LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, OBJECT-IDENTITY FROM SNMPv2-SMI liebertFlexibleConditionsModuleReg FROM LIEBERT-GP-REGISTRATION-MIB lgpFlexConditions FROM LIEBERT-GP-CONDITIONS-MIB ; -- ============================================================================= -- Module Identification and Registration -- ============================================================================= liebertGlobalProductsFlexibleConditionsModule MODULE-IDENTITY LAST-UPDATED "201308060000Z" ORGANIZATION "Liebert Corporation" CONTACT-INFO "Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@emerson.com Web: www.liebert.com" DESCRIPTION "The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification." REVISION "201308060000Z" DESCRIPTION "Compiled From GDD Version: 5924.1" ::= { liebertFlexibleConditionsModuleReg 1 } -- ============================================================================= -- lgpFlexConditions - Liebert Conditions Registrations -- ============================================================================= lgpFlexConditionsWellKnown OBJECT IDENTIFIER -- STATUS current -- DESCRIPTION -- "Liebert well known conditions are defined by OIDs that -- reside in this sub-tree." ::= { lgpFlexConditions 1 } -- ============================================================================= -- lgpFlexConditionsWellKnown - Liebert "well-known" Conditions -- ============================================================================= lgpCondId4122SystemInputPowerProblem OBJECT-IDENTITY STATUS current DESCRIPTION "The input is not qualified to provide power to the system." ::= { lgpFlexConditionsWellKnown 4122 } lgpCondId4132BypassOverloadPhaseA OBJECT-IDENTITY STATUS current DESCRIPTION "An overload exists on output phase A while operating on the bypass." ::= { lgpFlexConditionsWellKnown 4132 } lgpCondId4133BypassOverloadPhaseB OBJECT-IDENTITY STATUS current DESCRIPTION "An overload exists on output phase B while operating on the bypass." ::= { lgpFlexConditionsWellKnown 4133 } lgpCondId4134BypassOverloadPhaseC OBJECT-IDENTITY STATUS current DESCRIPTION "An overload exists on output phase C while operating on the bypass." ::= { lgpFlexConditionsWellKnown 4134 } lgpCondId4135BypassNotAvailable OBJECT-IDENTITY STATUS current DESCRIPTION "A problem associated with the bypass has been detected." ::= { lgpFlexConditionsWellKnown 4135 } lgpCondId4137BypassAutoRetransferPrimed OBJECT-IDENTITY STATUS current DESCRIPTION "Automatic retransfer from bypass to inverter is possible." ::= { lgpFlexConditionsWellKnown 4137 } lgpCondId4138BypassAutoRetransferFailed OBJECT-IDENTITY STATUS current DESCRIPTION "After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed." ::= { lgpFlexConditionsWellKnown 4138 } lgpCondId4139BypassExcessAutoRetransfers OBJECT-IDENTITY STATUS current DESCRIPTION "The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval." ::= { lgpFlexConditionsWellKnown 4139 } lgpCondId4140BypassRestartInhibitExternal OBJECT-IDENTITY STATUS current DESCRIPTION "Restart of the bypass is inhibited by the state of an external signal." ::= { lgpFlexConditionsWellKnown 4140 } lgpCondId4141BypassBreakerClosed OBJECT-IDENTITY STATUS current DESCRIPTION "The bypass breaker is closed." ::= { lgpFlexConditionsWellKnown 4141 } lgpCondId4142BypassStaticSwitchOverload OBJECT-IDENTITY STATUS current DESCRIPTION "Bypass off due to static switch overload." ::= { lgpFlexConditionsWellKnown 4142 } lgpCondId4143BypassStaticSwitchUnavailable OBJECT-IDENTITY STATUS current DESCRIPTION "The static bypass switch is off, and unable to operate." ::= { lgpFlexConditionsWellKnown 4143 } lgpCondId4144BypassExcessivePulseParallel OBJECT-IDENTITY STATUS current DESCRIPTION "The system has performed too many pulse parallel operations within a specified time interval." ::= { lgpFlexConditionsWellKnown 4144 } lgpCondId4145BypassAutoTransferFailed OBJECT-IDENTITY STATUS current DESCRIPTION "An automatic transfer to static bypass failed." ::= { lgpFlexConditionsWellKnown 4145 } lgpCondId4146SystemInputPhsRotationError OBJECT-IDENTITY STATUS current DESCRIPTION "The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C)." ::= { lgpFlexConditionsWellKnown 4146 } lgpCondId4147SystemInputCurrentLimit OBJECT-IDENTITY STATUS current DESCRIPTION "The RMS input current has reached the input current limit threshold." ::= { lgpFlexConditionsWellKnown 4147 } lgpCondId4162BatteryLow OBJECT-IDENTITY STATUS current DESCRIPTION "The calculated battery time remaining has reached the low battery threshold." ::= { lgpFlexConditionsWellKnown 4162 } lgpCondId4163OutputOffEndofDischarge OBJECT-IDENTITY STATUS current DESCRIPTION "Output turned off due to battery reaching end-of-discharge." ::= { lgpFlexConditionsWellKnown 4163 } lgpCondId4164BatteryChargingError OBJECT-IDENTITY STATUS current DESCRIPTION "The battery is not charging properly." ::= { lgpFlexConditionsWellKnown 4164 } lgpCondId4165BatteryChargingReducedExtrnl OBJECT-IDENTITY STATUS current DESCRIPTION "Using a reduced battery charging algorithm due to an external signal." ::= { lgpFlexConditionsWellKnown 4165 } lgpCondId4166BatteryCapacityLow OBJECT-IDENTITY STATUS current DESCRIPTION "Battery capacity is low." ::= { lgpFlexConditionsWellKnown 4166 } lgpCondId4167OutputOff OBJECT-IDENTITY STATUS current DESCRIPTION "Output is off." ::= { lgpFlexConditionsWellKnown 4167 } lgpCondId4168BatteryDischarging OBJECT-IDENTITY STATUS current DESCRIPTION "The battery is discharging." ::= { lgpFlexConditionsWellKnown 4168 } lgpCondId4169BatteryTemperatureImbalance OBJECT-IDENTITY STATUS current DESCRIPTION "Excessive temperature differences between battery sensors detected." ::= { lgpFlexConditionsWellKnown 4169 } lgpCondId4170BatteryEqualize OBJECT-IDENTITY STATUS current DESCRIPTION "The rectifier output voltage is increased to equalize the battery voltage level." ::= { lgpFlexConditionsWellKnown 4170 } lgpCondId4171BatteryManualTestInProgress OBJECT-IDENTITY STATUS current DESCRIPTION "Manual battery test is in progress." ::= { lgpFlexConditionsWellKnown 4171 } lgpCondId4172BatteryAutoTestInProgress OBJECT-IDENTITY STATUS current DESCRIPTION "Automatic battery test is in progress." ::= { lgpFlexConditionsWellKnown 4172 } lgpCondId4173MainBatteryDisconnectOpen OBJECT-IDENTITY STATUS current DESCRIPTION "Main battery disconnect is open." ::= { lgpFlexConditionsWellKnown 4173 } lgpCondId4174BatteryTemperatureSensorFault OBJECT-IDENTITY STATUS current DESCRIPTION "A battery temperature sensor fault has been detected." ::= { lgpFlexConditionsWellKnown 4174 } lgpCondId4175BypassFrequencyError OBJECT-IDENTITY STATUS current DESCRIPTION "The bypass frequency is outside the inverter synchronization limits." ::= { lgpFlexConditionsWellKnown 4175 } lgpCondId4176BatteryCircuitBreaker1Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 1 is open." ::= { lgpFlexConditionsWellKnown 4176 } lgpCondId4177BatteryBreaker1OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 1 failed to open." ::= { lgpFlexConditionsWellKnown 4177 } lgpCondId4178BatteryBreaker1CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 1 failed to close." ::= { lgpFlexConditionsWellKnown 4178 } lgpCondId4179BatteryCircuitBreaker2Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 2 is open." ::= { lgpFlexConditionsWellKnown 4179 } lgpCondId4180BatteryBreaker2OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 2 failed to open." ::= { lgpFlexConditionsWellKnown 4180 } lgpCondId4181BatteryBreaker2CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 2 failed to close." ::= { lgpFlexConditionsWellKnown 4181 } lgpCondId4182BatteryCircuitBreaker3Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 3 is open." ::= { lgpFlexConditionsWellKnown 4182 } lgpCondId4183BatteryBreaker3OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 3 failed to open." ::= { lgpFlexConditionsWellKnown 4183 } lgpCondId4184BatteryBreaker3CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 3 failed to close." ::= { lgpFlexConditionsWellKnown 4184 } lgpCondId4185BatteryCircuitBreaker4Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 4 is open." ::= { lgpFlexConditionsWellKnown 4185 } lgpCondId4186BatteryBreaker4OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 4 failed to open." ::= { lgpFlexConditionsWellKnown 4186 } lgpCondId4187BatteryBreaker4CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 4 failed to close." ::= { lgpFlexConditionsWellKnown 4187 } lgpCondId4188BatteryCircuitBreaker5Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 5 is open." ::= { lgpFlexConditionsWellKnown 4188 } lgpCondId4189BatteryBreaker5OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 5 failed to open." ::= { lgpFlexConditionsWellKnown 4189 } lgpCondId4190BatteryBreaker5CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 5 failed to close." ::= { lgpFlexConditionsWellKnown 4190 } lgpCondId4191BatteryCircuitBreaker6Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 6 is open." ::= { lgpFlexConditionsWellKnown 4191 } lgpCondId4192BatteryBreaker6OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 6 failed to open." ::= { lgpFlexConditionsWellKnown 4192 } lgpCondId4193BatteryBreaker6CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 6 failed to close." ::= { lgpFlexConditionsWellKnown 4193 } lgpCondId4194BatteryCircuitBreaker7Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 7 is open." ::= { lgpFlexConditionsWellKnown 4194 } lgpCondId4195BatteryBreaker7OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 7 failed to open." ::= { lgpFlexConditionsWellKnown 4195 } lgpCondId4196BatteryBreaker7CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 7 failed to close." ::= { lgpFlexConditionsWellKnown 4196 } lgpCondId4197BatteryCircuitBreaker8Open OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 8 is open." ::= { lgpFlexConditionsWellKnown 4197 } lgpCondId4198BatteryBreaker8OpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 8 failed to open." ::= { lgpFlexConditionsWellKnown 4198 } lgpCondId4199BatteryBreaker8CloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery circuit breaker 8 failed to close." ::= { lgpFlexConditionsWellKnown 4199 } lgpCondId4200BatteryChargingInhibited OBJECT-IDENTITY STATUS current DESCRIPTION "Battery charging is inhibited due to an external inhibit signal." ::= { lgpFlexConditionsWellKnown 4200 } lgpCondId4213SystemShutdownEPO OBJECT-IDENTITY STATUS current DESCRIPTION "System shutdown due to Emergency Power Off (EPO)." ::= { lgpFlexConditionsWellKnown 4213 } lgpCondId4214SystemShutdownREPO OBJECT-IDENTITY STATUS current DESCRIPTION "System shutdown due to Remote Emergency Power Off (REPO)." ::= { lgpFlexConditionsWellKnown 4214 } lgpCondId4215SystemOutputOff OBJECT-IDENTITY STATUS current DESCRIPTION "The system output is off." ::= { lgpFlexConditionsWellKnown 4215 } lgpCondId4216BypassBackfeedDetected OBJECT-IDENTITY STATUS current DESCRIPTION "The system detected a voltage on the bypass when none was expected." ::= { lgpFlexConditionsWellKnown 4216 } lgpCondId4217BypassManualXfrInhibited OBJECT-IDENTITY STATUS current DESCRIPTION "Manual transfer from inverter to bypass is inhibited - bypass not qualified." ::= { lgpFlexConditionsWellKnown 4217 } lgpCondId4218BypassManualRexfrInhibited OBJECT-IDENTITY STATUS current DESCRIPTION "Manual transfer from bypass to inverter is inhibited - inverter output not qualified." ::= { lgpFlexConditionsWellKnown 4218 } lgpCondId4219BatteryOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "A battery temperature sensor is reporting a value above a threshold." ::= { lgpFlexConditionsWellKnown 4219 } lgpCondId4220BatteryExternalMonitor1 OBJECT-IDENTITY STATUS current DESCRIPTION "External battery monitor 1 - battery maintenance required." ::= { lgpFlexConditionsWellKnown 4220 } lgpCondId4221BatteryExternalMonitor2 OBJECT-IDENTITY