraps 1 }
|
|
|
|
|
|
cpqWcrmTrapTableTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CpqWcrmTrapTableEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A list of trap-receiver entries"
|
|
::= { cpqWcrmTraps 2 }
|
|
|
|
|
|
cpqWcrmTrapTableEntry OBJECT-TYPE
|
|
SYNTAX CpqWcrmTrapTableEntry
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Entries of trapTable"
|
|
INDEX { trapIndex }
|
|
|
|
::= { cpqWcrmTrapTableTable 1 }
|
|
|
|
cpqWcrmTrapTableEntry ::=
|
|
SEQUENCE {
|
|
trapIndex INTEGER,
|
|
trapStatus INTEGER,
|
|
trapIPaddress DisplayString
|
|
}
|
|
|
|
trapIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index for the trap-receiver-table. Its value ranges between
|
|
1 and the value of traptableNumber "
|
|
::= { cpqWcrmTrapTableEntry 1 }
|
|
|
|
|
|
trapStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Enable or disable trap receiver"
|
|
::= { cpqWcrmTrapTableEntry 2 }
|
|
|
|
|
|
trapIPaddress OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "IP-address of trap-receiver"
|
|
::= { cpqWcrmTrapTableEntry 3 }
|
|
|
|
|
|
cpqWcrmResetUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noReset(1),
|
|
reset(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Command to reset (acknowledge) alarms of Environmental Controller unit.
|
|
Setting to 'reset' (2) will have same result as pressing 'C' on Units.
|
|
Variable is automatically set back to 'noReset' (1)."
|
|
::= { cpqWcrmControl 1 }
|
|
|
|
|
|
alarmSensorInternal TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation, internalMsgIndex, internalMsgText, internalMsgStatus, internalSensorValue, cpqWcrmURL }
|
|
|
|
--#TYPE "Internal sensor alarm"
|
|
|
|
--#SUMMARY "Location: %s, Alarm[%d]: %s, Status: %d, Actual Value: %d, from: %s, contact %s, URL %s"
|
|
|
|
--#ARGUMENTS { 2, 3, 4, 5, 6, 1, 0, 7}
|
|
|
|
--#SEVERITY MAJOR
|
|
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
|
|
--#TIMEINDEX 99
|
|
DESCRIPTION "Internal Sensor Alarm"
|
|
::= 1
|
|
|
|
|
|
alarmSensorWaterCoolUnit TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation, waterCoolUnitMsgIndex, waterCoolUnitMsgText, waterCoolUnitMsgStatus, waterCoolUnitSensorValue, cpqWcrmURL }
|
|
|
|
--#TYPE "Water cool unit sensor alarm"
|
|
|
|
--#SUMMARY "Location: %s, Alarm[%d]: %s, Status: %d, Actual Value: %d, from: %s, contact %s, URL %s"
|
|
|
|
--#ARGUMENTS { 2, 3, 4, 5, 6, 1, 0, 7}
|
|
|
|
--#SEVERITY MAJOR
|
|
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
|
|
--#TIMEINDEX 99
|
|
DESCRIPTION "Water Cool Unit Sensor Alarm"
|
|
::= 2
|
|
|
|
|
|
alarmInternal TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation, cpqWcrmInternalText, cpqWcrmInternalStatus, cpqWcrmURL }
|
|
|
|
--#TYPE "Internal unit alarm"
|
|
|
|
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s, URL %s"
|
|
|
|
--#ARGUMENTS { 2, 3, 1, 0, 5}
|
|
|
|
--#SEVERITY MAJOR
|
|
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
|
|
--#TIMEINDEX 99
|
|
DESCRIPTION "Internal Unit Alarm"
|
|
::= 5
|
|
|
|
|
|
alarmWaterCoolUnit TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation, cpqWcrmWaterCoolUnitText, cpqWcrmWaterCoolUnitStatus, cpqWcrmURL }
|
|
|
|
--#TYPE "Water cool unit alarm"
|
|
|
|
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s, URL %s"
|
|
|
|
--#ARGUMENTS { 2, 3, 1, 0, 5}
|
|
|
|
--#SEVERITY MAJOR
|
|
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
|
|
--#TIMEINDEX 99
|
|
DESCRIPTION "Water Cool Unit System Alarm"
|
|
::= 6
|
|
|
|
|
|
testTrap TRAP-TYPE
|
|
ENTERPRISE cpqWcrm
|
|
VARIABLES { sysContact, sysName, sysLocation, cpqWcrmURL }
|
|
|
|
--#TYPE "Test Trap"
|
|
|
|
--#SUMMARY "Location: %s, Test Trap from unit %s was sent, contact %s, URL %s"
|
|
|
|
--#ARGUMENTS { 2, 1, 0, 3}
|
|
|
|
--#SEVERITY INFORMATIONAL
|
|
|
|
--#CATEGORY "SYSTEM AND ENVIRONMENTAL"
|
|
|
|
--#TIMEINDEX 99
|
|
DESCRIPTION "Test trap sent to a trap receiver to check proper reception of traps"
|
|
::= 10
|
|
|
|
END
|
|
|