STATUS current DESCRIPTION "External battery monitor 2 - battery maintenance required." ::= { lgpFlexConditionsWellKnown 4221 } lgpCondId4222BatteryGroundFault OBJECT-IDENTITY STATUS current DESCRIPTION "Battery system ground fault amperage exceeds the threshold." ::= { lgpFlexConditionsWellKnown 4222 } lgpCondId4229EmergencyPowerOffLatched OBJECT-IDENTITY STATUS current DESCRIPTION "System output is off - 'Emergency Power Off (EPO) - latched' requires manual reset." ::= { lgpFlexConditionsWellKnown 4229 } lgpCondId4230SystemOutputLowPowerFactor OBJECT-IDENTITY STATUS current DESCRIPTION "The system output power factor is low, resulting in reduced output capacity." ::= { lgpFlexConditionsWellKnown 4230 } lgpCondId4231OutputCurrentExceedsThreshold OBJECT-IDENTITY STATUS current DESCRIPTION "Output current for one or more phases exceeds a threshold." ::= { lgpFlexConditionsWellKnown 4231 } lgpCondId4233InverterFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter failure - inverter output is off." ::= { lgpFlexConditionsWellKnown 4233 } lgpCondId4234InverterOverloadPhaseA OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter is operating with an overload on phase A." ::= { lgpFlexConditionsWellKnown 4234 } lgpCondId4235InverterOverloadPhaseB OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter is operating with an overload on phase B." ::= { lgpFlexConditionsWellKnown 4235 } lgpCondId4236InverterOverloadPhaseC OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter is operating with an overload on phase C." ::= { lgpFlexConditionsWellKnown 4236 } lgpCondId4237InverterInhibitExternal OBJECT-IDENTITY STATUS current DESCRIPTION "Restart of the inverter is inhibited by an external signal." ::= { lgpFlexConditionsWellKnown 4237 } lgpCondId4238InverterOutBreakerOpenFail OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter output breaker failed to open." ::= { lgpFlexConditionsWellKnown 4238 } lgpCondId4239InverterOutBreakerCloseFail OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter output breaker failed to close." ::= { lgpFlexConditionsWellKnown 4239 } lgpCondId4270InputContact01 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 1." ::= { lgpFlexConditionsWellKnown 4270 } lgpCondId4271InputContact02 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 2." ::= { lgpFlexConditionsWellKnown 4271 } lgpCondId4272InputContact03 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 3." ::= { lgpFlexConditionsWellKnown 4272 } lgpCondId4273InputContact04 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 4." ::= { lgpFlexConditionsWellKnown 4273 } lgpCondId4274InputContact05 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 5." ::= { lgpFlexConditionsWellKnown 4274 } lgpCondId4275InputContact06 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 6." ::= { lgpFlexConditionsWellKnown 4275 } lgpCondId4276InputContact07 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 7." ::= { lgpFlexConditionsWellKnown 4276 } lgpCondId4277InputContact08 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 8." ::= { lgpFlexConditionsWellKnown 4277 } lgpCondId4278InputContact09 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 9." ::= { lgpFlexConditionsWellKnown 4278 } lgpCondId4279InputContact10 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 10." ::= { lgpFlexConditionsWellKnown 4279 } lgpCondId4280InputContact11 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 11." ::= { lgpFlexConditionsWellKnown 4280 } lgpCondId4281InputContact12 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 12." ::= { lgpFlexConditionsWellKnown 4281 } lgpCondId4282InputContact13 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 13." ::= { lgpFlexConditionsWellKnown 4282 } lgpCondId4283InputContact14 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 14." ::= { lgpFlexConditionsWellKnown 4283 } lgpCondId4284InputContact15 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 15." ::= { lgpFlexConditionsWellKnown 4284 } lgpCondId4285InputContact16 OBJECT-IDENTITY STATUS current DESCRIPTION "The external input contact 16." ::= { lgpFlexConditionsWellKnown 4285 } lgpCondId4286OutputAmpOverUserLimitPhsA OBJECT-IDENTITY STATUS current DESCRIPTION "The phase A output has exceeded the user amperage threshold." ::= { lgpFlexConditionsWellKnown 4286 } lgpCondId4287OutputAmpOverUserLimitPhsB OBJECT-IDENTITY STATUS current DESCRIPTION "The phase B output has exceeded the user amperage threshold." ::= { lgpFlexConditionsWellKnown 4287 } lgpCondId4288OutputAmpOverUserLimitPhsC OBJECT-IDENTITY STATUS current DESCRIPTION "The phase C output has exceeded the user amperage threshold." ::= { lgpFlexConditionsWellKnown 4288 } lgpCondId4289InverterTransferInhibitExt OBJECT-IDENTITY STATUS current DESCRIPTION "Transfer of critical bus source to inverter is inhibited by an external signal." ::= { lgpFlexConditionsWellKnown 4289 } lgpCondId4290InverterShutdownOverload OBJECT-IDENTITY STATUS current DESCRIPTION "The inverter has shutdown due to a sustained overload." ::= { lgpFlexConditionsWellKnown 4290 } lgpCondId4294InletAirOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The inlet air exceeds the maximum temperature threshold." ::= { lgpFlexConditionsWellKnown 4294 } lgpCondId4295RectifierFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Rectifier failure - rectifier is off." ::= { lgpFlexConditionsWellKnown 4295 } lgpCondId4296RectifierOperationInhibitExt OBJECT-IDENTITY STATUS current DESCRIPTION "The operation of the rectifier is inhibited by an external signal." ::= { lgpFlexConditionsWellKnown 4296 } lgpCondId4297UPSOutputonInverter OBJECT-IDENTITY STATUS current DESCRIPTION "The output power is supplied by the inverter." ::= { lgpFlexConditionsWellKnown 4297 } lgpCondId4298UPSOutputonBypass OBJECT-IDENTITY STATUS current DESCRIPTION "The output power is supplied by the bypass." ::= { lgpFlexConditionsWellKnown 4298 } lgpCondId4299OutputLoadonMaintBypass OBJECT-IDENTITY STATUS current DESCRIPTION "The output power is supplied by the maintenance bypass." ::= { lgpFlexConditionsWellKnown 4299 } lgpCondId4300InternalCommunicationsFailure OBJECT-IDENTITY STATUS current DESCRIPTION "The control has detected a communication failure of a component on the internal communication bus." ::= { lgpFlexConditionsWellKnown 4300 } lgpCondId4308DCBusGroundFaultPositive OBJECT-IDENTITY STATUS current DESCRIPTION "A ground fault has been detected on the positive DC Bus link." ::= { lgpFlexConditionsWellKnown 4308 } lgpCondId4309DCBusGroundFaultNegative OBJECT-IDENTITY STATUS current DESCRIPTION "A ground fault has been detected on the negative DC Bus link." ::= { lgpFlexConditionsWellKnown 4309 } lgpCondId4310EquipmentOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Equipment over temperature summary event." ::= { lgpFlexConditionsWellKnown 4310 } lgpCondId4311SystemFanFailure OBJECT-IDENTITY STATUS current DESCRIPTION "System fan failure - one or more fans have failed." ::= { lgpFlexConditionsWellKnown 4311 } lgpCondId4313PasswordChanged OBJECT-IDENTITY STATUS current DESCRIPTION "Password changed." ::= { lgpFlexConditionsWellKnown 4313 } lgpCondId4314PowerSupplyFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Power supply failure." ::= { lgpFlexConditionsWellKnown 4314 } lgpCondId4315OnGenerator OBJECT-IDENTITY STATUS current DESCRIPTION "A generator is supplying the power to the system." ::= { lgpFlexConditionsWellKnown 4315 } lgpCondId4316AutoRestartInProgress OBJECT-IDENTITY STATUS current DESCRIPTION "Auto restart is in progress." ::= { lgpFlexConditionsWellKnown 4316 } lgpCondId4317AutoRestartInhibitedExt OBJECT-IDENTITY STATUS current DESCRIPTION "Auto restart inhibited due to an external signal." ::= { lgpFlexConditionsWellKnown 4317 } lgpCondId4320InitiatedTransfertoBypass OBJECT-IDENTITY STATUS current DESCRIPTION "User initiated manual transfer to bypass." ::= { lgpFlexConditionsWellKnown 4320 } lgpCondId4321InitiatedTransfertoInverter OBJECT-IDENTITY STATUS current DESCRIPTION "User initiated manual transfer to inverter." ::= { lgpFlexConditionsWellKnown 4321 } lgpCondId4322BatteryTestPassed OBJECT-IDENTITY STATUS current DESCRIPTION "Battery test passed." ::= { lgpFlexConditionsWellKnown 4322 } lgpCondId4323BatteryTestFailed OBJECT-IDENTITY STATUS current DESCRIPTION "Battery test failed." ::= { lgpFlexConditionsWellKnown 4323 } lgpCondId4324BatteryTestManuallyStopped OBJECT-IDENTITY STATUS current DESCRIPTION "The battery test was manually stopped prior to completion." ::= { lgpFlexConditionsWellKnown 4324 } lgpCondId4325BackfeedBreakerOpen OBJECT-IDENTITY STATUS current DESCRIPTION "The backfeed breaker is in the open position." ::= { lgpFlexConditionsWellKnown 4325 } lgpCondId4341VelocityAuthenticationFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Notification of a message rejected by Velocity due to an authentication failure." ::= { lgpFlexConditionsWellKnown 4341 } lgpCondId4360ReceptacleOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a receptacle over current condition." ::= { lgpFlexConditionsWellKnown 4360 } lgpCondId4361ReceptacleUnderCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a receptacle under current condition." ::= { lgpFlexConditionsWellKnown 4361 } lgpCondId4382SystemInputCurrentImbalance OBJECT-IDENTITY STATUS current DESCRIPTION "System Input Currents are Imbalanced." ::= { lgpFlexConditionsWellKnown 4382 } lgpCondId4383BypassStaticSwitchOffExtrnl OBJECT-IDENTITY STATUS current DESCRIPTION "Bypass static switch is off due to the state of an external signal." ::= { lgpFlexConditionsWellKnown 4383 } lgpCondId4384BatteryEoDDisconnect OBJECT-IDENTITY STATUS current DESCRIPTION "Battery disconnect due to end-of-discharge." ::= { lgpFlexConditionsWellKnown 4384 } lgpCondId4389SystemOutputFault OBJECT-IDENTITY STATUS current DESCRIPTION "A fault has been detected in the system output." ::= { lgpFlexConditionsWellKnown 4389 } lgpCondId4390InverterOffExternal OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter is off (operation is inhibited) due to external signal state." ::= { lgpFlexConditionsWellKnown 4390 } lgpCondId4391InverterStaticSwitchSCRShort OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR)." ::= { lgpFlexConditionsWellKnown 4391 } lgpCondId4392TemperatureSensorError OBJECT-IDENTITY STATUS current DESCRIPTION "One or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc)." ::= { lgpFlexConditionsWellKnown 4392 } lgpCondId4406BranchOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module over current condition." ::= { lgpFlexConditionsWellKnown 4406 } lgpCondId4407BranchUnderCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under current condition." ::= { lgpFlexConditionsWellKnown 4407 } lgpCondId4416BranchOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module over current condition." ::= { lgpFlexConditionsWellKnown 4416 } lgpCondId4417BranchUnderCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under current condition." ::= { lgpFlexConditionsWellKnown 4417 } lgpCondId4421BranchFailure OBJECT-IDENTITY STATUS current DESCRIPTION "One or more conditions indicate a Branch Receptacle Module failure , service is required." ::= { lgpFlexConditionsWellKnown 4421 } lgpCondId4436PDUOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module over current condition." ::= { lgpFlexConditionsWellKnown 4436 } lgpCondId4437PDUUnderCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under current condition." ::= { lgpFlexConditionsWellKnown 4437 } lgpCondId4438SystemInternalTemperatureRise OBJECT-IDENTITY STATUS current DESCRIPTION "Excessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large)." ::= { lgpFlexConditionsWellKnown 4438 } lgpCondId4439AutomaticRestartFailed OBJECT-IDENTITY STATUS current DESCRIPTION "Automatic restart failed." ::= { lgpFlexConditionsWellKnown 4439 } lgpCondId4440FuseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "A summary event indicating one or more fuse failures." ::= { lgpFlexConditionsWellKnown 4440 } lgpCondId4441SystemControllerError OBJECT-IDENTITY STATUS current DESCRIPTION "System controller internal error." ::= { lgpFlexConditionsWellKnown 4441 } lgpCondId4442SystemBreakersOpenFailure OBJECT-IDENTITY STATUS current DESCRIPTION "One or more breakers in the system failed to open." ::= { lgpFlexConditionsWellKnown 4442 } lgpCondId4448PDUOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module over current condition." ::= { lgpFlexConditionsWellKnown 4448 } lgpCondId4449PDUUnderCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under current condition." ::= { lgpFlexConditionsWellKnown 4449 } lgpCondId4468PDUOverCurrentL1 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module over current condition on line 1." ::= { lgpFlexConditionsWellKnown 4468 } lgpCondId4469PDUOverCurrentL2 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module over current condition on line 2." ::= { lgpFlexConditionsWellKnown 4469 } lgpCondId4470PDUOverCurrentL3 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module over current condition on line 3." ::= { lgpFlexConditionsWellKnown 4470 } lgpCondId4471PDUUnderCurrentL1 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under current condition on line 1." ::= { lgpFlexConditionsWellKnown 4471 } lgpCondId4472PDUUnderCurrentL2 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under current condition on line 2." ::= { lgpFlexConditionsWellKnown 4472 } lgpCondId4473PDUUnderCurrentL3 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under current condition on line 3." ::= { lgpFlexConditionsWellKnown 4473 } lgpCondId4492ReceptaclePowerStateOn OBJECT-IDENTITY STATUS current DESCRIPTION "The receptacle power state changed to the ON state." ::= { lgpFlexConditionsWellKnown 4492 } lgpCondId4493ReceptaclePowerStateOff OBJECT-IDENTITY STATUS current DESCRIPTION "The receptacle power state changed to the OFF state." ::= { lgpFlexConditionsWellKnown 4493 } lgpCondId4494BranchBreakerOpen OBJECT-IDENTITY STATUS current DESCRIPTION "The Branch Receptacle Module's input breaker is open." ::= { lgpFlexConditionsWellKnown 4494 } lgpCondId4495DeviceConfigurationChange OBJECT-IDENTITY STATUS current DESCRIPTION "Device Configuration Change." ::= { lgpFlexConditionsWellKnown 4495 } lgpCondId4496BasicDisplayModuleRemoved OBJECT-IDENTITY STATUS current DESCRIPTION "Basic Display Module Removed." ::= { lgpFlexConditionsWellKnown 4496 } lgpCondId4497BasicDisplayModuleDiscovered OBJECT-IDENTITY STATUS current DESCRIPTION "Basic Display Module Discovered." ::= { lgpFlexConditionsWellKnown 4497 } lgpCondId4500PDUOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a power module over current condition." ::= { lgpFlexConditionsWellKnown 4500 } lgpCondId4501PDUUnderCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a power module under current condition." ::= { lgpFlexConditionsWellKnown 4501 } lgpCondId4502PDUFailure OBJECT-IDENTITY STATUS current DESCRIPTION "One or more conditions indicate a power module failure, service is required." ::= { lgpFlexConditionsWellKnown 4502 } lgpCondId4503PDUCommunicationFail OBJECT-IDENTITY STATUS current DESCRIPTION "Internal communications failure with the Power Module." ::= { lgpFlexConditionsWellKnown 4503 } lgpCondId4504BranchRemoved OBJECT-IDENTITY STATUS current DESCRIPTION "Branch Receptacle Module Removed." ::= { lgpFlexConditionsWellKnown 4504 } lgpCondId4505BranchDiscovered OBJECT-IDENTITY STATUS current DESCRIPTION "Branch Receptacle Module Discovered." ::= { lgpFlexConditionsWellKnown 4505 } lgpCondId4506BranchOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a Branch Receptacle Module over current condition." ::= { lgpFlexConditionsWellKnown 4506 } lgpCondId4507BranchCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a Branch Receptacle Module under current condition." ::= { lgpFlexConditionsWellKnown 4507 } lgpCondId4508ReceptacleLoadRemoved OBJECT-IDENTITY STATUS current DESCRIPTION "The receptacle's load stopped drawing power." ::= { lgpFlexConditionsWellKnown 4508 } lgpCondId4509ReceptacleLoadAdded OBJECT-IDENTITY STATUS current DESCRIPTION "The receptacle's load started to draw power." ::= { lgpFlexConditionsWellKnown 4509 } lgpCondId4523ModuleRemoved OBJECT-IDENTITY STATUS current DESCRIPTION "Module Removed." ::= { lgpFlexConditionsWellKnown 4523 } lgpCondId4524ModuleAdded OBJECT-IDENTITY STATUS current DESCRIPTION "Module Added." ::= { lgpFlexConditionsWellKnown 4524 } lgpCondId4550FirmwareUpdateRequired OBJECT-IDENTITY STATUS current DESCRIPTION "Module compatibility error requires a system firmware update to resolve." ::= { lgpFlexConditionsWellKnown 4550 } lgpCondId4551GenericTestEvent OBJECT-IDENTITY STATUS current DESCRIPTION "A generic test event designed to evaluate system handling of events." ::= { lgpFlexConditionsWellKnown 4551 } lgpCondId4580OverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "An over temperature condition was detected." ::= { lgpFlexConditionsWellKnown 4580 } lgpCondId4581UnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "An under temperature condition was detected." ::= { lgpFlexConditionsWellKnown 4581 } lgpCondId4588OverRelativeHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "An over relative humidity condition was detected." ::= { lgpFlexConditionsWellKnown 4588 } lgpCondId4589UnderRelativeHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "An under relative humidity condition was detected." ::= { lgpFlexConditionsWellKnown 4589 } lgpCondId4601ExternalAirSensorAOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 4601 } lgpCondId4604ExternalAirSensorBOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 4604 } lgpCondId4608ExtAirSensorAUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 4608 } lgpCondId4611ExtAirSensorBUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 4611 } lgpCondId4615ExtDewPointOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 4615 } lgpCondId4618ExternalAirSensorAIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The external air sensor A is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 4618 } lgpCondId4621ExternalAirSensorBIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The external air sensor B is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 4621 } lgpCondId4626SupplyChilledWaterOverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Chilled Water Temperature] has exceeded [Supply Chilled Water Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 4626 } lgpCondId4629SupplyChilledWaterTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The supply chilled water temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 4629 } lgpCondId4634SupplyRefrigerantOverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold." ::= { lgpFlexConditionsWellKnown 4634 } lgpCondId4637SupplyRefrigerantUnderTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Refrigerant Temperature] has dropped below a specified threshold." ::= { lgpFlexConditionsWellKnown 4637 } lgpCondId4640SupplyRefrigerantTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The supply refrigeramt temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 4640 } lgpCondId4645SupplyFluidOverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 4645 } lgpCondId4648SupplyFluidUnderTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Fluid Temperature] has dropped below a specified threshold." ::= { lgpFlexConditionsWellKnown 4648 } lgpCondId4651SupplyFluidTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The supply fluid temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 4651 } lgpCondId4656Pump1LossofFlow OBJECT-IDENTITY STATUS current DESCRIPTION "Loss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump." ::= { lgpFlexConditionsWellKnown 4656 } lgpCondId4659Pump2LossofFlow OBJECT-IDENTITY STATUS current DESCRIPTION "Loss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump." ::= { lgpFlexConditionsWellKnown 4659 } lgpCondId4662PumpShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Pumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 4662 } lgpCondId4669Compressor1AHighHeadPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 1A high head pressure." ::= { lgpFlexConditionsWellKnown 4669 } lgpCondId4672Compressor1BHighHeadPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 1B high head pressure." ::= { lgpFlexConditionsWellKnown 4672 } lgpCondId4675Compressor2AHighHeadPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 2A high head pressure." ::= { lgpFlexConditionsWellKnown 4675 } lgpCondId4678Compressor2BHighHeadPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 2B high head pressure." ::= { lgpFlexConditionsWellKnown 4678 } lgpCondId4681Compressor1AShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 4681 } lgpCondId4684Compressor1BShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 4684 } lgpCondId4687Compressor2AShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 4687 } lgpCondId4690Compressor2BShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 4690 } lgpCondId4693Tandem1LowSuctionPressure OBJECT-IDENTITY STATUS current DESCRIPTION "'Tandem compressors' 1 low suction pressure." ::= { lgpFlexConditionsWellKnown 4693 } lgpCondId4696Tandem2LowSuctionPressure OBJECT-IDENTITY STATUS current DESCRIPTION "'Tandem compressors' 2 low suction pressure." ::= { lgpFlexConditionsWellKnown 4696 } lgpCondId4703ChilledWaterControlValvePosition OBJECT-IDENTITY STATUS current DESCRIPTION "Chilled water valve out of position. Chilled water control valve position does not match expected value." ::= { lgpFlexConditionsWellKnown 4703 } lgpCondId4711SystemCondensationDetected OBJECT-IDENTITY STATUS current DESCRIPTION "System condensation detected." ::= { lgpFlexConditionsWellKnown 4711 } lgpCondId4714ShutdownLossOfPower OBJECT-IDENTITY STATUS current DESCRIPTION "System lost power. This event becomes active when the unit is powered on following an unexpected loss of power." ::= { lgpFlexConditionsWellKnown 4714 } lgpCondId4720SmokeDetected OBJECT-IDENTITY STATUS current DESCRIPTION "Smoke detected." ::= { lgpFlexConditionsWellKnown 4720 } lgpCondId4723WaterUnderFloor OBJECT-IDENTITY STATUS current DESCRIPTION "Water under the floor is detected." ::= { lgpFlexConditionsWellKnown 4723 } lgpCondId4726ServiceRequired OBJECT-IDENTITY STATUS current DESCRIPTION "Unit requires servicing." ::= { lgpFlexConditionsWellKnown 4726 } lgpCondId4729FanIssue OBJECT-IDENTITY STATUS current DESCRIPTION "One or more fans are not operating within their operational parameters." ::= { lgpFlexConditionsWellKnown 4729 } lgpCondId4732ReceptacleLoadDropped OBJECT-IDENTITY STATUS current DESCRIPTION "The receptacle's load is not drawing power." ::= { lgpFlexConditionsWellKnown 4732 } lgpCondId4740BatteryAutomaticTestInhibited OBJECT-IDENTITY STATUS current DESCRIPTION "Automatic (scheduled) battery tests are inhibited." ::= { lgpFlexConditionsWellKnown 4740 } lgpCondId4741BatterySelfTest OBJECT-IDENTITY STATUS current DESCRIPTION "Battery self test is in progress." ::= { lgpFlexConditionsWellKnown 4741 } lgpCondId4742BatteryLowShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "Battery disconnect due to end-of-discharge." ::= { lgpFlexConditionsWellKnown 4742 } lgpCondId4747EquipmentTemperatureSensorFail OBJECT-IDENTITY STATUS current DESCRIPTION "One or more temperature sensors report a temperature outside of the range of expected operation." ::= { lgpFlexConditionsWellKnown 4747 } lgpCondId4749SystemFanFailureRedundant OBJECT-IDENTITY STATUS current DESCRIPTION "Redundant system fan failure." ::= { lgpFlexConditionsWellKnown 4749 } lgpCondId4750MultipleFanFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Multiple fan failure." ::= { lgpFlexConditionsWellKnown 4750 } lgpCondId4753MainControllerFault OBJECT-IDENTITY STATUS current DESCRIPTION "A Main Controller fault has been detected." ::= { lgpFlexConditionsWellKnown 4753 } lgpCondId4754SystemBreakersCloseFailure OBJECT-IDENTITY STATUS current DESCRIPTION "One or more breakers in the system failed to close." ::= { lgpFlexConditionsWellKnown 4754 } lgpCondId4755InputFilterCycleLock OBJECT-IDENTITY STATUS current DESCRIPTION "The input filter disconnect is open due to exceeding the maximum number of cycles." ::= { lgpFlexConditionsWellKnown 4755 } lgpCondId4756ServiceCodeActive OBJECT-IDENTITY STATUS current DESCRIPTION "Service code is running." ::= { lgpFlexConditionsWellKnown 4756 } lgpCondId4757LBSActive OBJECT-IDENTITY STATUS current DESCRIPTION "The Load Bus Sync option is active." ::= { lgpFlexConditionsWellKnown 4757 } lgpCondId4758LBSInhibited OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected that conditions to perform Load Bus Sync are not satisfied." ::= { lgpFlexConditionsWellKnown 4758 } lgpCondId4759LeadingPowerFactor OBJECT-IDENTITY STATUS current DESCRIPTION "The leading output Power Factor has fallen below a specified value." ::= { lgpFlexConditionsWellKnown 4759 } lgpCondId4760ControlsResetRequired OBJECT-IDENTITY STATUS current DESCRIPTION "A controls reset is required due to one or more critical settings changing." ::= { lgpFlexConditionsWellKnown 4760 } lgpCondId4823ParallelCommWarning OBJECT-IDENTITY STATUS current DESCRIPTION "Parallel communication bus warning." ::= { lgpFlexConditionsWellKnown 4823 } lgpCondId4824SystemCommFail OBJECT-IDENTITY STATUS current DESCRIPTION "Failure of a device on the multi-module system communication bus." ::= { lgpFlexConditionsWellKnown 4824 } lgpCondId4825LossofRedundancy OBJECT-IDENTITY STATUS current DESCRIPTION "The multi-module collection doesn't have enough modules to redundantly support the load." ::= { lgpFlexConditionsWellKnown 4825 } lgpCondId4826BPSSStartupInhibit OBJECT-IDENTITY STATUS current DESCRIPTION "The Bypass Static Switch startup is inhibited." ::= { lgpFlexConditionsWellKnown 4826 } lgpCondId4827MMSTransferInhibit OBJECT-IDENTITY STATUS current DESCRIPTION "The critical load can not be manually transferred from inverter to bypass." ::= { lgpFlexConditionsWellKnown 4827 } lgpCondId4828MMSRetransferInhibit OBJECT-IDENTITY STATUS current DESCRIPTION "The critical load can not be manually retransferred from bypass to inverter." ::= { lgpFlexConditionsWellKnown 4828 } lgpCondId4830MMSLossofSyncPulse OBJECT-IDENTITY STATUS current DESCRIPTION "Multi-module system loss of sync pulse." ::= { lgpFlexConditionsWellKnown 4830 } lgpCondId4831MMSOverload OBJECT-IDENTITY STATUS current DESCRIPTION "Multi-module system overload." ::= { lgpFlexConditionsWellKnown 4831 } lgpCondId4834MMSOnBattery OBJECT-IDENTITY STATUS current DESCRIPTION "The multi-module system is on battery." ::= { lgpFlexConditionsWellKnown 4834 } lgpCondId4835MMSLowBatteryWarning OBJECT-IDENTITY STATUS current DESCRIPTION "Multi-module system low battery warning." ::= { lgpFlexConditionsWellKnown 4835 } lgpCondId4906LowAmbientTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low ambient temperature condition." ::= { lgpFlexConditionsWellKnown 4906 } lgpCondId4907HighAmbientTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high ambient temperature condition." ::= { lgpFlexConditionsWellKnown 4907 } lgpCondId4908LowOverallVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low battery string overall voltage condition." ::= { lgpFlexConditionsWellKnown 4908 } lgpCondId4909HighOverallVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high battery string overall voltage condition." ::= { lgpFlexConditionsWellKnown 4909 } lgpCondId4910HighBatteryStringCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high battery string current condition." ::= { lgpFlexConditionsWellKnown 4910 } lgpCondId4911LowBatteryStringFloatCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low battery string float current condition." ::= { lgpFlexConditionsWellKnown 4911 } lgpCondId4912HighBatteryStringFloatCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high battery string float current condition." ::= { lgpFlexConditionsWellKnown 4912 } lgpCondId4913HighBatteryStringRippleCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high battery string ripple current condition." ::= { lgpFlexConditionsWellKnown 4913 } lgpCondId4914BatteryStringDischargeDetected OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a battery string discharge condition." ::= { lgpFlexConditionsWellKnown 4914 } lgpCondId4915MaximumDischargeTimeExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected an excessive discharge time condition." ::= { lgpFlexConditionsWellKnown 4915 } lgpCondId4916DischargeLowOverallVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low battery string overall voltage condition during a discharge." ::= { lgpFlexConditionsWellKnown 4916 } lgpCondId4917DischargeLowCellVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low cell voltage condition during a discharge." ::= { lgpFlexConditionsWellKnown 4917 } lgpCondId4918DischargeHighBatteryStringCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high battery string current condition during a discharge." ::= { lgpFlexConditionsWellKnown 4918 } lgpCondId4919ExcessiveCelltoCellTemperatureDeviation OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected an excessive cell to cell temperature deviation condition." ::= { lgpFlexConditionsWellKnown 4919 } lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected an excessive cell to ambient temperature deviation condition." ::= { lgpFlexConditionsWellKnown 4920 } lgpCondId4964LowCellVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low cell voltage condition." ::= { lgpFlexConditionsWellKnown 4964 } lgpCondId4965HighCellVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high cell voltage condition." ::= { lgpFlexConditionsWellKnown 4965 } lgpCondId4966LowCellTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low cell temperature condition." ::= { lgpFlexConditionsWellKnown 4966 } lgpCondId4967HighCellTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high cell temperature condition." ::= { lgpFlexConditionsWellKnown 4967 } lgpCondId4968LowInternalResistance OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low internal resistance condition." ::= { lgpFlexConditionsWellKnown 4968 } lgpCondId4969HighInternalResistance OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high internal resistance condition." ::= { lgpFlexConditionsWellKnown 4969 } lgpCondId4970HighIntercellResistance OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high intercell resistance condition." ::= { lgpFlexConditionsWellKnown 4970 } lgpCondId4978IntertierResistanceHigh OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high intertier resistance condition." ::= { lgpFlexConditionsWellKnown 4978 } lgpCondId4980SupplyChilledWaterLossofFlow OBJECT-IDENTITY STATUS current DESCRIPTION "Supply chilled water flow is too low." ::= { lgpFlexConditionsWellKnown 4980 } lgpCondId4983SupplyRefrigOverTempBand1 OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1]." ::= { lgpFlexConditionsWellKnown 4983 } lgpCondId4986SupplyRefrigUnderTempBand1 OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1]." ::= { lgpFlexConditionsWellKnown 4986 } lgpCondId4990SupplyRefrigOverTempBand2 OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2]." ::= { lgpFlexConditionsWellKnown 4990 } lgpCondId4993SupplyRefrigUnderTempBand2 OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2]." ::= { lgpFlexConditionsWellKnown 4993 } lgpCondId4996Inverter1ShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 4996 } lgpCondId4999Inverter2ShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Inverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 4999 } lgpCondId5015SupplyAirOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Air Temperature] has exceeded [Supply Air Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5015 } lgpCondId5019SupplyAirUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Supply Air Temperature] has dropped below [Supply Air Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5019 } lgpCondId5023ReturnAirOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Return Air Temperature] has exceeded [Return Air Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5023 } lgpCondId5026SupplyAirSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The air sensor at the outlet of the unit is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5026 } lgpCondId5034HighReturnHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "[Return Humidity] has exceeded [High Return Humidity Threshold]." ::= { lgpFlexConditionsWellKnown 5034 } lgpCondId5036LowReturnHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "[Return Humidity] has dropped below [Low Return Humidity Threshold]." ::= { lgpFlexConditionsWellKnown 5036 } lgpCondId5037HumidifierHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "Operating hours for the humidifier have exceeded the threshold." ::= { lgpFlexConditionsWellKnown 5037 } lgpCondId5038DehumidifierHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "Operating hours for the dehumidifier have exceeded the threshold." ::= { lgpFlexConditionsWellKnown 5038 } lgpCondId5039HumidifierUnderCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The electrical current to the humidifier has dropped below its lower threshold." ::= { lgpFlexConditionsWellKnown 5039 } lgpCondId5040HumidifierOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The electrical current to the humidifier has exceeded its upper threshold." ::= { lgpFlexConditionsWellKnown 5040 } lgpCondId5041HumidifierLowWater OBJECT-IDENTITY STATUS current DESCRIPTION "The water level in the humidifier has dropped below its threshold." ::= { lgpFlexConditionsWellKnown 5041 } lgpCondId5042HumidifierCylinderWorn OBJECT-IDENTITY STATUS current DESCRIPTION "Humidifier cylinder is not operating properly and needs to be replaced." ::= { lgpFlexConditionsWellKnown 5042 } lgpCondId5043HumidifierIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Humidifier issue detected, causing it to be locked out." ::= { lgpFlexConditionsWellKnown 5043 } lgpCondId5044ExtHumidifierLockout OBJECT-IDENTITY STATUS current DESCRIPTION "The humidifier is shut down and disabled by an external input signal." ::= { lgpFlexConditionsWellKnown 5044 } lgpCondId5045HumidifierControlBoardNotDetected OBJECT-IDENTITY STATUS current DESCRIPTION "Humidifier control board is required to be connected, but no signal is detected." ::= { lgpFlexConditionsWellKnown 5045 } lgpCondId5046ReturnHumidityOutOfProportionalBand OBJECT-IDENTITY STATUS current DESCRIPTION "[Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time." ::= { lgpFlexConditionsWellKnown 5046 } lgpCondId5053LossofAirFlow OBJECT-IDENTITY STATUS current DESCRIPTION "No air flow through the unit due to failure of all fans." ::= { lgpFlexConditionsWellKnown 5053 } lgpCondId5054FanHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "Operating hours for the unit blower fan have exceeded the threshold." ::= { lgpFlexConditionsWellKnown 5054 } lgpCondId5055TopFanIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The top fan is not operating within its normal parameters." ::= { lgpFlexConditionsWellKnown 5055 } lgpCondId5056BottomFanIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The bottom fan is not operating within its normal parameters." ::= { lgpFlexConditionsWellKnown 5056 } lgpCondId5060RemoteSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Remote sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5060 } lgpCondId5062Compressor1LowSuctionPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 1 low suction pressure." ::= { lgpFlexConditionsWellKnown 5062 } lgpCondId5063Compressor1HoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "Operating hours for compressor 1 have exceeded the threshold." ::= { lgpFlexConditionsWellKnown 5063 } lgpCondId5064DigScrollComp1TempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Digital scroll compressor 1 temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5064 } lgpCondId5065DigScrollComp1OverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "Digital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold." ::= { lgpFlexConditionsWellKnown 5065 } lgpCondId5066Compressor1LowPressureTransducerIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor 1 low pressure transducer is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5066 } lgpCondId5067ExtCompressorLockout OBJECT-IDENTITY STATUS current DESCRIPTION "The compressor is shut down and disabled by an external input signal." ::= { lgpFlexConditionsWellKnown 5067 } lgpCondId5068ReheaterOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The temperature of the reheater has exceeded its threshold." ::= { lgpFlexConditionsWellKnown 5068 } lgpCondId5069ElectricReheater1HoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "Operating hours for electric reheater 1 have exceeded the threshold." ::= { lgpFlexConditionsWellKnown 5069 } lgpCondId5070ExtReheatLockout OBJECT-IDENTITY STATUS current DESCRIPTION "The reheater is shut down and disabled by an external input signal." ::= { lgpFlexConditionsWellKnown 5070 } lgpCondId5071Condenser1Issue OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser 1 is not operating within its normal parameters." ::= { lgpFlexConditionsWellKnown 5071 } lgpCondId5072CondenserVFDIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The condenser fan Variable Frequency Drive is offline." ::= { lgpFlexConditionsWellKnown 5072 } lgpCondId5073CondenserTVSSIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed." ::= { lgpFlexConditionsWellKnown 5073 } lgpCondId5104ExtOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "A temperature has exceeded its threshold, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5104 } lgpCondId5105ExtLossofFlow OBJECT-IDENTITY STATUS current DESCRIPTION "Loss of flow is detected, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5105 } lgpCondId5106ExtCondenserPumpHighWater OBJECT-IDENTITY STATUS current DESCRIPTION "High water is detected in the condenser, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5106 } lgpCondId5107ExtStandbyGlycolPumpOn OBJECT-IDENTITY STATUS current DESCRIPTION "The standby glycol pump is on, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5107 } lgpCondId5108ExternalFireDetected OBJECT-IDENTITY STATUS current DESCRIPTION "Fire detected, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5108 } lgpCondId5109UnitOn OBJECT-IDENTITY STATUS current DESCRIPTION "Unit was turned on." ::= { lgpFlexConditionsWellKnown 5109 } lgpCondId5110UnitOff OBJECT-IDENTITY STATUS current DESCRIPTION "Unit was turned off." ::= { lgpFlexConditionsWellKnown 5110 } lgpCondId5111UnitStandby OBJECT-IDENTITY STATUS current DESCRIPTION "Unit was placed in standby mode." ::= { lgpFlexConditionsWellKnown 5111 } lgpCondId5112UnitPartialShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "An event has occurred requiring some system components to be shutdown and disabled." ::= { lgpFlexConditionsWellKnown 5112 } lgpCondId5113UnitShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system." ::= { lgpFlexConditionsWellKnown 5113 } lgpCondId5114WaterLeakageDetectorSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The water leakage detector sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5114 } lgpCondId5115BMSCommunicationsTimeout OBJECT-IDENTITY STATUS current DESCRIPTION "Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe." ::= { lgpFlexConditionsWellKnown 5115 } lgpCondId5116MaintenanceDue OBJECT-IDENTITY STATUS current DESCRIPTION "The calculated maintenance date has been reached." ::= { lgpFlexConditionsWellKnown 5116 } lgpCondId5117MaintenanceCompleted OBJECT-IDENTITY STATUS current DESCRIPTION "Maintenance has been completed on the unit." ::= { lgpFlexConditionsWellKnown 5117 } lgpCondId5118CloggedAirFilter OBJECT-IDENTITY STATUS current DESCRIPTION "Air filter is dirty and needs to be (cleaned or) replaced." ::= { lgpFlexConditionsWellKnown 5118 } lgpCondId5119RAMBatteryIssue OBJECT-IDENTITY STATUS current DESCRIPTION "RAM or RAM backup battery is not operating correctly." ::= { lgpFlexConditionsWellKnown 5119 } lgpCondId5120MasterUnitCommunicationLost OBJECT-IDENTITY STATUS current DESCRIPTION "Communication with master unit has been lost." ::= { lgpFlexConditionsWellKnown 5120 } lgpCondId5121HighPowerShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "Supply to high power components has been shutdown." ::= { lgpFlexConditionsWellKnown 5121 } lgpCondId5126DigScrollComp2OverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "Digital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold." ::= { lgpFlexConditionsWellKnown 5126 } lgpCondId5144OutputOfUf OBJECT-IDENTITY STATUS current DESCRIPTION "The output frequency has exceeded a specified range for a specified period of time." ::= { lgpFlexConditionsWellKnown 5144 } lgpCondId5145MMSModuleAlarmActive OBJECT-IDENTITY STATUS current DESCRIPTION "Active alarm or fault of any module in a multi-module system." ::= { lgpFlexConditionsWellKnown 5145 } lgpCondId5146CompressorPumpDownIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Unable to pump down suction-side pressure during compressor shutdown." ::= { lgpFlexConditionsWellKnown 5146 } lgpCondId5147ReturnAirSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The air sensor at the inlet of the unit is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5147 } lgpCondId5148CompressorHighPressureTransducerIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor high pressure transducer is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5148 } lgpCondId5149BatteryNotQualified OBJECT-IDENTITY STATUS current DESCRIPTION "The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open." ::= { lgpFlexConditionsWellKnown 5149 } lgpCondId5150BatteryTerminalsReversed OBJECT-IDENTITY STATUS current DESCRIPTION "The measured battery voltage is a negative value due to reverse battery terminal connections." ::= { lgpFlexConditionsWellKnown 5150 } lgpCondId5151BatteryConverterFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module." ::= { lgpFlexConditionsWellKnown 5151 } lgpCondId5152InverterSCROpen OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers." ::= { lgpFlexConditionsWellKnown 5152 } lgpCondId5153LoadSharingFault OBJECT-IDENTITY STATUS current DESCRIPTION "Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current." ::= { lgpFlexConditionsWellKnown 5153 } lgpCondId5154DCBusAbnormal OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected an abnormal DC Bus Voltage." ::= { lgpFlexConditionsWellKnown 5154 } lgpCondId5155MainsInputNeutralLost OBJECT-IDENTITY STATUS current DESCRIPTION "Loss of neutral in the input source is detected." ::= { lgpFlexConditionsWellKnown 5155 } lgpCondId5156LoadImpactTransfer OBJECT-IDENTITY STATUS current DESCRIPTION "On bypass as result of load impact." ::= { lgpFlexConditionsWellKnown 5156 } lgpCondId5157UserOperationInvalid OBJECT-IDENTITY STATUS current DESCRIPTION "User attempted an invalid operation." ::= { lgpFlexConditionsWellKnown 5157 } lgpCondId5158PowerSubModuleFault OBJECT-IDENTITY STATUS current DESCRIPTION "One or more failures detected in power module, inverter or rectifier." ::= { lgpFlexConditionsWellKnown 5158 } lgpCondId5178OutputOvervoltage OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the output phase voltages has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5178 } lgpCondId5179OutputUndervoltage OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the output phase voltages has dropped below the limit." ::= { lgpFlexConditionsWellKnown 5179 } lgpCondId5180OutputOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the phase currents has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5180 } lgpCondId5181NeutralOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system's neutral current has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5181 } lgpCondId5182GroundOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "System ground current has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5182 } lgpCondId5183OutputVoltageTHD OBJECT-IDENTITY STATUS current DESCRIPTION "The Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5183 } lgpCondId5184OutputFrequencyError OBJECT-IDENTITY STATUS current DESCRIPTION "The output frequency is outside a specified range." ::= { lgpFlexConditionsWellKnown 5184 } lgpCondId5185TransformerOvertemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Indicates a unit transformer overtemperature condition." ::= { lgpFlexConditionsWellKnown 5185 } lgpCondId5212PanelSummaryStatus OBJECT-IDENTITY STATUS current DESCRIPTION "The status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event." ::= { lgpFlexConditionsWellKnown 5212 } lgpCondId5213PanelOvervoltage OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the phase voltages of this panel has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5213 } lgpCondId5214PanelUndervoltage OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the phase voltages of this panel is less than the limit." ::= { lgpFlexConditionsWellKnown 5214 } lgpCondId5215PanelOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the phase currents of this panel has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5215 } lgpCondId5216PanelNeutralOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The Neutral current of this panel has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5216 } lgpCondId5217PanelGroundOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The Ground current of this panel has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5217 } lgpCondId5226BranchOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The current in one or more phases of this branch exceeds the limit." ::= { lgpFlexConditionsWellKnown 5226 } lgpCondId5227BranchUndercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The current in one or more phases of this branch is less than the limit." ::= { lgpFlexConditionsWellKnown 5227 } lgpCondId5245SubfeedPhaseOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the phase currents in this subfeed has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5245 } lgpCondId5246SubfeedNeutralOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The Neutral current in this subfeed has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5246 } lgpCondId5247SubfeedGroundOvercurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The Ground current of this subfeed has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5247 } lgpCondId5249EventState OBJECT-IDENTITY STATUS current DESCRIPTION "The present state of this digital event input." ::= { lgpFlexConditionsWellKnown 5249 } lgpCondId5263CompressorNotStopping OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor commanded to stop, but continues to run." ::= { lgpFlexConditionsWellKnown 5263 } lgpCondId5269CompressorHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "[Compressor Hours] has exceeded [Compressor Hours Threshold]." ::= { lgpFlexConditionsWellKnown 5269 } lgpCondId5270CompressorHighHeadPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor is shut down due to high head pressure." ::= { lgpFlexConditionsWellKnown 5270 } lgpCondId5271CompressorLowSuctionPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor is shut down due to low suction pressure." ::= { lgpFlexConditionsWellKnown 5271 } lgpCondId5272CompressorThermalOverload OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor is shut down due to thermal overload." ::= { lgpFlexConditionsWellKnown 5272 } lgpCondId5273CompressorLowOilPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor low oil pressure." ::= { lgpFlexConditionsWellKnown 5273 } lgpCondId5274CompressorHeadPressureOverThreshold OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor head pressure has exceeded an upper threshold." ::= { lgpFlexConditionsWellKnown 5274 } lgpCondId5275CompressorLossofDifferentialPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor is shut down due to low differential pressure." ::= { lgpFlexConditionsWellKnown 5275 } lgpCondId5277CondenserFanIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser fan is not operating within its operational parameters." ::= { lgpFlexConditionsWellKnown 5277 } lgpCondId5278LowCondenserRefrigerantPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Refrigerant pressure in condenser coil is too low." ::= { lgpFlexConditionsWellKnown 5278 } lgpCondId5280LowFluidPressure OBJECT-IDENTITY STATUS current DESCRIPTION "[Fluid Pressure] has dropped below a specified threshold." ::= { lgpFlexConditionsWellKnown 5280 } lgpCondId5293ReturnFluidOverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Return Fluid Temperature] has exceeded a specified threshold." ::= { lgpFlexConditionsWellKnown 5293 } lgpCondId5294ReturnFluidUnderTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Return Fluid Temperature] has dropped below a specified threshold." ::= { lgpFlexConditionsWellKnown 5294 } lgpCondId5295ReturnFluidTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The return fluid temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5295 } lgpCondId5296TeamworkReturnFluidTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range." ::= { lgpFlexConditionsWellKnown 5296 } lgpCondId5297AllPumpsLossofFlow OBJECT-IDENTITY STATUS current DESCRIPTION "System is shut down due to loss of flow in all available pumps." ::= { lgpFlexConditionsWellKnown 5297 } lgpCondId5300PumpHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "[Pump Hours] has exceeded [Pump Hours Threshold]." ::= { lgpFlexConditionsWellKnown 5300 } lgpCondId5306FreeCoolingValveHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]." ::= { lgpFlexConditionsWellKnown 5306 } lgpCondId5308EvaporatorInletTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The evaporator inlet temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5308 } lgpCondId5309TeamworkEvaporatorInletTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range." ::= { lgpFlexConditionsWellKnown 5309 } lgpCondId5310EvaporatorFluidFreezeAutoReset OBJECT-IDENTITY STATUS current DESCRIPTION "Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold." ::= { lgpFlexConditionsWellKnown 5310 } lgpCondId5311EvaporatorFluidFreezeManualResetRequired OBJECT-IDENTITY STATUS current DESCRIPTION "Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset." ::= { lgpFlexConditionsWellKnown 5311 } lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss OBJECT-IDENTITY STATUS current DESCRIPTION "While subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log." ::= { lgpFlexConditionsWellKnown 5315 } lgpCondId5335ReturnAirUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Return Air Temperature] has dropped below [Return Air Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5335 } lgpCondId5349ExtAirSensorAHighHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]." ::= { lgpFlexConditionsWellKnown 5349 } lgpCondId5351ExtAirSensorALowHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]." ::= { lgpFlexConditionsWellKnown 5351 } lgpCondId5352CompressorShortCycle OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period." ::= { lgpFlexConditionsWellKnown 5352 } lgpCondId5354DigScrollCompDischargeTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5354 } lgpCondId5355DigScrollCompOverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "Digital scroll compressor is shut down due to head temperature exceeding an upper threshold." ::= { lgpFlexConditionsWellKnown 5355 } lgpCondId5361ExtFreeCoolingLockout OBJECT-IDENTITY STATUS current DESCRIPTION "Free cooling is disabled by an external input signal." ::= { lgpFlexConditionsWellKnown 5361 } lgpCondId5362FreeCoolingTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The free cooling fluid temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5362 } lgpCondId5365HotWaterHotGasValveHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]." ::= { lgpFlexConditionsWellKnown 5365 } lgpCondId5368ElectricReheaterHoursExceeded OBJECT-IDENTITY STATUS current DESCRIPTION "[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]." ::= { lgpFlexConditionsWellKnown 5368 } lgpCondId5376MainFanOverload OBJECT-IDENTITY STATUS current DESCRIPTION "Main fan is shut down due to thermal overload." ::= { lgpFlexConditionsWellKnown 5376 } lgpCondId5377Condenser OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser is not operating within its operational parameters." ::= { lgpFlexConditionsWellKnown 5377 } lgpCondId5415ExtLossofAirBlower OBJECT-IDENTITY STATUS current DESCRIPTION "Loss of air blower is detected, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5415 } lgpCondId5416ExtStandbyUnitOn OBJECT-IDENTITY STATUS current DESCRIPTION "Standby unit is on, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5416 } lgpCondId5417DigitalOutputBoardNotDetected OBJECT-IDENTITY STATUS current DESCRIPTION "Digital output board is required to be connected, but no signal is detected." ::= { lgpFlexConditionsWellKnown 5417 } lgpCondId5418UnitCodeMissing OBJECT-IDENTITY STATUS current DESCRIPTION "Unit code has not been entered and saved." ::= { lgpFlexConditionsWellKnown 5418 } lgpCondId5419UnitCommunicationLost OBJECT-IDENTITY STATUS current DESCRIPTION "Master has lost communication with one or more networked units." ::= { lgpFlexConditionsWellKnown 5419 } lgpCondId5422OvertemperaturePowerOff OBJECT-IDENTITY STATUS current DESCRIPTION "Power turned off because equipment over temperature limit." ::= { lgpFlexConditionsWellKnown 5422 } lgpCondId5423TooManySensors OBJECT-IDENTITY STATUS current DESCRIPTION "The number of sensors connected to the PDU exceeds the allowable limit." ::= { lgpFlexConditionsWellKnown 5423 } lgpCondId5432TransformerOvertemperaturePowerOff OBJECT-IDENTITY STATUS current DESCRIPTION "Output power shutdown due to high transformer temperature." ::= { lgpFlexConditionsWellKnown 5432 } lgpCondId5433TransformerOvertemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Transformer temperature has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5433 } lgpCondId5434TransformerTemperatureSensorFail OBJECT-IDENTITY STATUS current DESCRIPTION "Transformer temperature sensor has failed." ::= { lgpFlexConditionsWellKnown 5434 } lgpCondId5436LowAmbientTemperatureProbeTwo OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low ambient temperature condition on temperature probe 2." ::= { lgpFlexConditionsWellKnown 5436 } lgpCondId5437HighAmbientTemperatureProbeTwo OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a high ambient temperature condition on temperature probe 2." ::= { lgpFlexConditionsWellKnown 5437 } lgpCondId5438ThermalRunawayDetected OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a thermal runaway condition." ::= { lgpFlexConditionsWellKnown 5438 } lgpCondId5439BatteryStringEqualize OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a battery string equalize condition." ::= { lgpFlexConditionsWellKnown 5439 } lgpCondId5440BatteryStringOffline OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected the battery string is offline." ::= { lgpFlexConditionsWellKnown 5440 } lgpCondId5442DischargeLowCellVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a low cell voltage condition during a discharge." ::= { lgpFlexConditionsWellKnown 5442 } lgpCondId5447MMSPowerSharing OBJECT-IDENTITY STATUS current DESCRIPTION "A module is not sharing power with the other modules in a multi -module system." ::= { lgpFlexConditionsWellKnown 5447 } lgpCondId5453ModuleInStandbyIntelligentParalleling OBJECT-IDENTITY STATUS current DESCRIPTION "Module is placed into standby operation per Intelligent Paralleling." ::= { lgpFlexConditionsWellKnown 5453 } lgpCondId5456ECOModeActive OBJECT-IDENTITY STATUS current DESCRIPTION "Conditions for Activation or Automatic Reactivation have been satisfied." ::= { lgpFlexConditionsWellKnown 5456 } lgpCondId5457ECOModeSuspended OBJECT-IDENTITY STATUS current DESCRIPTION "ECO Mode session is suspended." ::= { lgpFlexConditionsWellKnown 5457 } lgpCondId5458ExcessECOSuspends OBJECT-IDENTITY STATUS current DESCRIPTION "Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting." ::= { lgpFlexConditionsWellKnown 5458 } lgpCondId5471DoorOpen OBJECT-IDENTITY STATUS current DESCRIPTION "An open door was detected." ::= { lgpFlexConditionsWellKnown 5471 } lgpCondId5472DoorSensorDisconnected OBJECT-IDENTITY STATUS current DESCRIPTION "Door sensor disconnect detected." ::= { lgpFlexConditionsWellKnown 5472 } lgpCondId5479ContactClosureOpen OBJECT-IDENTITY STATUS current DESCRIPTION "An open circuit was detected." ::= { lgpFlexConditionsWellKnown 5479 } lgpCondId5480ContactClosureClosed OBJECT-IDENTITY STATUS current DESCRIPTION "A closed circuit was detected." ::= { lgpFlexConditionsWellKnown 5480 } lgpCondId5492ExtSystemCondensationDetected OBJECT-IDENTITY STATUS current DESCRIPTION "External system condensation detected." ::= { lgpFlexConditionsWellKnown 5492 } lgpCondId5495ExtFanIssue OBJECT-IDENTITY STATUS current DESCRIPTION "One or more fans are not operating within their operational parameters." ::= { lgpFlexConditionsWellKnown 5495 } lgpCondId5500ExtRemoteShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "Unit is shut down by a remote signal." ::= { lgpFlexConditionsWellKnown 5500 } lgpCondId5505HotAisleTempOutofRange OBJECT-IDENTITY STATUS current DESCRIPTION "The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5505 } lgpCondId5508ColdAisleTempOutofRange OBJECT-IDENTITY STATUS current DESCRIPTION "The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5508 } lgpCondId5512RemoteShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "Unit is shut down by a remote signal." ::= { lgpFlexConditionsWellKnown 5512 } lgpCondId5513CompressorCapacityReduced OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor capacity has been reduced." ::= { lgpFlexConditionsWellKnown 5513 } lgpCondId5514CompressorLowPressureTransducerIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor low pressure transducer is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5514 } lgpCondId5524PDUNeutralOverCurrent OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a neutral over current condition." ::= { lgpFlexConditionsWellKnown 5524 } lgpCondId5531CondenserCommunicationLost OBJECT-IDENTITY STATUS current DESCRIPTION "Communication with condenser unit has been lost." ::= { lgpFlexConditionsWellKnown 5531 } lgpCondId5535CondenserOutsideAirTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser outside air temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5535 } lgpCondId5536CondenserOutsideAirTempOutofOperatingRange OBJECT-IDENTITY STATUS current DESCRIPTION "[Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold." ::= { lgpFlexConditionsWellKnown 5536 } lgpCondId5537CondenserControlBoardIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The condenser control board is reporting an issue." ::= { lgpFlexConditionsWellKnown 5537 } lgpCondId5539CondenserRefrigerantPressureOverThreshold OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser refrigerant pressure has exceeded a threshold." ::= { lgpFlexConditionsWellKnown 5539 } lgpCondId5540CondenserRefrigerantPressureUnderThreshold OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser refrigerant pressure has dropped below a threshold." ::= { lgpFlexConditionsWellKnown 5540 } lgpCondId5541CondenserRefrigerantPressureSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser refrigerant pressure sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5541 } lgpCondId5542CondenserSupplyRefrigerantOverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser supply refrigerant temperature has exceeded a threshold." ::= { lgpFlexConditionsWellKnown 5542 } lgpCondId5543CondenserSupplyRefrigerantUnderTemp OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser supply refrigerant temperature has dropped below a specified threshold." ::= { lgpFlexConditionsWellKnown 5543 } lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5544 } lgpCondId5545CondenserMaxFanSpeedOverride OBJECT-IDENTITY STATUS current DESCRIPTION "Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition." ::= { lgpFlexConditionsWellKnown 5545 } lgpCondId5559EvaporatorReturnFluidOverTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold." ::= { lgpFlexConditionsWellKnown 5559 } lgpCondId5560EvaporatorReturnFluidUnderTemp OBJECT-IDENTITY STATUS current DESCRIPTION "[Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold." ::= { lgpFlexConditionsWellKnown 5560 } lgpCondId5561LBSActiveMaster OBJECT-IDENTITY STATUS current DESCRIPTION "This UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system." ::= { lgpFlexConditionsWellKnown 5561 } lgpCondId5562LBSActiveSlave OBJECT-IDENTITY STATUS current DESCRIPTION "This UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system." ::= { lgpFlexConditionsWellKnown 5562 } lgpCondId5563DCBusLowFault OBJECT-IDENTITY STATUS current DESCRIPTION "The DC Bus voltage has reached a critical low level." ::= { lgpFlexConditionsWellKnown 5563 } lgpCondId5564FanContactorOpen OBJECT-IDENTITY STATUS current DESCRIPTION "The fan contactor is open." ::= { lgpFlexConditionsWellKnown 5564 } lgpCondId5565FanContactorOpenFail OBJECT-IDENTITY STATUS current DESCRIPTION "The fan contactor failed to open." ::= { lgpFlexConditionsWellKnown 5565 } lgpCondId5566FanContactorCloseFail OBJECT-IDENTITY STATUS current DESCRIPTION "The fan contactor failed to close." ::= { lgpFlexConditionsWellKnown 5566 } lgpCondId5567IPInhibit OBJECT-IDENTITY STATUS current DESCRIPTION "The intelligent paralleling operation is inhibited." ::= { lgpFlexConditionsWellKnown 5567 } lgpCondId5568InputUndervoltage OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the input phase voltages has dropped below the limit." ::= { lgpFlexConditionsWellKnown 5568 } lgpCondId5569InputOvervoltage OBJECT-IDENTITY STATUS current DESCRIPTION "One or more of the input phase voltages has exceeded the limit." ::= { lgpFlexConditionsWellKnown 5569 } lgpCondId5573AmbientAirSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Ambient air sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5573 } lgpCondId5577ExtDewPointUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5577 } lgpCondId5578DewPointOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Dew point temperature reading has exceeded the upper threshold." ::= { lgpFlexConditionsWellKnown 5578 } lgpCondId5579DewPointUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Dew point temperature reading has dropped below the lower threshold." ::= { lgpFlexConditionsWellKnown 5579 } lgpCondId5588UnspecifiedGeneralEvent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more unspecified events active. See local unit display for further details." ::= { lgpFlexConditionsWellKnown 5588 } lgpCondId5593RemoteSensorAverageOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5593 } lgpCondId5594RemoteSensorAverageUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5594 } lgpCondId5595RemoteSensorSystemAverageOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5595 } lgpCondId5596RemoteSensorSystemAverageUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5596 } lgpCondId5597RemoteSensorOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5597 } lgpCondId5598RemoteSensorUnderTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "[Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]." ::= { lgpFlexConditionsWellKnown 5598 } lgpCondId5600AirEconomizerEmergencyOverride OBJECT-IDENTITY STATUS current DESCRIPTION "Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling." ::= { lgpFlexConditionsWellKnown 5600 } lgpCondId5601AirEconomizerReducedAirflow OBJECT-IDENTITY STATUS current DESCRIPTION "Air economizer filter is dirty and needs to be cleaned or replaced." ::= { lgpFlexConditionsWellKnown 5601 } lgpCondId5604CompressorSuperheatOverThreshold OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor discharge refrigerant superheat temperature has exceeded an upper threshold." ::= { lgpFlexConditionsWellKnown 5604 } lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent OBJECT-IDENTITY STATUS current DESCRIPTION "The delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold." ::= { lgpFlexConditionsWellKnown 5609 } lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent OBJECT-IDENTITY STATUS current DESCRIPTION "The delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold." ::= { lgpFlexConditionsWellKnown 5610 } lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent OBJECT-IDENTITY STATUS current DESCRIPTION "The Battery-String charger current has exceeded the thermal runaway charger current level one threshold." ::= { lgpFlexConditionsWellKnown 5611 } lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent OBJECT-IDENTITY STATUS current DESCRIPTION "The Battery-String charger current has exceeded the thermal runaway charger current level two threshold." ::= { lgpFlexConditionsWellKnown 5612 } lgpCondId5617TemperatureControlSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The air sensor selected for cooling control is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5617 } lgpCondId5621EEVSuperheatBelowThreshold OBJECT-IDENTITY STATUS current DESCRIPTION "Electronic expansion valve refrigerant low superheat event." ::= { lgpFlexConditionsWellKnown 5621 } lgpCondId5622EEVDischargeTempAboveThreshold OBJECT-IDENTITY STATUS current DESCRIPTION "Electronic expansion valve refrigerant high discharge temperature event." ::= { lgpFlexConditionsWellKnown 5622 } lgpCondId5623EEVBatteryIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Electronic expansion valve battery cannot be recharged and needs to be replaced." ::= { lgpFlexConditionsWellKnown 5623 } lgpCondId5624EEVPowerIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Electronic expansion valve lost power and is running on battery backup." ::= { lgpFlexConditionsWellKnown 5624 } lgpCondId5625EEVUnspecifiedGeneralEvent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more unspecified electronic expansion valve events active. See local unit display for further details." ::= { lgpFlexConditionsWellKnown 5625 } lgpCondId5629StaticPressureSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The static pressure sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5629 } lgpCondId5630HighStaticPressure OBJECT-IDENTITY STATUS current DESCRIPTION "High static pressure event." ::= { lgpFlexConditionsWellKnown 5630 } lgpCondId5631LowStaticPressure OBJECT-IDENTITY STATUS current DESCRIPTION "Low static pressure event." ::= { lgpFlexConditionsWellKnown 5631 } lgpCondId5636PumpUnspecifiedGeneralEvent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more unspecified pump events active. See local unit display for further details." ::= { lgpFlexConditionsWellKnown 5636 } lgpCondId5637CondenserUnitUnspecifiedGeneralEvent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more unspecified condenser unit events active. See local unit display for further details." ::= { lgpFlexConditionsWellKnown 5637 } lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more unspecified condenser circuit events active. See local unit display for further details." ::= { lgpFlexConditionsWellKnown 5638 } lgpCondId5642SFAReservedEvent1 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5642 } lgpCondId5643SFAReservedEvent2 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5643 } lgpCondId5644SFAReservedEvent3 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5644 } lgpCondId5645SFAReservedEvent4 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5645 } lgpCondId5646SFAReservedEvent5 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5646 } lgpCondId5647SFAReservedEvent6 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5647 } lgpCondId5648SFAReservedEvent7 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5648 } lgpCondId5649SFAReservedEvent8 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5649 } lgpCondId5650SFAReservedEvent9 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5650 } lgpCondId5651SFAReservedEvent10 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5651 } lgpCondId5652SFAReservedEvent11 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5652 } lgpCondId5653SFAReservedEvent12 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5653 } lgpCondId5654SFAReservedEvent13 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5654 } lgpCondId5655SFAReservedEvent14 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5655 } lgpCondId5656SFAReservedEvent15 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5656 } lgpCondId5657SFAReservedEvent16 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5657 } lgpCondId5658SFAReservedEvent17 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5658 } lgpCondId5659SFAReservedEvent18 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5659 } lgpCondId5660SFAReservedEvent19 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5660 } lgpCondId5661SFAReservedEvent20 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5661 } lgpCondId5662SFAReservedEvent21 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5662 } lgpCondId5663SFAReservedEvent22 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5663 } lgpCondId5664SFAReservedEvent23 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5664 } lgpCondId5665SFAReservedEvent24 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5665 } lgpCondId5666SFAReservedEvent25 OBJECT-IDENTITY STATUS current DESCRIPTION "Reserved event for SFA use." ::= { lgpFlexConditionsWellKnown 5666 } lgpCondId5768OutletAirOvertemperatureLimit OBJECT-IDENTITY STATUS current DESCRIPTION "The difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature." ::= { lgpFlexConditionsWellKnown 5768 } lgpCondId5769EMOShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "An Emergency Module Off command has been detected." ::= { lgpFlexConditionsWellKnown 5769 } lgpCondId5770TopOutletFanFault OBJECT-IDENTITY STATUS current DESCRIPTION "Top outlet fan fault - one or more top outlet fans have failed." ::= { lgpFlexConditionsWellKnown 5770 } lgpCondId5771MMSOverCapacity OBJECT-IDENTITY STATUS current DESCRIPTION "The multi-module system load is larger than the apparent power limit setting." ::= { lgpFlexConditionsWellKnown 5771 } lgpCondId5773CompressorCapacityNormal OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor has returned to normal load capacity." ::= { lgpFlexConditionsWellKnown 5773 } lgpCondId5774CompressorContactorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor contactor is not closing during compressor startup or is not opening during compressor shutdown." ::= { lgpFlexConditionsWellKnown 5774 } lgpCondId5775UnitShutdownUnspecifiedGeneralEvent OBJECT-IDENTITY STATUS current DESCRIPTION "One or more unspecified unit shutdown events active. See local unit display for further details." ::= { lgpFlexConditionsWellKnown 5775 } lgpCondId5776PDULowVoltageLN OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under voltage condition (LN)." ::= { lgpFlexConditionsWellKnown 5776 } lgpCondId5777PDULowVoltageLL OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under voltage condition (LL)." ::= { lgpFlexConditionsWellKnown 5777 } lgpCondId5778PDULowVoltageL1L2 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a line-to-line under voltage condition (L1 -L2)." ::= { lgpFlexConditionsWellKnown 5778 } lgpCondId5779PDULowVoltageL2L3 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a line-to-line under voltage condition (L2 -L3)." ::= { lgpFlexConditionsWellKnown 5779 } lgpCondId5780PDULowVoltageL3L1 OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a line-to-line under voltage condition (L3 -L1)." ::= { lgpFlexConditionsWellKnown 5780 } lgpCondId5781PDULowVoltageL1N OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a line to neutral under voltage condition (L1-N)." ::= { lgpFlexConditionsWellKnown 5781 } lgpCondId5782PDULowVoltageL2N OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a line to neutral under voltage condition (L2-N)." ::= { lgpFlexConditionsWellKnown 5782 } lgpCondId5783PDULowVoltageL3N OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a line to neutral under voltage condition (L3-N)." ::= { lgpFlexConditionsWellKnown 5783 } lgpCondId5784BranchLowVoltageLN OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under voltage condition (LN)." ::= { lgpFlexConditionsWellKnown 5784 } lgpCondId5785BranchLowVoltageLL OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under voltage condition (LL)." ::= { lgpFlexConditionsWellKnown 5785 } lgpCondId5786BranchLowVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a module under voltage condition." ::= { lgpFlexConditionsWellKnown 5786 } lgpCondId5788ContTieActive OBJECT-IDENTITY STATUS current DESCRIPTION "Continuous Power Tie Active." ::= { lgpFlexConditionsWellKnown 5788 } lgpCondId5792UserkWhReset OBJECT-IDENTITY STATUS current DESCRIPTION "The user kWh accumulator was reset to zero by the operator." ::= { lgpFlexConditionsWellKnown 5792 } lgpCondId5796PeakkWReset OBJECT-IDENTITY STATUS current DESCRIPTION "The Peak kW was reset." ::= { lgpFlexConditionsWellKnown 5796 } lgpCondId5798BypassOverload OBJECT-IDENTITY STATUS current DESCRIPTION "Bypass overloaded, reduce load immediately." ::= { lgpFlexConditionsWellKnown 5798 } lgpCondId5801LowBatteryShutdownImminent OBJECT-IDENTITY STATUS current DESCRIPTION "If active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS." ::= { lgpFlexConditionsWellKnown 5801 } lgpCondId5806OutputOverload OBJECT-IDENTITY STATUS current DESCRIPTION "An overload exists on the output." ::= { lgpFlexConditionsWellKnown 5806 } lgpCondId5807OutputOffPending OBJECT-IDENTITY STATUS current DESCRIPTION "Output off pending - shutdown imminent." ::= { lgpFlexConditionsWellKnown 5807 } lgpCondId5808SystemShutdownOutputShort OBJECT-IDENTITY STATUS current DESCRIPTION "Shutdown was due to a short on the output." ::= { lgpFlexConditionsWellKnown 5808 } lgpCondId5809SystemShutdownLowBattery OBJECT-IDENTITY STATUS current DESCRIPTION "Shutdown was due to a low battery condition." ::= { lgpFlexConditionsWellKnown 5809 } lgpCondId5810SystemShutdownRemoteShutdown OBJECT-IDENTITY STATUS current DESCRIPTION "Shutdown was due to a remote communications shutdown command." ::= { lgpFlexConditionsWellKnown 5810 } lgpCondId5811SystemShutdownHardwareFault OBJECT-IDENTITY STATUS current DESCRIPTION "Shutdown was due to an externally applied hardware control signal." ::= { lgpFlexConditionsWellKnown 5811 } lgpCondId5817LossofRedundancy OBJECT-IDENTITY STATUS current DESCRIPTION "The system has an insufficient number of power modules to provide redundancy." ::= { lgpFlexConditionsWellKnown 5817 } lgpCondId5818PowerModuleFailure OBJECT-IDENTITY STATUS current DESCRIPTION "One or more conditions indicate a power module failure, service is required." ::= { lgpFlexConditionsWellKnown 5818 } lgpCondId5819PowerModuleWarning OBJECT-IDENTITY STATUS current DESCRIPTION "One or more power modules is reporting a warning condition." ::= { lgpFlexConditionsWellKnown 5819 } lgpCondId5838PowerModuleFanFault OBJECT-IDENTITY STATUS current DESCRIPTION "The Power Module has detected a fan fault." ::= { lgpFlexConditionsWellKnown 5838 } lgpCondId5839PowerModuleOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The Power Module has detected an over temperature condition." ::= { lgpFlexConditionsWellKnown 5839 } lgpCondId5840PowerModuleShutdownOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Power Module has shutdown due to over temperature." ::= { lgpFlexConditionsWellKnown 5840 } lgpCondId5842ChargerModuleFanFault OBJECT-IDENTITY STATUS current DESCRIPTION "The Charger Module has detected a fan fault." ::= { lgpFlexConditionsWellKnown 5842 } lgpCondId5847BatteryModuleTemperatureSensorFault OBJECT-IDENTITY STATUS current DESCRIPTION "A Battery Module temperature sensor fault has been detected." ::= { lgpFlexConditionsWellKnown 5847 } lgpCondId5848BatteryModuleOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The Battery Module has detected an over temperature condition." ::= { lgpFlexConditionsWellKnown 5848 } lgpCondId5849ReplaceBatteryModule OBJECT-IDENTITY STATUS current DESCRIPTION "The Battery Module needs to be replaced." ::= { lgpFlexConditionsWellKnown 5849 } lgpCondId5850SystemShutdownTransformerOverTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "System shutdown due to transformer over temperature." ::= { lgpFlexConditionsWellKnown 5850 } lgpCondId5851MaximumLoadAlarm OBJECT-IDENTITY STATUS current DESCRIPTION "Maximum load alarm indicating load setting has been exceeded." ::= { lgpFlexConditionsWellKnown 5851 } lgpCondId5856BatteryModuleFault OBJECT-IDENTITY STATUS current DESCRIPTION "One or more battery modules are reporting a fault condition." ::= { lgpFlexConditionsWellKnown 5856 } lgpCondId5857BatteryModuleWarning OBJECT-IDENTITY STATUS current DESCRIPTION "One or more battery modules are reporting a warning condition." ::= { lgpFlexConditionsWellKnown 5857 } lgpCondId5862CheckAirFilter OBJECT-IDENTITY STATUS current DESCRIPTION "Please check air filter, it may need to be cleaned or replaced." ::= { lgpFlexConditionsWellKnown 5862 } lgpCondId5863TransformerFanFault OBJECT-IDENTITY STATUS current DESCRIPTION "The transformer fan has failed." ::= { lgpFlexConditionsWellKnown 5863 } lgpCondId5865NoLoadWarning OBJECT-IDENTITY STATUS current DESCRIPTION "Indicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay]." ::= { lgpFlexConditionsWellKnown 5865 } lgpCondId5871BatteryOverTemperatureLimit OBJECT-IDENTITY STATUS current DESCRIPTION "A battery temperature sensor is reporting a value above a predetermined limit." ::= { lgpFlexConditionsWellKnown 5871 } lgpCondId5873UnexpectedMainBatteryDisconnectClosure OBJECT-IDENTITY STATUS current DESCRIPTION "The main battery disconnect has closed unexpectedly." ::= { lgpFlexConditionsWellKnown 5873 } lgpCondId5874BatteryOverVoltage OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected that the battery voltage has exceeded a predetermined limit." ::= { lgpFlexConditionsWellKnown 5874 } lgpCondId5875BatteryFuseFault OBJECT-IDENTITY STATUS current DESCRIPTION "One or more battery fuse faults has occurred." ::= { lgpFlexConditionsWellKnown 5875 } lgpCondId5878MainBatteryDisconnectForcedToUnlock OBJECT-IDENTITY STATUS current DESCRIPTION "The main battery disconnect is forced to the unlocked state." ::= { lgpFlexConditionsWellKnown 5878 } lgpCondId5879VdcBackfeed OBJECT-IDENTITY STATUS current DESCRIPTION "The voltage between battery and DC bus measurements is out of tolerance." ::= { lgpFlexConditionsWellKnown 5879 } lgpCondId5880RectifierConfigurationChangeRequest OBJECT-IDENTITY STATUS current DESCRIPTION "This event indicates that the battery is not configured and PFC is not enabled." ::= { lgpFlexConditionsWellKnown 5880 } lgpCondId5881RegenerationActive OBJECT-IDENTITY STATUS current DESCRIPTION "Regeneration operation is active." ::= { lgpFlexConditionsWellKnown 5881 } lgpCondId5882RegenerationOperationTerminated OBJECT-IDENTITY STATUS current DESCRIPTION "Regeneration operation is not active." ::= { lgpFlexConditionsWellKnown 5882 } lgpCondId5883RegenerationOperationFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Regeneration operation has been terminated due to bypass source instability or unit misoperation." ::= { lgpFlexConditionsWellKnown 5883 } lgpCondId5884ProgramInputContact01 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5884 } lgpCondId5885ProgramInputContact02 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5885 } lgpCondId5886ProgramInputContact03 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5886 } lgpCondId5887ProgramInputContact04 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5887 } lgpCondId5888ProgramInputContact05 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5888 } lgpCondId5889ProgramInputContact06 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5889 } lgpCondId5890ProgramInputContact07 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5890 } lgpCondId5891ProgramInputContact08 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5891 } lgpCondId5892ProgramInputContact09 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5892 } lgpCondId5893ProgramInputContact10 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5893 } lgpCondId5894ProgramInputContact11 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5894 } lgpCondId5895ProgramInputContact12 OBJECT-IDENTITY STATUS current DESCRIPTION "When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed." ::= { lgpFlexConditionsWellKnown 5895 } lgpCondId5896GroundFaultDetected OBJECT-IDENTITY STATUS current DESCRIPTION "The system has detected a ground fault on a Battery-String." ::= { lgpFlexConditionsWellKnown 5896 } lgpCondId5902ReturnHumiditySensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The humidity sensor at the inlet of the unit is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5902 } lgpCondId5903CompressorLowDifferentialPressureLockout OBJECT-IDENTITY STATUS current DESCRIPTION "Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled." ::= { lgpFlexConditionsWellKnown 5903 } lgpCondId5906AirflowSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Airflow sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5906 } lgpCondId5907ExtAirDamperPositionIssue OBJECT-IDENTITY STATUS current DESCRIPTION "Air damper position does not match expected value, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5907 } lgpCondId5908ExtPowerSourceAFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Unit main power source A failure, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5908 } lgpCondId5909ExtPowerSourceBFailure OBJECT-IDENTITY STATUS current DESCRIPTION "Unit main power source B failure, as indicated by an external input signal." ::= { lgpFlexConditionsWellKnown 5909 } lgpCondId5910StaticPressureSensorOutofRange OBJECT-IDENTITY STATUS current DESCRIPTION "Static pressure sensor signal is out of its configured range." ::= { lgpFlexConditionsWellKnown 5910 } lgpCondId5911FluidTemperatureSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The fluid temperature sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5911 } lgpCondId5912FluidFlowSensorIssue OBJECT-IDENTITY STATUS current DESCRIPTION "The fluid flow sensor is disconnected or the signal is out of range." ::= { lgpFlexConditionsWellKnown 5912 } lgpCondId5914OverDifferentialPressure OBJECT-IDENTITY STATUS current DESCRIPTION "An over differential pressure condition was detected." ::= { lgpFlexConditionsWellKnown 5914 } lgpCondId5915UnderDifferentialPressure OBJECT-IDENTITY STATUS current DESCRIPTION "An under differential pressure condition was detected." ::= { lgpFlexConditionsWellKnown 5915 } lgpCondId5924MixedModeLockout OBJECT-IDENTITY STATUS current DESCRIPTION "Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit." ::= { lgpFlexConditionsWellKnown 5924 } END